Commissioning
Mono Power Unit BUM 62, 63, 64
61
Baumüller Nürnberg GmbH
5.94005.12
6.7
Voltage failure
y
BUM 62
It is possible to enable an automatic restart of the mono supply unit after a voltage failure.
For that purpose
Sub-unit terminal X99AB
Terminal no. 5:to +24 V
Terminal no. 6:to ground 24 V
corresponds to reset (error memory).
- "In the case of voltage failure (intermediate circuit voltage lower than 300 V) the mono unit generates
the message voltage failure (power error H2).
"The unit's "ready for use" signal is taken away.
"The message voltage failure is deleted automatically if the mains voltage returns. The unit's status is
now "ready for use".
y
BUM 63 / 64
In the case of voltage failure the "ready for use" signal is taken away.
- If the mains voltage returns is the unit’s status "ready for use" again.
Содержание BUM 62
Страница 1: ...E 5 94005 12 Manual Mono Power Unit BUM 62 63 64 ...
Страница 8: ...Safety Notes 8 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical Data 10 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 2 1 2 Block diagram BUM 62 ...
Страница 14: ...Technical Data 14 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 16: ...Transportation Unpacking 16 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 28: ...Installation 28 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 40: ...Installation 40 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 5 5 2 Terminal diagram BUM 63 ...
Страница 41: ...Installation Mono Power Unit BUM 62 63 64 41 Baumüller Nürnberg GmbH 5 94005 12 5 5 3 Terminal diagram BUM 64 ...
Страница 62: ...Commissioning 62 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 66: ...Maintenance 66 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 73: ......