Assembly
Mono Power Unit BUM 62, 63, 64
21
Baumüller Nürnberg GmbH
5.94005.12
4.2
Assembly information
y
The units must be installed in the switch cabinet vertically. Several units must be installed side by
side.
y
Ventilation must be from bottom to top.
y
Unrestricted ventilation must be guaranteed.
y
A space of at least
BUM 62100 mm
BUM 63, 64150 mm
must be left above and below the units, and sufficient cool air and air circulation is to be provided.
y
Coolant temperature 50 mm under the units, up to 45 °C. With higher temperatures (up to max.
55 °C), power output of the units must be reduced by 3 % per K.
y
Do not locate any additional sources of heat above or below the units.
y
You must avoid degrees of contamination 3 and 4 according to provisional standard EN 50178:1994
Section 5.2.15.2. The devices are suitable for use in enclosed workshops (VDE 0558 Part 1a, Sec-
tions 5.4.3.2.1 and 5.4.3.2.2).
WARNING
Not appropriate heave can lead to injury or damage. The unit must be heaved by appropriate device
and with qualified personnel.
WARNING
The following measures must be strictly observed to avoid the danger of device overheating.
Содержание BUM 62
Страница 1: ...E 5 94005 12 Manual Mono Power Unit BUM 62 63 64 ...
Страница 8: ...Safety Notes 8 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 10: ...Technical Data 10 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 2 1 2 Block diagram BUM 62 ...
Страница 14: ...Technical Data 14 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 2 3 Type code ...
Страница 16: ...Transportation Unpacking 16 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 28: ...Installation 28 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 40: ...Installation 40 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH 5 5 2 Terminal diagram BUM 63 ...
Страница 41: ...Installation Mono Power Unit BUM 62 63 64 41 Baumüller Nürnberg GmbH 5 94005 12 5 5 3 Terminal diagram BUM 64 ...
Страница 62: ...Commissioning 62 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 66: ...Maintenance 66 Mono Power Unit BUM 62 63 64 5 94005 12 Baumüller Nürnberg GmbH ...
Страница 73: ......