Valid for FlexTop™ 2202 / 2211 / 2221 

The FlexProgrammer configuration unit must not be connected to the 
FlexTop within the hazardous area. 

Configuration procedure: 

a.  Disconnect mains from the 4...20 mA loop circuit 
b.  Disconnect the product from the circuitry within the hazardous area 
c.  Bring the product to the safe area 
d.  Connect the FlexProgrammer and perform the configuration 
e.  Reinstall the product in the hazardous area 
f.  Connect the power supply to the circuit 

Valid for FlexTop™ 2221 only 

Configuration for the FlexTop™ 2221 can be made within the hazardous 
area by means of a handheld HART configurator, providing the precau-
tions and guidelines described in the product’s manual are observed. 

www.baumer.com 

Page 1 / 16 

 

2019

-10

-2

9

  

  

Des

ig

n

 a

nd

 sp

e

ci

fica

tio

n

s su

b

je

ct 

to

 ch

a

n

ge

 w

ith

o

u

t n

o

tice

 

CombiTemp™ TCR6 is a temperature sensor, based on RTD technolo-
gy, which is designed and produced to meet the requirements in general     
industry where threaded connections are used. 

CombiTemp™ TCR6 comprises a series of basic elements which can be 
combined in various ways to a CombiTemp TCR6 temperature sensor. 
The product offers great flexibility in respect to modification, service and 
maintenance. 

The sensor can be made to feature a RTD output signal or with a built in 
FlexTop™ temperature transmitter types 2202, 2211, 2221 with 4-20 mA 
output and the type 2231 with Profibus output (for documentation of 
FlexTops, please see relevant data sheet or operating instructions). 

 

Description

 

Safety instructions 

This instrument is built and tested according to the current EU-directives 
and packed in technically safe conditions. In order to maintain this condi-
tion and to ensure safe operation, the user must follow the hints and 
warnings given in this instruction.  

During the installation the valid national rules have to be observed. Ig-
noring the warnings may lead to severe personal injury or substantial 
damage of property. 

The product must be operated by trained staff. Correct and safe opera-
tion of this equipment is dependent on proper transport, storage installa-
tion and operation. 

All electrical wirings must conform to local standards. In order to prevent 
stray electrical radiation, we recommend twisted and shielded input 
cables and also to keep power supply cables separated from the input 
cables. The connection must be made according to the connection dia-
grams.  

Before switching on the power supply take care that other equipment is 
not affected. Ensure that the power voltage and the conditions is the 
environment comply with the specification of the device. 

Before switching of the power supply voltage, check the possible effects 
on other equipment and the processing system. 

ATEX application - configuration 

           WARNING 

For electrical installations and commissioning of the explosion protected 
devices, the data given in the conformity certificate as also the local 
regulations for installation of electrical apparatus within explosion pro-
tected areas must be considered. The intrinsically safe versions can be 
mounted in the explosion hazarded area according to its specification 
and only connected to a certified intrinsically safe supply loop with the 
corresponding electrical values. 

After mounting of the device - do check that the housing has a ground 
potential. 

The product contains not replaceable parts, except from insert and/or 
FlexTop transmitter if selected. In case of malfunction the product must 
be sent to Baumer for repair. 

 Technical specifications 

Sensor and connection material  Stainless steel, AISI 316L 

Housing 

 

 

  M16     3 … 9    mm                          

 

 

 

 

M16     5 … 9   - 

 

      

 

M20     8 … 13   - 

 

 

 
Media temperature 

-50...400°C on sensor tube tip 

Ambient temperature (cable) 

-50...160°C  w. RTD output 

 

-50...85°C 

w. transmitter 

 Environment 

Pressure 

≤100 bar 

Humidity 

<98% RH, condensing 

Protection class 

IP65 

Vibrations 

GL, test 2 (sensor tube <200 mm) 

English 

page 1...4 

Deutsch  Seite 5...8 
Français  page 9...12 

Operating instructions: 11119033 08

 

Operating instructions for temperature sensor 

TCR6

 

 Industrial temperature sensor  

Содержание TCR6

Страница 1: ...r substantial damage of property The product must be operated by trained staff Correct and safe opera tion of this equipment is dependent on proper transport storage installa tion and operation All el...

Страница 2: ...m A R 1 2 ISO 7 1 M18 M20 ISO 261 14 NPT ANSI ASME B1 20 1 G 1 2 A G 3 4 A G 1 A nipple ISO 228 1 G 1 2 G 3 4 union ISO 228 1 Sensor tip Standard Fast response 4 20 mm DIN form B head Response time ti...

Страница 3: ...supplied Mount the gland pocket into the application and install the sensor after the gland pocket is fixed to the application This will ensure that the cable is not twisted during mounting Baumer rec...

Страница 4: ...imple apparatus no transmitter or display The CombiTemp TCR6 can be supplied for hazardous area Either as a Simple Apparatus with RDT output or with built in transmitter with 4 20 mA output A CombiTem...

Страница 5: ...sind m gliche Auswir kungen auf andere Ger te und das gesamte System zu pr fen ATEX Anwendungen Konfiguration G ltig f r FlexTop 2202 2211 2221 Das FlexProgrammer Konfigurationsger t darf in der gef...

Страница 6: ...SI ASME B1 20 1 G 1 2 A G 3 4 A G 1 A Druck schraube ISO 228 1 G 1 2 G 3 4 berwurfmutter ISO 228 1 Sensorspitze Standard Schnell ansprechend 4 20 mm DIN Form B Kopf Ansprechzeit Zeitkonstante 0 5 Sens...

Страница 7: ...chl sse ist ein spezielles Schutzrohr lieferbar Die Verschraubung Schutzh lse in der Anwendung montieren und anschlie end den Sensor installieren Dadurch wird sichergestellt dass sich das Kabel bei de...

Страница 8: ...riere U 28 VDC I 0 1A P 0 7 W Ex Daten f r FlexTop 2211 und 2221 Zulassung ATEX II 1G Ex ia IIC T5 T6 Spannungsversorgung 2211 6 5 30 VDC 2221 8 30 VDC Interne Induktivit t Li 15 H Interne Kapazit t C...

Страница 9: ...ement et sur le syst me de traitement Application configuration ATEX Valide pour le FlexTop 2202 2211 2221 L unit de configuration FlexProgrammer ne doit pas tre connect e au FlexTop dans la zone dang...

Страница 10: ...3 4 A G 1 A m le tournant ISO 228 1 G 1 2 G 3 4 femelle tour nant ISO 228 1 Pointe du capteur Standard Temps de r ponse 4 20 mm T te DIN forme B Temps de r ponse constante de temps 0 5 Diam tre de la...

Страница 11: ...raccords Installez le presse toupe doigt de gant sur l application puis installez le capteur une fois le presse toupe doigt de gant fix l application Cela pr viendra toute torsion du c ble pendant le...

Страница 12: ...ta pour FlexTop 2211 et 2221 Homologation ATEX II 1G Ex ia IIC T5 T6 Alimentation 2211 6 5 30 V DC 2221 8 30 V DC Inductance interne Li 15 H Capacitance interne Ci 5 nF Plage de temp rature T1 T5 40 T...

Страница 13: ...www baumer com Page 13 16 Operating instructions 11119033 08 Operating instructions for temperature sensor TCR6 Industrial temperature sensor...

Страница 14: ...www baumer com Page 14 16 Operating instructions 11119033 08 Operating instructions for temperature sensor TCR6 Industrial temperature sensor...

Страница 15: ...www baumer com Page 15 16 Operating instructions 11119033 08 Operating instructions for temperature sensor TCR6 Industrial temperature sensor...

Страница 16: ...www baumer com Page 16 16 Operating instructions 11119033 08 For further information please refer to www baumer com...

Отзывы: