8.7
Polarity
With the
Polarity
function, you can define the behavior of the switching outputs regarding the
output level.
With parameterization you can choose between
Active High
and
Active Low
.
Active High
SP1
SP2
SP1
Point mode
Window mode
1
0
1
0
Ill. 12:
Polarity – Active High
n
Point mode: The switching output is activated as soon as the defined distance SP1 is not
reached.
n
Window mode: The switching output is activated as soon as the measured value is within
the window of SP1 and SP2.
Active Low
SP1
SP2
SP1
Point mode
Window mode
0
1
0
1
Ill. 13:
Polarity – Active Low
n
Point mode: The switching output is activated as soon as the defined distance SP1 is ex-
ceeded.
n
Window mode: The switching output is activated as soon as the measured value is outside
the window of SP1 and SP2.
IO-Link parameter: Polarity
Parameter name
Values
Description
SSC1 Config.Polarity
Active Low
,
Ac-
tive High
Polarity of the switching output