9171300990 Rev R
BE1-87T Controls and Indicators
2-3
Letter
Control or Indicator
Function
O
S
Indicator
Red LED lights when the
% OF TRIP
pushbutton P is
pressed and the restraint current is above the slope
characteristic kneepoint as defined in Table 1-1. That
is, the relay will operate based on the restraint
characteristic.
P
Percent of Trip Pushbutton
Pushbutton that is used to activate the
% of TRIP
LEDs.
Q
% OF TRIP
Indicators Option
When the
% OF TRIP
pushbutton P is pushed, eight
LEDs, shown in Figure 2-5, are used to indicate the
approximate percentage of operating current to:
Minimum pickup (LED
M
also lights); or
Slope characteristic pickup (LED
S
also lights).
The eight LEDs represent the following approximate
percentages.
1 LED: 3% (Yellow LED)
2 LEDs: 7% (Yellow LED)
3 LEDs: 11% (Yellow LED)
4 LEDs: 20% (Red LED)
5 LEDs: 40% (Red LED)
6 LEDs: 60% (Red LED)
7 LEDs: 80% (Red LED)
8 LEDs: 100% (Red LED)
A bar chart above the LEDs shows the relative
percentage of trip.
www
. ElectricalPartManuals
. com