4-18
BE1-87T Installation
9171300990 Rev R
Step 3.
Remove the four screws that attach the front panel to the cradle assembly, and remove the
front panel.
Step 4.
With a slight side-to-side rocking motion, withdraw Analog Board #1.
MOTHERBOARD
FRONT
PANEL
FRONT
PANEL
MOTHERBOARD
SINGLE-PHASE
THREE-PHASE
ANALOG BOARD #1
POWER SUPPLY
POWER SUPPLY
ANALOG BOARD #2
ANALOG BOARD #1
ANALOG BOARD #1
ANALOG BOARD #1
ANALOG BOARD #2
UPPER SWITCH BOARD
LOWER SWITCH BOARD
UPPER SWITCH BOARD
LOWER SWITCH BOARD
D638-003
2-23-93
BE1-87T
0 A
0 B
0 C
Figure 4-19. Side View of Cradle Assembly
DISABLING UNUSED INPUTS
To eliminate the possibility of a spurious input from induced currents within the relay, special internal
jumpers have been provided to disable any inputs that are not connected to CT wires.
CAUTION
Disabling unused inputs requires disassembly of the relay and must be done when the
relay has been taken out of service. Access to the input-disabling jumpers requires the
removal of the Analog #1 Board, shown in Figure 4-19. To avoid personal injury or
equipment damage, do
NOT
proceed unless thoroughly familiar with the instructions in
sections
RELAY OPERATING PRECAUTIONS
and
RELAY DISASSEMBLY:
Precautions
.
www
. ElectricalPartManuals