BE1-87T Test Procedures
9171300990 Rev R
This verifies the B- and C-phase differential circuits which respond together as provided earlier
in the Verification Tests: 5 Amp CT or Verification Tests: 1 Amp CT in this section. The A-
phase differential circuit sees no current and does not respond.