9171300990 Rev R
BE1-87T Test Procedures
5-23
This verifies the A- and C-phase differential circuits which respond together as provided
earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The B-
phase differential circuit sees no current and does not respond.
NOTE
The same test connections are used for
Δ
1-
Δ
1 and
Δ
2-
Δ
2. The proper jumper position is
confirmed by which relay differential circuits respond for the specific condition.
Jumper Positions
Δ
2-
Δ
2
Step 1.
Connect Input 1 current to terminals A and N.
Connect Input 2 current to terminals A and N.
This verifies the A- and C-phase differential circuits which respond together as provided earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The B-
phase differential circuit sees no current and does not respond.
Step 2.
Connect Input 1 current to terminals B and N.
Connect Input 2 current to terminals B and N.
This verifies the A- and B-phase differential circuits which respond together as provided earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The C-
phase differential circuit sees no current and does not respond.
Step 3.
Connect Input 1 current to terminals C and N.
Connect Input 2 current to terminals C and N.
This verifies the B- and C-phase differential circuits which respond together as provided earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The A-
phase differential circuit sees no current and does not respond.
Jumper Positions
Δ
1-
Δ
2
Step 1.
Connect Input 1 current to terminals A and N.
Connect Input 2 current to terminals N and B.
This verifies the A- and B-phase differential circuits which respond together as provided earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The C-
phase differential circuit sees no current and does not respond.
Step 2.
Connect Input 1 current to terminals C and N.
Connect Input 2 current to terminals N and A.
This verifies the A- and C-phase differential circuits which respond together as provided earlier
in the
Verification Tests: 5 Amp CT
or
Verification Tests: 1 Amp CT
in this section. The B-
phase differential circuit sees no current and does not respond.
Step 3.
Connect Input 1 current to terminals B and N.
Connect Input 2 current to terminals N and C.
www
. ElectricalPartManuals
. com