9252000981 Rev G
BE1-50/51B-219/-226 Testing
5-7
Step 1. Set target current source to 1.0 ampere, ac.
Step 2. Read all of Step 3 before beginning Step 3.
Step 3. Apply 0.8 amperes input current to terminals 8 and 9. After the unit trips, remove the input current
for 20 ±0.25 seconds, then reapply the 0.8 amperes input current. Record the elapsed time from
the re-application of input current to the output retrip.
Result:
Elapsed time should be 1.55 ±0.3 seconds.
SETTING THE RELAY
Select the desired relay settings before putting the relay into service. Changing pickup current settings
while the relay is in service may cause tripping.
PERIODIC TESTS
General
All relays should be tested periodically to identify and correct any problems that are found.
Single phase relays such as the BE1-50/51B-214 and BE1-50/51B-225 are normally used in groups of
four (three phase and ground) on the protected circuit. This relay scheme allows each unit to be
withdrawn one at a time for testing purposes without losing protection. Only three are required at any one
time to sense all types of faults on a grounded wye system. Refer to Figures 5-1 and 5-2 for
recommended test setups.
Periodic Test
Periodic testing should consist of the following procedures.
Step 1. Verify that the instantaneous pickup is within ±2% of the value set on the dials. Pickup occurs
when the INST output contacts close.
Step 2. Verify that the time pickup is within ±2% of the value set on the dials. Pickup occurs when the
LED turns GREEN then RED.
Step 3. Verify that the time to trip for the curve and time dial settings at a multiple of six is the same as
the time given on the characteristic curve. Refer to Section 1 for the characteristics curves.
Step 4. Verify that the time to trip for the instantaneous element at a pickup multiple of 2 is not greater
than the time given on the instantaneous characteristic curve. Refer to Section 1 for the
instantaneous characteristic curve.
Step 5. Verify that the targets operate with one ac ampere of trip current in the trip circuits and that they
can be reset using the RESET BUTTON.
Содержание BE1-50/51B-219
Страница 2: ......
Страница 6: ...iv BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 8: ...vi BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 10: ...ii BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 20: ...1 10 BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 22: ...ii BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 24: ...2 2 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G P0053 50 SW3 Figure 2 2 Location of SW3...
Страница 26: ...2 4 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 28: ...ii BE1 50 51B 219 226 Functional Description 9252000981 Rev G This page intentionally left blank...
Страница 32: ...ii BE1 50 51B 219 226 Installation 9252000981 Rev G This page intentionally left blank...
Страница 38: ...ii BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 46: ...5 8 BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 48: ...ii BE1 50 51B 219 226 Time Characteristic Curves 9252000981 Rev G This page intentionally left blank...