9252000981 Rev G
BE1-50/51B-219/-226 Installation
4-1
SECTION 4
•
INSTALLATION
GENERAL
When not shipped as part of a control or switchgear panel, the relays are shipped in sturdy cartons to
prevent damage during transit. Immediately upon receipt of a relay, check the model and part number
against the requisition and packing list to see that they agree. Visually inspect the relay for damage that
may have occurred during shipment. If there is evidence of damage, immediately file a claim with the
carrier and notify the Regional Sales Office, or contact the Sales Representative at Basler Electric,
Highland, Illinois.
Proper operation of the relay may be confirmed by performing the operational test procedure of Section 5.
If the relay won't be installed immediately, store the relay in its original shipping carton in a moisture and
dust-free environment.
FACTORY SETTINGS
Factory settings for the internal switches of SW3 are as follows:
•
SW3-1 — OFF (60 hertz operation).
•
SW3-2 — OFF (0.0 additional fixed delay for the instantaneous element).
•
SW3-3 — OFF (Westinghouse/ABB type characteristic curves).
•
SW3-4 — ON (Integrating reset characteristics).
INSTALLATION
Select the desired relay settings before putting the relay into service. Changing pickup current settings
while the relay is in service may cause tripping. Perform the following procedures to install the BE1-
50/51B-219 or BE1-50/51B-226 relay.
•
Select the desired relay settings on your new BE1-50/51B-219/-226 relay.
•
Remove the existing ABB relay cradle.
•
Insert the new relay cradle and close the cradle latches locking the relay into the case.
•
Close knife-blade switches.
•
To install the cover, position the interlocking bracket at the top of the new Basler Electric cover into
the mating receptacle at the top of the case. Secure the captive fastener at the bottom of the cover.
APPLICATION COORDINATION
In a typical application coordination scheme, a BE1-50/51B-219 or BE1-50/51B-226 is being used to
provide primary protection for a radial distribution feeder. An electromechanical overcurrent relay with
extremely inverse timing provides protection for the transformer and bus. To improve coordination with
the electromechanical relay, the BE1 relay with integrating reset characteristic has the time characteristic
curve E (extremely inverse) selected (SW3-3 set to OFF) and the TIME DIAL set to 2.0. The feeder
reclosing relay is set for two reclose attempts at 3 and 15 seconds after the initial trip. If a permanent fault
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG
copper wire attached to the ground terminal on the rear of the unit case. When
the relay is configured in a system with other devices, it is recommended to use a
separate lead to the ground bus from each unit.
CAUTION
Close all BLACK handle switches before closing any RED handle switches.
Insure that the RED handle switches are closed last.
Содержание BE1-50/51B-219
Страница 2: ......
Страница 6: ...iv BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 8: ...vi BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 10: ...ii BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 20: ...1 10 BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 22: ...ii BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 24: ...2 2 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G P0053 50 SW3 Figure 2 2 Location of SW3...
Страница 26: ...2 4 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 28: ...ii BE1 50 51B 219 226 Functional Description 9252000981 Rev G This page intentionally left blank...
Страница 32: ...ii BE1 50 51B 219 226 Installation 9252000981 Rev G This page intentionally left blank...
Страница 38: ...ii BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 46: ...5 8 BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 48: ...ii BE1 50 51B 219 226 Time Characteristic Curves 9252000981 Rev G This page intentionally left blank...