Instantaneous Overcurrent (50) Element
Setting the INST PICKUP at the minimum pickup setting places the relay in the most sensitive state and
may be used as a safety setting.
BE1-50/51B-219 Pickup
Setting Range:
1 to 99 Aac
Setting Increment:
1 Aac
Accuracy:
±2%, ±25 milliamperes at or above 1.0 ampere setting
BE1-50/51B-226 Pickup
Setting Range:
0.2 to 19.8 Aac
Setting Increment:
0.2 Aac
Accuracy:
±2%, ±5 milliamperes at or above 0.2 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Curve Characteristics
Instantaneous characteristic curves are similar to standard electromechanical instantaneous units.
However, the time to trip for applications where the initial current through the relay is less than 0.4
ampere (5 ampere relay) or 0.08 ampere (1 ampere relay) may be slightly longer. This may occur on a
very lightly loaded circuit or when the relay is providing ground protection and is connected to measure
neutral current. Figure 1-2 shows the instantaneous characteristic curves for maximum time to trip.
An additional fixed delay of 0.1 second may be added with internal switch SW3-2. This delay applies to
both phase and ground applications. Closing switch SW3-2 provides an additional delay of 0.1 second.
Section 2 illustrates the location of SW3.
The instantaneous element in BE1-50/51B-219 and BE1-50/51B-226 relays may be set lower than the
instantaneous element in ABB relays and still have the same reach. This is because the BE1-50/51B-219
and BE1-50/51B-226 instantaneous element effectively eliminates the fault current transient overreach
components. When calculating BE1-50/51B-219 and BE1-50/51B-226 relay instantaneous element
settings, calculate the symmetrical value without any adder for transient overreach.
Содержание BE1-50/51B-219
Страница 2: ......
Страница 6: ...iv BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 8: ...vi BE1 50 51B 219 226 Introduction 9252000981 Rev G This page intentionally left blank...
Страница 10: ...ii BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 20: ...1 10 BE1 50 51B 219 226 General Information 9252000981 Rev G This page intentionally left blank...
Страница 22: ...ii BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 24: ...2 2 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G P0053 50 SW3 Figure 2 2 Location of SW3...
Страница 26: ...2 4 BE1 50 51B 219 226 Controls and Indicators 9252000981 Rev G This page intentionally left blank...
Страница 28: ...ii BE1 50 51B 219 226 Functional Description 9252000981 Rev G This page intentionally left blank...
Страница 32: ...ii BE1 50 51B 219 226 Installation 9252000981 Rev G This page intentionally left blank...
Страница 38: ...ii BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 46: ...5 8 BE1 50 51B 219 226 Testing 9252000981 Rev G This page intentionally left blank...
Страница 48: ...ii BE1 50 51B 219 226 Time Characteristic Curves 9252000981 Rev G This page intentionally left blank...