BE1-50/51B-214/-215/-223/-225 Functional Description 

3-1 

SECTION 3 

 FUNCTIONAL DESCRIPTION 

GENERAL 

BE1-50/51B-214/-215/-223/-225 Overcurrent Relays are microprocessor based non-directional relays that 
measure ac current to provide secure and reliable instantaneous and time overcurrent protection for 
power systems. 

FUNCTIONAL DESCRIPTION 

Sensing Input 

Single phase ac current from system current transformers (CT) is brought into the Overcurrent Relay at 
terminals 5 and 6. Refer to Figure 3-1 to follow the functional description for the BE1-214/-225. Refer to 
Figure  3-2  to follow the functional description for the BE1-50/51B-215.  Refer to Figure  3-3  to follow the 
functional description for the BE1-50/51B-223.The input current is applied to internal power and signal 
CTs. 

Power Supply 

Current from the power CT is rectified, filtered, and supplied to all relay internal circuitry for operating 
power. A pre5 Vdc supply also serves as a reference for automatic calibration. 

Instantaneous Signal 

Current from the signal CT is rectified and applied to the instantaneous scaling resistors controlled by the 
INST PICKUP selector switches. The analog voltage of the instantaneous input signal developed across 
the scaling resistors is filtered and applied to the multiplexor (MUX). 

Time Signal 

Current from the signal CT is also rectified and applied to the time scaling resistors controlled by the TIME 
PICKUP selector switches. The analog voltage of the time input signal is also filtered and applied to the 
multiplexor. 

Microprocessor 

Operating power from the power supply is applied to the microprocessor supervisor circuit. When the 
microprocessor is active and executing code, the ACTIVE/PICKUP LED is green. When the input current 
falls below an acceptable level, the supervisor circuit interrupts the microprocessor, halts further 
operation, and turns OFF the ACTIVE/PICKUP LED. A microprocessor watchdog feature resets the 
microprocessor program when the program flow is interrupted. 

Information from the TIME DIAL selector switches, the TIME CURVE selector switch, and the 50/60 Hz, 
INST DELAY, and RESET CHAR switches is also applied to the microprocessor. The microprocessor 
uses these inputs to set the operating parameters. 

When the microprocessor is ready for analog information from the multiplexor, microprocessor control 
signals cause the multiplexor to route the desired input through to the output. The output is converted 
from an analog value to a digital value and applied to the microprocessor. 

The microprocessor performs the program operations based on the inputs and the internal software 
program. When the sensed current exceeds the TIME PICKUP setting, the ACTIVE/PICKUP LED turns 
from green to red. TIME contacts (51) are closed in accordance with the time characteristic equation. If 
the sensed current exceeds the INST PICKUP setting, the INST contacts (50) are closed. 

Power-Off Sensing 

Power-off sensing circuits measure the voltage across a capacitor at power-down and at power-up. These 
circuits determine how long power has been removed based on the difference voltage and the circuit RC 
time constant. This provides information for the integrating reset function even when power has been 
entirely removed. 

Содержание BE1-50/51B-214

Страница 1: ...INSTRUCTION MANUAL FOR OVERCURRENT RELAYS BE1 50 51B 214 215 223 225 Publication 9252000994 Revision N 04 10 9252000994...

Страница 2: ......

Страница 3: ...f the BE1 50 51B 214 215 223 225 Overcurrent Relays To accomplish this the following information is provided General Information and Specifications Controls and Indicators Functional Description Insta...

Страница 4: ...or operation The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electric BASLER ELECTRIC ROUTE 143...

Страница 5: ...ut Time Dial Test corrected the elapsed time stated in step 2 Added the relay s metric weight to Section 1 General Information Specifications Moved contents of Section 7 Manual Change Information to t...

Страница 6: ...iv BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...

Страница 7: ...5 223 225 Introduction v CONTENTS SECTION 1 GENERAL INFORMATION 1 1 SECTION 2 CONTROLS AND INDICATORS 2 1 SECTION 3 FUNCTIONAL DESCRIPTION 3 1 SECTION 4 INSTALLATION 4 1 SECTION 5 TESTING 5 1 APPENDIX...

Страница 8: ...vi BE1 50 51B 214 215 223 225 Introduction 9252000994 Rev N This page intentionally left blank...

Страница 9: ...ransient Response 1 7 Harmonic Response 1 7 Target Indicators 1 8 Output Contacts 1 8 Type Tests 1 8 Environment 1 9 Agency Recognition 1 9 Physical 1 9 Figures Figure 1 1 Integrating Reset Characteri...

Страница 10: ...ii BE1 50 51B 214 215 223 225 General Information 9252000994 Rev N This page intentionally left blank...

Страница 11: ...225 protective relays are self powered microprocessor based non directional phase or ground relays that monitor the magnitude of a single phase ac current to provide accurate instantaneous and time ov...

Страница 12: ...relay case SPECIFICATIONS BE1 50 51B 214 215 223 225 overcurrent relays have the following features and capabilities Current Sensing Input Continuous Current 14 Aac BE1 50 51B 214 215 223 One Second R...

Страница 13: ...ants are listed in Tables 1 2 and 1 3 Constants have been selected to conform to the characteristics of electromechanical relays over a range of pickup multiples from 1 3 to 40 Values of the constants...

Страница 14: ...rse Notes for Tables 1 2 and 1 3 L Long Inverse E Extremely Inverse D Definite Time B BS142 Very Inverse M Moderately Inverse C BS142 Extremely Inverse I Inverse F Fixed Time Delay Figure numbers refe...

Страница 15: ...r when the relay is providing ground protection and is connected to measure neutral current Curve Characteristics Figure 1 2 shows the instantaneous characteristic curves for maximum time to trip An a...

Страница 16: ...ion 9252000994 Rev N Figure 1 2 Instantaneous Characteristic Curves Burden Burden is non linear Figure 1 3 illustrates the device burden At 0 5 amperes 4 8 BE1 50 51B 214 215 223 At 5 0 amperes 0 2 At...

Страница 17: ...t causes 0 5 change in the current required for pickup Transient Response 10 overreach with system time constants up to 40 ms Harmonic Response Figure 1 4 shows that a relay set for 1 ampere pickup wo...

Страница 18: ...llows 120 240 Vac Make 30 amperes for 0 2 seconds carry 7 amperes for 2 minutes 3 amperes continuously and break 5 amperes Resistive Ratings 125 250 Vdc Make 30 amperes for 0 2 seconds carry 7 amperes...

Страница 19: ...a located 6 inches from the relay in both horizontal and vertical planes Radio Frequency Interference RFI Withstands 2 G in each of three mutually perpendicular planes swept over the range of 10 to 50...

Страница 20: ...1 10 BE1 50 51B 214 215 223 225 General Information 9252000994 Rev N This page intentionally left blank...

Страница 21: ...ROLS AND INDICATORS TABLE OF CONTENTS SECTION 2 CONTROLS AND INDICATORS 2 1 INTRODUCTION 2 1 Figures Figure 2 1 Front Panel Controls and Indicators 2 1 Figure 2 2 Location of SW3 2 2 Tables Table 2 1...

Страница 22: ...ii BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N This page intentionally left blank...

Страница 23: ...Figure 2 1 illustrates the front panel controls and indicators of the BE1 50 51B 214 215 223 225 Figure 2 2 illustrates the location of switch SW3 Both illustrations have lettered call outs that corr...

Страница 24: ...2 2 BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N Figure 2 2 Location of SW3 P0053 50...

Страница 25: ...l time provided by an electromechanical relay at its maximum dial setting G TIME MANUAL TRIP Test Points When shorted the test points provide a secure means to manually trip the controlled breaker Jac...

Страница 26: ...2 4 BE1 50 51B 214 215 223 225 Controls and Indicators 9252000994 Rev N This page intentionally left blank...

Страница 27: ...N 3 1 GENERAL 3 1 FUNCTIONAL DESCRIPTION 3 1 Sensing Input 3 1 Power Supply 3 1 Instantaneous Signal 3 1 Time Signal 3 1 Microprocessor 3 1 Power Off Sensing 3 1 Outputs 3 2 Figures Figure 3 1 Functio...

Страница 28: ...ii BE1 50 51B 214 215 223 225 Functional Description 9252000994 Rev N This page intentionally left blank...

Страница 29: ...the multiplexor Microprocessor Operating power from the power supply is applied to the microprocessor supervisor circuit When the microprocessor is active and executing code the ACTIVE PICKUP LED is g...

Страница 30: ...urrent flow in the trip circuit is indicated by the operation of the target The targets will not operate without adequate operating power for the relay Instantaneous and Timed Figure 3 1 Functional Bl...

Страница 31: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Functional Description 3 3 Figure 3 3 Functional Block Diagram BE1 50 51B 223...

Страница 32: ...3 4 BE1 50 51B 214 215 223 225 Functional Description 9252000994 Rev N This page intentionally left blank...

Страница 33: ...TINGS 4 1 INSTALLATION 4 1 APPLICATION COORDINATION 4 1 CONNECTIONS 4 3 MAINTENANCE 4 6 STORAGE 4 6 Figures Figure 4 1 Coordination Timing Diagram 4 2 Figure 4 2 AC Input Connections 4 3 Figure 4 3 DC...

Страница 34: ...ii BE1 50 51B 214 215 223 225 Installation 9252000994 Rev N This page intentionally left blank...

Страница 35: ...o install the BE1 50 51B 214 215 223 225 relay Select the desired relay settings on your new BE1 50 51B 214 215 223 225 relay Remove the existing IAC relay Use the four screws provided and attach the...

Страница 36: ...ll reset 15 5 seconds if current goes to zero In Figure 4 1 TA 0 209 seconds relay was at reset TB value TA because rewind has not gone to zero TC value TA because rewind has not gone to zero Figure 4...

Страница 37: ...igure 4 2 Typical dc control connections for the BE1 50 51B 214 225 are shown in Figure 4 3 Typical dc control connections for the BE1 50 51B 215 are shown in Figure 4 4 Typical dc control connections...

Страница 38: ...4 4 BE1 50 51B 214 215 223 225 Installation 9252000994 Rev N Figure 4 3 DC Control Connections BE1 50 51B 214 225...

Страница 39: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Installation 4 5 Figure 4 4 DC Control Connections BE1 50 51B 215...

Страница 40: ...performed according to scheduled practices A recommended periodic test is provided in Section 5 If the relay fails to function properly contact the Technical Sales Support Department of Basler Electri...

Страница 41: ...Model BE1 50 51B 225 One Ampere Sensing Input 5 7 SETTING THE RELAY 5 9 PERIODIC TESTS 5 9 General 5 9 Periodic Test 5 9 Figures Figure 5 1 Pickup and Timing Test Setup BE1 50 51B 214 225 5 2 Figure 5...

Страница 42: ...ii BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...

Страница 43: ...d BE1 50 51B 225 1 ampere model The test setup of Figures 5 1 and 5 2 BE1 50 51B 214 225 are intended primarily as an illustration of the principles involved The BE1 50 51B 215 is illustrated in Figur...

Страница 44: ...re 5 2 Target Operational Test Setup BE1 50 51B 214 225 BE1 50 51B 214 225 6 5 3 1 TIME INST 2 CURRENT SOURCE INPUT STOP TIMER START AMPS TEST SET P0059 08 BE1 50 51B 214 225 6 5 CURRENT SOURCE INPUT...

Страница 45: ...ure 5 4 Target Operational Test Setup BE1 50 51B 215 BE1 50 51B 215 6 5 10 1 TIME INST 2 CURRENT SOURCE INPUT STOP TIMER START AMPS TEST SET P0059 05 9 BE1 50 51B 215 6 5 CURRENT SOURCE INPUT STOP TIM...

Страница 46: ...ure 5 6 Target Operational Test Setup BE1 50 51B 223 BE1 50 51B 223 6 5 10 1 TIME INST 2 CURRENT SOURCE INPUT STOP TIMER START AMPS TEST SET P0061 20 9 BE1 50 51B 223 6 5 10 1 TIME INST 2 CURRENT SOUR...

Страница 47: ...s shown in Figure 5 1 BE1 50 51B 214 Figure 5 3 BE1 50 51B 215 or Figure 5 5 BE1 50 51B 223 Insure that SW3 switches are set SW3 1 for the operating frequency SW3 2 to OFF SW3 3 to ON and SW3 4 ON Set...

Страница 48: ...perates Step 3 Remove input current and reset target Step 4 Set TIME PICKUP to 15 9 and set INST PICKUP to 01 Step 5 Set voltage source to provide a target current of 1 0 ampere Step 6 Apply 5 amperes...

Страница 49: ...e set SW3 1 for the operating frequency SW3 2 to OFF SW3 3 to ON and SW3 4 to ON Set TIME DIAL to 0 0 Set CURVE to S Set TIME PICKUP to 0 5 Set INST PICKUP to 18 0 Step 1 Slowly increase current to te...

Страница 50: ...1 for the operating frequency SW3 2 to OFF SW3 3 to ON and SW3 4 ON Set TIME DIAL to 4 5 Set CURVE to S Set TIME PICKUP to 0 2 Set INST PICKUP to 19 8 Step 1 Set voltage source to provide a target cu...

Страница 51: ...pping PERIODIC TESTS General All relays should be tested periodically to identify and correct any problems that are found Single phase relays such as the BE1 50 51B 214 215 223 225 are normally used i...

Страница 52: ...5 10 BE1 50 51B 214 215 223 225 Testing 9252000994 Rev N This page intentionally left blank...

Страница 53: ...OFF Similar to ABB CO 8 A 5 Figure A 6 Time Characteristic Curve V Very Inverse SW3 3 OFF Similar to ABB CO 9 A 6 Figure A 7 Time Characteristic Curve E Extremely Inverse SW3 3 OFF Similar to ABB CO...

Страница 54: ...ii BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N This page intentionally left blank...

Страница 55: ...PPENDIX A TIME CHARACTERISTIC CURVES TIME CHARACTERISTIC CURVES Figures A 1 through A 14 illustrate the time characteristic curves that are programmed into the nonvolatile memory of this relay Figure...

Страница 56: ...A 2 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 2 Time Characteristic Curve L Long Inverse SW3 3 OFF Similar to ABB CO 5...

Страница 57: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 3 Figure A 3 Time Characteristic Curve D Definite Time Similar to ABB CO 6...

Страница 58: ...A 4 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 4 Time Characteristic Curve M Moderately Inverse Similar to ABB CO 7...

Страница 59: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 5 Figure A 5 Time Characteristic Curve I Inverse SW3 3 OFF Similar to ABB CO 8...

Страница 60: ...A 6 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 6 Time Characteristic Curve V Very Inverse SW3 3 OFF Similar to ABB CO 9...

Страница 61: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 7 Figure A 7 Time Characteristic Curve E Extremely Inverse SW3 3 OFF Similar to ABB CO 11...

Страница 62: ...A 8 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 8 Time Characteristic Curve BS142 B BS142 Very Inverse...

Страница 63: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 9 Figure A 9 Time Characteristic Curve BS142 C BS142 Extremely Inverse...

Страница 64: ...A 10 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 10 Time Characteristic Curve S2 Short Inverse SW3 3 ON Similar to GE IAC 55...

Страница 65: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 11 Figure A 11 Time Characteristic Curve L2 Long Inverse SW3 3 ON Similar to GE IAC 66...

Страница 66: ...A 12 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 12 Time Characteristic Curve I2 Inverse SW3 3 ON Similar to GE IAC 51...

Страница 67: ...9252000994 Rev N BE1 50 51B 214 215 223 225 Time Characteristic Curves A 13 Figure A 13 Time Characteristic Curve V2 Very Inverse SW3 3 ON Similar to GE IAC 53...

Страница 68: ...A 14 BE1 50 51B 214 215 223 225 Time Characteristic Curves 9252000994 Rev N Figure A 14 Time Characteristic Curve E2 Extremely Inverse SW3 3 ON Similar to GE IAC 77...

Страница 69: ......

Страница 70: ...ROUTE 143 BOX 269 HIGHLAND IL 62249 USA http www basler com info basler com PHONE 1 618 654 2341 FAX 1 618 654 2351...

Отзывы: