324
9424200994 Rev U
BESTlogic
™
Plus
BE1-11
g
Logic Schemes
A logic scheme is a group of logic variables that defines the operation of a BE1-11
g
. Each logic scheme is
given a unique name. This gives you the ability to select a specific scheme and be confident that the
selected scheme is in operation. One logic scheme is configured for typical control applications and is the
default active logic scheme. Only one logic scheme can be active at a given time. In most applications,
preprogrammed logic schemes eliminate the need for custom programming. Preprogrammed logic
schemes can provide more inputs, outputs, or features than are needed for a particular application. This
is because a preprogrammed scheme is designed for a large number of applications with no special
programming required. Unneeded logic block outputs can be left open to disable a function or a function
block can be disabled through operating settings.
When a custom logic scheme is required, programming time is reduced by modifying the default logic
scheme.
Default Logic Scheme
All BE1-11
g
protection systems are delivered with the default logic scheme pre-loaded in memory
.
If the
function block configuration and output logic of the default logic scheme meets the requirements of your
application, then only the operating settings (power system parameters and threshold settings) need to be
adjusted before placing the BE1-11
g
in service.
Details of Default Logic Scheme
describes the characteristics of the logic scheme and how it combines to
create an Overcurrent Protection System for a radial system substation. A detailed description of the
default scheme is also provided.
The default logic scheme is designed to accommodate most common distribution or sub-transmission
radial system overcurrent coordination schemes. The protection engineer can adapt it by changing the
function block operation and settings. This eliminates the need to create a custom logic scheme.
It should be noted that the default logic scheme also illustrates typical ways of using or controlling various
functions. The user can choose to create a custom logic scheme by mixing the logic from the default
scheme. The flexibility of BESTlogic
Plus
allows the protection engineer to create a custom scheme that
exactly meets the requirements of the application.
Caution
Always remove the BE1-11
g
from service prior to changing or
modifying the active logic scheme. Attempting to modify a logic
scheme while the BE1-11
g
is in service could generate unexpected or
unwanted outputs.
Modifying a logic scheme in BESTCOMS
Plus
does not automatically
make that scheme active in the BE1-11
g
. The modified scheme must
be uploaded into the BE1-11
g
. See the paragraphs on
Sending and
Retrieving Logic Schemes.
Operational settings are not included in the default logic scheme. Each
element, target, pickup setting, timing setting, etc. will have to be
enabled and programmed separately using the Settings Explorer in
BESTCOMS
Plus
.
Overview of Default Logic Scheme
The default logic scheme provides basic time and instantaneous overcurrent protection. Included
protective elements are 50-1, 50-2, 50-3, 51-1, 51-2, and 51-3. Functions such as breaker failure, virtual
breaker control, and protective voltage features are not enabled in this scheme. However, these features
can be activated through BESTCOMS
Plus
.
Содержание BE1-11g
Страница 1: ...INSTRUCTION MANUAL FOR BE1 11g Generator Protection System Publication 9424200994 Revision U Jul 17...
Страница 2: ......
Страница 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Страница 22: ...10 9424200994 Rev U Introduction BE1 11g...
Страница 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Страница 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Страница 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Страница 61: ...9424200994 Rev U 49 BE1 11g Overexcitation 24 Protection Figure 40 Inverse Time Delay and Reset Time...
Страница 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Страница 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Страница 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Страница 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Страница 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Страница 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Страница 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Страница 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Страница 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Страница 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Страница 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Страница 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Страница 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Страница 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Страница 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Страница 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Страница 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Страница 236: ...224 9424200994 Rev U Alarms BE1 11g...
Страница 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Страница 248: ...236 9424200994 Rev U Demands BE1 11g...
Страница 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Страница 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Страница 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Страница 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Страница 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Страница 280: ...268 9424200994 Rev U Mounting BE1 11g Figure 196 Retrofit Mounting Plate Basler P N 9424200073 Part 2...
Страница 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Страница 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Страница 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Страница 290: ...278 9424200994 Rev U Mounting BE1 11g...
Страница 297: ...9424200994 Rev U 285 BE1 11g Terminals and Connectors Figure 215 Example of Reversed CT Polarity...
Страница 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Страница 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Страница 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Страница 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Страница 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Страница 367: ...9424200994 Rev U 355 BE1 11g Timekeeping Figure 275 Front Panel Circuit Board Backup Battery Location...
Страница 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Страница 374: ...362 9424200994 Rev U Device Information BE1 11g...
Страница 392: ...380 9424200994 Rev U Configuration BE1 11g...
Страница 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Страница 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Страница 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Страница 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Страница 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Страница 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Страница 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Страница 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Страница 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Страница 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Страница 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Страница 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Страница 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Страница 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Страница 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Страница 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Страница 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Страница 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Страница 622: ...610 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 357 Time Characteristic Curve A Standard Inverse BS 142...
Страница 630: ...618 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 365 Time Characteristic Curve G Long Time Inverse BS 142...
Страница 633: ...9424200994 Rev U 621 BE1 11g Time Curve Characteristics Figure 368 Time Characteristic Curve B Very Inverse BS 142...
Страница 638: ...626 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 373 Time Characteristic Curve C Extremely Inverse BS 142...
Страница 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Страница 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Страница 705: ......