9424200994 Rev U
187
BE1-11
g
Setting Groups
Setting Groups
Four setting groups allow for adapting the coordination settings to optimize them for a predictable
situation. Sensitivity and time coordination settings can be adjusted to optimize sensitivity or clearing time
based upon source conditions or to improve security during overload conditions. The possibilities for
improving protection by eliminating compromises in coordination settings with adaptive setting groups are
endless.
The four setting groups are designated Setting Group 0, Setting Group 1, Setting Group 2, and Setting
Group 3. Setting group logic connections are made on the BESTlogic
™
Plus
screen in BESTCOMS
Plus
®
and setting group operational settings are configured on the Setting Group Setup screen in
BESTCOMS
Plus
. A summary of the logic inputs and outputs and operational settings appears at the end
of this chapter.
BESTCOMSPlus Navigation Path:
Settings Explorer, General Settings, Setting Group Setup
HMI Navigation Path:
Settings Explorer, General Settings, Settings Group
Setting Group Functions
The group of settings that is active at any point in time is controlled by the setting group selection logic.
This function logic allows for manual (logic) selection.
Logic Inputs
The function monitors logic inputs D0 through D3 and changes the active setting group according to the
status of these inputs. These inputs can be connected to logic expressions such as contact sensing
outputs.
Logic Outputs
The function logic has four logic variable outputs, SG0 through SG3. The appropriate variable is asserted
when each setting group is active. These logic variables can be used in programmable logic to modify the
logic based upon which setting group is active.
The SGCACTIVE logic output is asserted when setting group control is active. The SGCLOVRD logic
output is asserted when setting group control is overridden by logic.
Changing Setting Groups
When the BE1-11
g
switches to a new setting group, all functions are reset and initialized with the new
operating parameters. The settings change occurs instantaneously so at no time is the BE1-11
g
off line.
The active setting group is saved in nonvolatile memory so that the BE1-11
g
will power up using the
same setting group that was active when it was powered down. To prevent the BE1-11
g
from changing
settings while a fault condition is in process, setting group changes are blocked when the BE1-11
g
is in a
picked-up state. Since the BE1-11
g
is completely programmable, the fault condition is defined by the
pickup logic expression in the fault reporting functions. See the
Fault Reporting
chapter for more
information.
Setting Group Selection
Selection of the active setting group provided by this function logic can also be overridden. When logic
override is used, a setting group is made active and the BE1-11
g
stays in that group regardless of the
state of the manual logic control conditions.
Manual (logic) selection reads the status of the logic inputs to the setting group selection function block to
determine what setting group should be active.
For the logic inputs to determine which setting group
should be active, the AUTOMATIC input must be logic 0.
The function block operational mode setting
determines how it reads these logic inputs. There are three possible logic modes as shown in Table 75.
Содержание BE1-11g
Страница 1: ...INSTRUCTION MANUAL FOR BE1 11g Generator Protection System Publication 9424200994 Revision U Jul 17...
Страница 2: ......
Страница 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Страница 22: ...10 9424200994 Rev U Introduction BE1 11g...
Страница 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Страница 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Страница 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Страница 61: ...9424200994 Rev U 49 BE1 11g Overexcitation 24 Protection Figure 40 Inverse Time Delay and Reset Time...
Страница 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Страница 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Страница 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Страница 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Страница 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Страница 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Страница 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Страница 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Страница 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Страница 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Страница 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Страница 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Страница 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Страница 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Страница 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Страница 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Страница 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Страница 236: ...224 9424200994 Rev U Alarms BE1 11g...
Страница 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Страница 248: ...236 9424200994 Rev U Demands BE1 11g...
Страница 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Страница 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Страница 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Страница 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Страница 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Страница 280: ...268 9424200994 Rev U Mounting BE1 11g Figure 196 Retrofit Mounting Plate Basler P N 9424200073 Part 2...
Страница 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Страница 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Страница 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Страница 290: ...278 9424200994 Rev U Mounting BE1 11g...
Страница 297: ...9424200994 Rev U 285 BE1 11g Terminals and Connectors Figure 215 Example of Reversed CT Polarity...
Страница 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Страница 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Страница 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Страница 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Страница 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Страница 367: ...9424200994 Rev U 355 BE1 11g Timekeeping Figure 275 Front Panel Circuit Board Backup Battery Location...
Страница 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Страница 374: ...362 9424200994 Rev U Device Information BE1 11g...
Страница 392: ...380 9424200994 Rev U Configuration BE1 11g...
Страница 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Страница 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Страница 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Страница 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Страница 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Страница 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Страница 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Страница 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Страница 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Страница 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Страница 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Страница 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Страница 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Страница 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Страница 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Страница 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Страница 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Страница 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Страница 622: ...610 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 357 Time Characteristic Curve A Standard Inverse BS 142...
Страница 630: ...618 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 365 Time Characteristic Curve G Long Time Inverse BS 142...
Страница 633: ...9424200994 Rev U 621 BE1 11g Time Curve Characteristics Figure 368 Time Characteristic Curve B Very Inverse BS 142...
Страница 638: ...626 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 373 Time Characteristic Curve C Extremely Inverse BS 142...
Страница 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Страница 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Страница 705: ......