9424200994 Rev U
5
BE1-11
g
Introduction
Fault Reporting
Fault reports consist of simple target information, fault summary reports, and detailed oscillography
records to enable the user to retrieve information about disturbances in as much detail as is desired. The
BE1-11
g
records and reports oscillography data in industry-standard IEEE, COMTRADE format to allow
using any fault analysis software. Basler Electric provides a Windows
®
based program called
BESTwave
™
that can read and plot binary or ASCII format files that are in the COMTRADE format. A
copy of BESTwave is included on the BE1-11 product CD.
Sequence of Events Recorder
A Sequence of Events Recorder (SER) records and time stamps all BE1-11
g
inputs and outputs as well
as all alarm conditions monitored by the BE1-11
g
. Time stamp resolution is to the nearest half-cycle. I/O
and Alarm reports can be extracted from the records as well as reports of events recorded during the time
span associated with a specific fault report.
Protection and Control
The BE1-11
g
includes protection elements that monitor voltage, current, power, phase angle, frequency,
temperature, and more to provide protection against faults and abnormal operating conditions. Control
elements make the BE1-11
g
capable of controlling complex distribution configurations. The following
paragraphs describe each protection and control function.
Overexcitation (24) Protection
One volts per hertz protection element provides overexcitation protection for a generator and/or
transformer.
Sync-Check (25) Protection
With the auxiliary voltage input connected to the bus, one sync-check function provides synchronism
protection. Sync-check protection checks for phase angle difference, magnitude difference, frequency
difference (slip) and, optionally, if the three-phase VT frequency is greater than the auxiliary VT
frequency. One voltage monitor output (25VM) provides independent dead/live voltage closing logic.
Undervoltage (27P) and Overvoltage (59P) Protection
Five phase undervoltage and four phase overvoltage elements are included. Phase
undervoltage/overvoltage protection can be set to operate when one, two, or three phases decrease
below the pickup level. When a four-wire voltage transformer connection is used, under/overvoltage
protection can be set for either phase-to-phase voltage or phase-to-neutral voltage. The 27P elements
are equipped with an undervoltage inhibit feature. Inverse or definite time can be selected.
Auxiliary Undervoltage (27X) and Auxiliary Overvoltage (59X) Protection
Four auxiliary overvoltage and four auxiliary undervoltage elements provide over/undervoltage protection.
Auxiliary voltage protection elements can be set to monitor separately the third harmonic, neutral-shift,
positive-sequence, negative-sequence, or auxiliary fundamental voltages. Ground unbalance protection is
provided when the auxiliary voltage input is connected to a source of 3V0 such as a broken-delta VT or
when 3V0 mode is selected to obtain calculated offset voltage from the phase quantities. The 27X is
equipped with an undervoltage inhibit feature. Inverse or definite time can be selected.
Vector Jump (78) Protection
One vector jump protection element protects the generator by disconnecting it from the grid when a loss
of mains or mains failure occurs, preventing the generator from remaining tied to the mains if the mains
returns due to an external reclose device.
Frequency (81) Protection
Eight independent frequency elements can be set for over, under, or rate of change (81R) frequency
operation. Each can be set separately to monitor the frequency on the main three-phase voltage input or
the Vx input. Rate of change can be set to operate on positive, negative, or “either”.
Содержание BE1-11g
Страница 1: ...INSTRUCTION MANUAL FOR BE1 11g Generator Protection System Publication 9424200994 Revision U Jul 17...
Страница 2: ......
Страница 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Страница 22: ...10 9424200994 Rev U Introduction BE1 11g...
Страница 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Страница 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Страница 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Страница 61: ...9424200994 Rev U 49 BE1 11g Overexcitation 24 Protection Figure 40 Inverse Time Delay and Reset Time...
Страница 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Страница 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Страница 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Страница 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Страница 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Страница 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Страница 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Страница 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Страница 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Страница 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Страница 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Страница 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Страница 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Страница 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Страница 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Страница 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Страница 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Страница 236: ...224 9424200994 Rev U Alarms BE1 11g...
Страница 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Страница 248: ...236 9424200994 Rev U Demands BE1 11g...
Страница 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Страница 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Страница 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Страница 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Страница 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Страница 280: ...268 9424200994 Rev U Mounting BE1 11g Figure 196 Retrofit Mounting Plate Basler P N 9424200073 Part 2...
Страница 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Страница 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Страница 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Страница 290: ...278 9424200994 Rev U Mounting BE1 11g...
Страница 297: ...9424200994 Rev U 285 BE1 11g Terminals and Connectors Figure 215 Example of Reversed CT Polarity...
Страница 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Страница 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Страница 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Страница 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Страница 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Страница 367: ...9424200994 Rev U 355 BE1 11g Timekeeping Figure 275 Front Panel Circuit Board Backup Battery Location...
Страница 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Страница 374: ...362 9424200994 Rev U Device Information BE1 11g...
Страница 392: ...380 9424200994 Rev U Configuration BE1 11g...
Страница 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Страница 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Страница 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Страница 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Страница 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Страница 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Страница 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Страница 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Страница 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Страница 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Страница 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Страница 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Страница 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Страница 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Страница 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Страница 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Страница 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Страница 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Страница 622: ...610 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 357 Time Characteristic Curve A Standard Inverse BS 142...
Страница 630: ...618 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 365 Time Characteristic Curve G Long Time Inverse BS 142...
Страница 633: ...9424200994 Rev U 621 BE1 11g Time Curve Characteristics Figure 368 Time Characteristic Curve B Very Inverse BS 142...
Страница 638: ...626 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 373 Time Characteristic Curve C Extremely Inverse BS 142...
Страница 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Страница 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Страница 705: ......