Fuse Loss (60FL)
BE1-11
g
Table 97. Fuse Loss Logic Parameters
Input
True Condition
A
Positive-sequence volts greater than 8.8% of the nominal voltage; Detects minimum voltage is applied.
B
Positive-sequence amps greater than 8.8% of the nominal current; Detects minimum current is applied.
C
Negative-sequence volts greater than 25% of the pos-seq volts; Detects loss of 1 or 2 phase voltages.
D
Negative-sequence amps less than 17.7% of the pos-seq amps; Detects a normal current condition.
E
Positive-sequence volts less than 8.8% of the nominal voltage; Detects loss of three-phase voltage.
F
Positive-sequence amps less than 200% of the nominal current; Detects a normal load current condition.
G
Three-wire or four-wire sensing selected.
H
Positive-sequence volts greater than 85% of nominal voltage; Detects a restored voltage condition.
J
(B + S); Detects breaker position and nominal current condition.
K
(A * C * G * J * P); Detects when either one or two phases are lost.
L
(E * F * G * J); Detects when all three phases are lost.
M, N
Latches the 60FL output until the reset criteria are met.
P
(R+D); Logical OR of comparators R and D to detect a normal current condition.
R
Negative-sequence amps less than 15% of the nominal current; Detects a normal current condition.
S
Breaker Status is configured by the Breaker Status logic block. Information on setting up the breaker
status logic can be found in the
Breaker Monitoring
chapter. The Ignore Breaker Status setting is found
on the 60FL settings screen. (Enabled = 1, Disabled = 0)
Function Blocking
User selectable block settings determine how the 51/27, 24, 25, 25A, 27, 59, 78V, 27X, 59X, 32, 40Z, and
67 protection functions operate when a fuse loss condition exists. The Block Voltage Control (51/27)
setting assumes that the voltage is V
NOM
when Fuse Loss is true because the voltage measurement is not
present or is unreliable. If the input voltage is nominal, then voltage restraint and control have no effect.
The Block Voltage settings determine which voltage functions are blocked when the Fuse Loss logic is
true. The Block Power/Power Factor setting blocks the power based functions when the Fuse Loss logic
is true. The Block Impedance setting blocks the impedance based functions when the Fuse Loss logic is
true.
Note
Protective elements blocked by 60FL should be set so that trip times
are 60 milliseconds or greater to assure proper coordination of
blocking.
Directional Supervision
The directional tests are also supervised by the fuse loss element. If the 60FL logic is true, then voltage
sensing was lost or is unreliable. Under this condition positive, negative, and zero-sequence directional
tests are disabled and their bits are cleared. There is no user setting to enable or disable this supervision.
Current polarization is not affected by the 60FL since it does not rely on voltage sensing. Similarly, zero-
sequence voltage polarization can be performed only if 3P4W sensing is selected. The following qualifiers
are applied to the voltage polarized ground direction element based on the user selected input quantity:
•
V0IN inputs:
Test: 60FL=FALSE & 3P4W=TRUE & (IN > minimum) & (IN > I1*8%) & (V0 > minimum)
•
V0IG inputs:
Test: 60FL=FALSE & 3P4W=TRUE & (IG > minimum) & (V0 > minimum)
•
VXIN inputs:
Test: (IG > minimum) & (IN > I1*8%) & (VX > minimum)
•
VXIG inputs:
Test: (IG > minimum) & (VX > minimum)
Содержание BE1-11g
Страница 1: ...INSTRUCTION MANUAL FOR BE1 11g Generator Protection System Publication 9424200994 Revision U Jul 17...
Страница 2: ......
Страница 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Страница 22: ...10 9424200994 Rev U Introduction BE1 11g...
Страница 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Страница 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Страница 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Страница 61: ...9424200994 Rev U 49 BE1 11g Overexcitation 24 Protection Figure 40 Inverse Time Delay and Reset Time...
Страница 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Страница 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Страница 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Страница 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Страница 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Страница 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Страница 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Страница 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Страница 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Страница 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Страница 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Страница 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Страница 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Страница 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Страница 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Страница 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Страница 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Страница 236: ...224 9424200994 Rev U Alarms BE1 11g...
Страница 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Страница 248: ...236 9424200994 Rev U Demands BE1 11g...
Страница 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Страница 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Страница 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Страница 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Страница 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Страница 280: ...268 9424200994 Rev U Mounting BE1 11g Figure 196 Retrofit Mounting Plate Basler P N 9424200073 Part 2...
Страница 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Страница 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Страница 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Страница 290: ...278 9424200994 Rev U Mounting BE1 11g...
Страница 297: ...9424200994 Rev U 285 BE1 11g Terminals and Connectors Figure 215 Example of Reversed CT Polarity...
Страница 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Страница 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Страница 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Страница 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Страница 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Страница 367: ...9424200994 Rev U 355 BE1 11g Timekeeping Figure 275 Front Panel Circuit Board Backup Battery Location...
Страница 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Страница 374: ...362 9424200994 Rev U Device Information BE1 11g...
Страница 392: ...380 9424200994 Rev U Configuration BE1 11g...
Страница 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Страница 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Страница 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Страница 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Страница 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Страница 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Страница 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Страница 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Страница 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Страница 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Страница 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Страница 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Страница 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Страница 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Страница 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Страница 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Страница 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Страница 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Страница 622: ...610 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 357 Time Characteristic Curve A Standard Inverse BS 142...
Страница 630: ...618 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 365 Time Characteristic Curve G Long Time Inverse BS 142...
Страница 633: ...9424200994 Rev U 621 BE1 11g Time Curve Characteristics Figure 368 Time Characteristic Curve B Very Inverse BS 142...
Страница 638: ...626 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 373 Time Characteristic Curve C Extremely Inverse BS 142...
Страница 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Страница 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Страница 705: ......