EXACTUS IFD-5 and IFA-5 User Guide

   

 

If the modules are not to be stacked, the connections are wired the same as described above in 
figure 2.0.  The IFA-5 Module and the IFD-5 Module can be wired up to 50 meters from each 
other.  Shielded wiring is recommended for distances greater than a few meters or if the 
electronics are mounted in an area of high electromagnetic interference.   

The voltage and current output connections are adjacent to the power and digital communication 
connections.  For a voltage output, connect to “+V out” and “-V out”, and for a current output 
connect to “+I out” and “-I out”.  

 

3.2  Optional External Power  

The internal power source on the IFA-5 Module will drive the current output through a resistance 
of up to 500 ohms.  The module can drive up to 1050 ohms if an external 24VDC power source 
is used.   

The IFA-5 Module is supplied configured for internal power.  To configure for external power a 
jumper inside the module must be moved.  The IFA-5 Module and the IFD-5 Module are similar 
in appearance, so make sure you are working with the IFA-5 Module before you proceed. To 
move the jumper, completely remove the two screws that hold the IFA-5 Module case together.  
With one hand, grasp the sides of the module just below the case seam and squeeze firmly; the 
upper and lower covers will separate from each other.  Remove the top cover of the module and 
set it aside. 

Hold the IFA-5 Module so the writing on the circuit board is upright.  There is only one jumper 
on the board, it is labeled JP1 and will be in the upper left-hand side of the board close to the 
module connections.  Three pins allow the jumper to be in one of two positions.  To configure 
for external power, locate the jumper connector onto the bottom two pins, to configure for 
internal power locate the jumper connector onto the top two pins.  See Figure 3 below for details. 

 

Figure 3

 

 

 

 

 

 

 

 

Содержание EXACTUS IFA-5

Страница 1: ...ta proportions weights etc given herein may change without prior information and do not constitute the agreed contractual quality of the product It is the responsibility of the recipient of our produc...

Страница 2: ...Optics either a lightpipe or lens assembly Ex 100 Electronics SST tube dimension 1 0 diameter 4 0 long 25 4mm 102mm IFD 5 Interface module for conditioning power and communicating with a PC Dimension...

Страница 3: ...em is powered with a DC Power Supply through the IFD 5 Digital Interface Module as shown in Fig 1 0 The IFD 5 Module may be powered by any DC voltage between 12 and 24VDC The IFD 5 supplies power for...

Страница 4: ...vides a connector designed for use when the two modules are stacked When the two modules are stacked vertically the power input and digital communications connections are pin for pin directly above on...

Страница 5: ...dule is supplied configured for internal power To configure for external power a jumper inside the module must be moved The IFA 5 Module and the IFD 5 Module are similar in appearance so make sure you...

Страница 6: ...es above the graphical display Open the Pyrometer Settings menu for the pyrometer that is to be configured and follow the steps below 1 Select the Analog Output tab See Figure 5 below 2 Click the Use...

Страница 7: ...e table If the temperature goes below the temperature assigned to 1 volt the output will stay at 1 volt If the temperature exceeds the temperature assigned to 5 volts the output will stay at 5 volts T...

Страница 8: ...atchdog Failure Alarm Timeout In ____ box The Configure IFA 5 Module menu accessed through Menu Options Configure IFA 5 Module is used to set the Watchdog Failure Signal Level current or voltage level...

Страница 9: ...the meter should be connected in series 5 Configure the IFA 5 Module for Internal Power see instructions for Optional External Power 6 Make sure the IFA 5 Module has been running for at least 30 minu...

Страница 10: ...to 30VDC Power Consumption with IFD 5 IFA 5 and Pyrometer sensor 3 watts 125mA 24VDC Pin 1 10 Assignments Pin 1 GND Pins 1 3 5 and 10 are internally connected Pin 2 Isolates pyrometer if open COM pow...

Страница 11: ...racy 0 02 of FSR Resolution 0 002 of FSR Readback Accuracy 1 of FSR Zero Drift Voltage output 10 V C Current output 0 2 A C Span Temperature Coefficient 5ppm C Accuracy 0 02 of FSR Resolution 0 002 of...

Страница 12: ...and IFA 5 User Guide 9 5 1 IFD 5 and IFA 5 Support Cabinets Figure 8 Electronics support cabinet layout example Integrated Instrument System Figure 7 Electronics support cabinet layout example Fiber...

Страница 13: ...tput C Cooling Fan if used Active air cooling from the air purge system is the preferred method of cooling the cabinet as it reduces the risk of introducing contaminants to the cabinet D Digital Inter...

Страница 14: ...st temperature The temperature should not exceed 70 C Exceeding this temperature will not damage the electronics but may affect the temperature measurement accuracy If the temperature exceeds 80 C fai...