EXACTUS IFD-5 and IFA-5 User Guide
8
IFA-5 Input/Output
Input Voltage Range
(supplied by IFD-5)
Standard: 24VDC (+10VDC to +30VDC)
Power Consumption (with IFD-5, IFA-5,
and Pyrometer sensor)
3 watts, 125mA, 24VDC
Pin 1 – 10 Assignments
(Isolated Analog Output - 3000VDC)
Pin 1 +I (0 to 20mA output)
Pin 2
-I (0 to 20mA output
Pin 3 +V (0 to 10VDC output)
Pin 4 -V (0 to 10VDC output)
Pin 5 Ext. Pwr (0 to 20mA loop power 24VDC)
Pin 6 Init (N/C - for manufacture use only)
Pin 7 D+ RS485 communications to IFD-5
Pin 8 D- RS485 communications to IFD-5
Pin 9 +Vs (power from IFD-5)
Pin 10 GND (circuit ground)
10 pin Terminal – pin spacing
5.08mm
Analog Outputs
0 to 20mA
0 to 10 Volts
0 – 10 Voltage Output
10mA maximum
Accuracy
± 0.02% of FSR
Resolution
± 0.002% of FSR
Readback Accuracy
± 1% of FSR
Zero Drift
Voltage output: ± 10µV/°C
Current output: ± 0.2µA/°C
Span Temperature Coefficient
± 5ppm/°C
Accuracy
± 0.02% of FSR
Resolution
± 0.002% of FSR
Current Load Resistance
Internal power : 500 ohms
External 24VDC power: 1050 ohms
Update Rate
Adjustable up to 100 readings per second.
5.0 Mounting
•
The backs of both the IFD-5 Digital Interface Module and IFA-5 Analog Output Module
have attachments for easy DIN rail mounting. To attach the modules to a DIN rail pull the
orange tab at the bottom of the module out, slip the module onto the DIN rail and push the
tab back in to secure the module to the rail. A short piece of DIN rail is provided for
mounting the Module to solid surfaces.
•
It is recommended that the modules be mounted in a cabinet or NEMA enclosure rated for
area of use. See mounting examples in section 5.1