background image

23 

 

Overrides  

Not only is the ClimateBoss programmed for automatic operation but it can also give the grower 

temporary overrides of the target temperature, manual start of the timer or dehumidification options, 
and on/off control of each output. 

Target Temperature (Set Point) Override 

The target temperature can be temporarily changed from the 

controller’s home screen. This feature is primarily used for when you want to 
change the growing temperature because it is too uncomfortable to work in, but 
you want to revert back to the automatic program after you have completed 
your task.  

To override, press the area of the home screen that says the zone you 

are working in and SP = ? underneath. See Figure 17: Set Point Override. By tapping that box, you will be 
brought to a screen to enter a temperature. Entering a value will turn the Set Point green on the home 
screen, signaling a manual override. The temperature will reset back to the normal programmed set 
point (see Stages, page 13) during the next stage transition (DIF, DAY, NIGHT). 

Vent Cycle or Timer Manual Start 

The dehumidification vent cycle or a timer cycle can be manually started. This allows you to 

program a cycle, set it to off and run it only on a manual cycle. For instructions on how to manually start 
one of these cycles, see Page 15 for the vent cycle and Page 18 for the timer cycle. 

Outputs 

Each Heat or Cool output can be set to on or off, in addition to the automatic function. This will 

override the safety checks and you may have instances where the heats and cools run at the same time. 
For information on how to manually turn on or off an output, see Page 14, Outputs.  

Error Codes 

Clock – indicates that the controller’s clock is not functioning properly.   

TH1 – indicates that thermistor 1 has a short circuit or an open circuit 

TH2 – indicates that thermistor 2 has a short circuit or an open circuit 

T1 Low – Indicates a low temperature alarm in Zone 1 

T2 Low – Indicates a low temperature alarm in Zone 2  

T1 High – Indicates a high temperature alarm in Zone 1 

T2 High – Indicates a high temperature alarm in Zone 2 

 

 

Figure 17: Set 

Point Override

 

Содержание ClimateBoss

Страница 1: ...CLIMATEBOSS Controller Louver Fan GHK Mode Operation Manual BARTLETT Instrument Co 1032 Avenue H Fort Madison IA 52627 319 372 8366 www bartinst com...

Страница 2: ...0 Vent C D Settings 10 Timer Mister 1 2 10 Dehumidify 11 Statistics 11 Settings 11 Configuration 12 Programming 14 Stages DIF DAY NIGHT 14 Outputs Heat 1 Cool 1 14 Date Time 15 Dehumidification Vent C...

Страница 3: ...ter COOL 1 to allow louvers to open In two zone mode COOL 2 and COOL 4 will not activate for 30 seconds after COOL 1 and COOL 3 respectively Definitions First we need to define and understand some ter...

Страница 4: ...nly displays when Auxiliary options C or CH are enabled Press to change settings Current Stage Displays the controller s current stage DIF DAY or NITE Graph Button Press to view graph of the controlle...

Страница 5: ...p to change settings Outside Weather Displays current temperature outside Tap to view status and settings of Wind Rain alarm if connected Timers Timer outputs used for lights irrigation or other equip...

Страница 6: ...erature for each stage and 24hr period Helps with troubleshooting and graphical tracking Timer Mister output for lights or irrigation fogging Humidity probe input to trigger the dehumidification vent...

Страница 7: ...u to lower the temperature at night to save on heating Controller Operations Target Temperature The figure below explains the workings of the stages DIF DAY and NIGHT Figure 4 shows the controller pro...

Страница 8: ...to the target temperature for each output Controller Operations Output Temperature Using the information in Figure 4 Figure 5 if the time is 8 00 AM the operating stage is DIF and the target temperatu...

Страница 9: ...iances but will also give a wider swing in temperature The hysteresis can be set to values of 1 2 or 3 through the menu options Using the output temperatures from Table 1 and a hysteresis setting of 1...

Страница 10: ...mes on based on their offset Each output has an offset or step temperature to be added to Cools or subtracted from Heats the set point to determine when each output will activate As the controller cha...

Страница 11: ...e the last reset Settings Zone 1 Low Alarm Used to set the temperature for Zone 1 low alarm Default 32 F Zone 1 High Alarm Used to set the temperature for Zone 1 high alarm Default 131 F Zone 2 Low Al...

Страница 12: ...s used in conjunction with the Headgrower mobile app for remote monitoring and control of the Climate Boss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmwa...

Страница 13: ...parate sensor thermistor for controlling boilers or bench heat Option CH combines Option C Option H to add both a proportional Curtain Vent control and a 3rd Heat option Timer Alarm Shade The Timer an...

Страница 14: ...ext screen then press save To edit a temperature follow the same steps except under the zone1 or zone2 column entering your desired temperature on the next screen You can see the timeline of your sett...

Страница 15: ...btracting your step value see Table 1 on page 8 Therefore you edit this value by changing the step value seen below SP To change your offset value press the green number in the SP row Enter your value...

Страница 16: ...r high You can change it to use a custom value by pressing the checkbox next to set temperature and entering a value The limits can only be set between the values of 32 and 131 Stage Enable Choose wha...

Страница 17: ...are in Timed mode Press it to toggle between on and off If on the vent cycle will continue to activate at its start time every day If off the vent cycle will activate at its start time a single time b...

Страница 18: ...utes format The maximum entry is 23 hours and 59 minutes 23 59 Repeat To choose whether it will repeat the following day press the repeat box like seen in Figure 10 This will toggle between on and off...

Страница 19: ...rtain opens and the run time will determine how long it stays open At the end of the timer the alarm will activate sending a message to CIS that you can ignore and closing your curtain shade Curtain V...

Страница 20: ...tep before the curtain vent will open or close to the next setting Tap this box to enter a value between 1 and 9 minutes Open Time You ll need to manually measure the amount of time in seconds to manu...

Страница 21: ...e mid right of the screen See figure 15 The Heat 3 output is currently active if the box surrounding Heat 3 is red Grey indicates inactivity Wind Rain Alarm Integration If your operation has both our...

Страница 22: ...ler s home screen The ClimateBoss also tracks the run time of each of the outputs Heat 1 Heat 2 Cool 1 Cool 2 Cool 3 Cool 4 and Heat 3 H and CH versions The ClimateBoss will store the information unti...

Страница 23: ...set point see Stages page 13 during the next stage transition DIF DAY NIGHT Vent Cycle or Timer Manual Start The dehumidification vent cycle or a timer cycle can be manually started This allows you to...

Страница 24: ...mum setting of 55 Minimum setting of 1 DAY target temperature 18 Maximum setting of 55 Minimum setting of 1 NITE target temperature 18 Maximum setting of 55 Minimum setting of 1 Hysteresis setting 1 N...

Страница 25: ...N SETTING Temperature Speed Units Fahrenheit F mph CIS ID 1 On to Auto time 10 Heat Cool Delay 15 Hysteresis 1 cannot be changed Alarms both zones Low 32 F High 131 F Number of Zones 1 Thermistor Fail...

Страница 26: ...ed when the calibration code is requested below The calibration code is also located on the label inside the humidity sensor casing To change enter your calibration code go to Menu Configuration Humid...

Отзывы: