background image

19 

 

Timer/Alarm for Shade Curtain Control 

The Timer and Alarm Outputs can be used to run a shade or energy curtain. The timer is used as 

the extend signal and the alarm is used as the retract signal.  

There are four things to note about this function: 

 

This can only be done if the Alarm output is NOT being used.  

 

The alarm (which doesn’t actually signal any problems) will still be displayed and sent to CIS as 
normal. 

 

This does not use or affect your Zone 1 Low/High or Zone 2 Low/High Settings or the function of 
those alarms, it is only using the alarm relay connected to your shade or curtain to signal it to 
close.  

 

The Timer/Alarm feature coordinates the outputs to give a 10-second delay between extend 
and retract signals to allow the motor to come to a complete stop before changing directions. 

To program the TIMER/ALARM for curtain control go to Menu > Configuration > Timer Alarm 

Shade. Here, select ON, then press save. With the mode activated, you now need to set the timer like in 
the Timer Mode section above. The start time will determine when the curtain opens and the run time 
will determine how long it stays open. At the end of the timer, the alarm will activate, sending a 
message to CIS (that you can ignore) and closing your curtain/shade. 

Curtain/Vent Control

 

The Curtain/Vent control option adds the ability to open a curtain, roof vent, or vent window in 

5 proportional steps. This includes a step size, or a programmable number of degrees above the target 
temperature. As the temperature rises above the target temperature, the output will open to the 
percentage that is proportional to the number of steps the temperature is above the target temp. For 
example, if the temperature rises to more than 1 step above the target temperature, the output will 
open to percentage 1. As it continues to rise above the next step, the output will open to percentage 2. 
If it decreases to just one step above the target temperature the output will close to percentage 1. 

All models of the ClimateBoss come with at least one vent output, but the C or CH upgrade 

includes another output, output C, accessible from the home screen. The default output, output D, is 
available from the “more” screen of the home screen. 

PERCENT 5 

PERCENT 4 

PERCENT 3 

PERCENT 2 

PERCENT 1 

TARGET TEMPERATURE 

STEP 

Figure 12: Curtain and Vent Control

 

Содержание ClimateBoss

Страница 1: ...CLIMATEBOSS Controller Louver Fan GHK Mode Operation Manual BARTLETT Instrument Co 1032 Avenue H Fort Madison IA 52627 319 372 8366 www bartinst com...

Страница 2: ...0 Vent C D Settings 10 Timer Mister 1 2 10 Dehumidify 11 Statistics 11 Settings 11 Configuration 12 Programming 14 Stages DIF DAY NIGHT 14 Outputs Heat 1 Cool 1 14 Date Time 15 Dehumidification Vent C...

Страница 3: ...ter COOL 1 to allow louvers to open In two zone mode COOL 2 and COOL 4 will not activate for 30 seconds after COOL 1 and COOL 3 respectively Definitions First we need to define and understand some ter...

Страница 4: ...nly displays when Auxiliary options C or CH are enabled Press to change settings Current Stage Displays the controller s current stage DIF DAY or NITE Graph Button Press to view graph of the controlle...

Страница 5: ...p to change settings Outside Weather Displays current temperature outside Tap to view status and settings of Wind Rain alarm if connected Timers Timer outputs used for lights irrigation or other equip...

Страница 6: ...erature for each stage and 24hr period Helps with troubleshooting and graphical tracking Timer Mister output for lights or irrigation fogging Humidity probe input to trigger the dehumidification vent...

Страница 7: ...u to lower the temperature at night to save on heating Controller Operations Target Temperature The figure below explains the workings of the stages DIF DAY and NIGHT Figure 4 shows the controller pro...

Страница 8: ...to the target temperature for each output Controller Operations Output Temperature Using the information in Figure 4 Figure 5 if the time is 8 00 AM the operating stage is DIF and the target temperatu...

Страница 9: ...iances but will also give a wider swing in temperature The hysteresis can be set to values of 1 2 or 3 through the menu options Using the output temperatures from Table 1 and a hysteresis setting of 1...

Страница 10: ...mes on based on their offset Each output has an offset or step temperature to be added to Cools or subtracted from Heats the set point to determine when each output will activate As the controller cha...

Страница 11: ...e the last reset Settings Zone 1 Low Alarm Used to set the temperature for Zone 1 low alarm Default 32 F Zone 1 High Alarm Used to set the temperature for Zone 1 high alarm Default 131 F Zone 2 Low Al...

Страница 12: ...s used in conjunction with the Headgrower mobile app for remote monitoring and control of the Climate Boss See the WiFi section for more information about firmware updates WiFi Set up Wi Fi for Firmwa...

Страница 13: ...parate sensor thermistor for controlling boilers or bench heat Option CH combines Option C Option H to add both a proportional Curtain Vent control and a 3rd Heat option Timer Alarm Shade The Timer an...

Страница 14: ...ext screen then press save To edit a temperature follow the same steps except under the zone1 or zone2 column entering your desired temperature on the next screen You can see the timeline of your sett...

Страница 15: ...btracting your step value see Table 1 on page 8 Therefore you edit this value by changing the step value seen below SP To change your offset value press the green number in the SP row Enter your value...

Страница 16: ...r high You can change it to use a custom value by pressing the checkbox next to set temperature and entering a value The limits can only be set between the values of 32 and 131 Stage Enable Choose wha...

Страница 17: ...are in Timed mode Press it to toggle between on and off If on the vent cycle will continue to activate at its start time every day If off the vent cycle will activate at its start time a single time b...

Страница 18: ...utes format The maximum entry is 23 hours and 59 minutes 23 59 Repeat To choose whether it will repeat the following day press the repeat box like seen in Figure 10 This will toggle between on and off...

Страница 19: ...rtain opens and the run time will determine how long it stays open At the end of the timer the alarm will activate sending a message to CIS that you can ignore and closing your curtain shade Curtain V...

Страница 20: ...tep before the curtain vent will open or close to the next setting Tap this box to enter a value between 1 and 9 minutes Open Time You ll need to manually measure the amount of time in seconds to manu...

Страница 21: ...e mid right of the screen See figure 15 The Heat 3 output is currently active if the box surrounding Heat 3 is red Grey indicates inactivity Wind Rain Alarm Integration If your operation has both our...

Страница 22: ...ler s home screen The ClimateBoss also tracks the run time of each of the outputs Heat 1 Heat 2 Cool 1 Cool 2 Cool 3 Cool 4 and Heat 3 H and CH versions The ClimateBoss will store the information unti...

Страница 23: ...set point see Stages page 13 during the next stage transition DIF DAY NIGHT Vent Cycle or Timer Manual Start The dehumidification vent cycle or a timer cycle can be manually started This allows you to...

Страница 24: ...mum setting of 55 Minimum setting of 1 DAY target temperature 18 Maximum setting of 55 Minimum setting of 1 NITE target temperature 18 Maximum setting of 55 Minimum setting of 1 Hysteresis setting 1 N...

Страница 25: ...N SETTING Temperature Speed Units Fahrenheit F mph CIS ID 1 On to Auto time 10 Heat Cool Delay 15 Hysteresis 1 cannot be changed Alarms both zones Low 32 F High 131 F Number of Zones 1 Thermistor Fail...

Страница 26: ...ed when the calibration code is requested below The calibration code is also located on the label inside the humidity sensor casing To change enter your calibration code go to Menu Configuration Humid...

Отзывы: