Operating Instructions
SILAS
Controller for Zones 2 and 22
Version 2.00
Page 27 of 28
SILAS_E_110806.doc Operating Instructions for the SILAS Controller
•
Technical data are subject to change
Characteristics of the SILAS Controller:
Parameters:
Rotary
switch and
pos.
Description
Default value
Switching value
Checked
Function
S2
Pos 1
The type of function must be selected in accordance
with the chapter on “Settings”.
Yes
PRG _____________
Purging time
S 2
Pos 2
The purging time is:
1:00
Min Sec.
P1
S2
Pos 3
Minimum overpressure between enclosure and
atmosphere (disconnection threshold)
1.0 mbar
P2
S2
Pos 4
Pre-alarm 1.5
mbar
P3
S1
Pos 5
Minimum overpressure between enclosure and
atmosphere (purging pressure)
15.0 mbar
P4
S1
Pos 6
The maximum overpressure between enclosure and
atmosphere (disconnection threshold)
20.0 mbar
Delay
S1
Pos 7
General time delay of relays K1 to K 3 for fluctuations in
the pressure air
5
seconds
K 3
S1
Pos 8
Function of K 3 relay
(K 2 = relay switching simultaneously with K 2)
K 2
Pressure test
Check the 1.5 times maximum pressure for 2 minutes:
no permanent deformation at the SCC.
OK
Disconnection MIN
Check alarm / disconnection minimum pressure
SILAS emits alarm or SCC switches off.
OK
Key-operated switch
Check the bypass key-operated switch
SILAS does not emit an alarm or SCC does not switch
off.
OK
Comments:
Tester:
Date: