Operating Instructions
SILAS
Controller for Zones 2 and 22
Version 2.00
Page 18 of 28
SILAS_E_110806.doc Operating Instructions for the SILAS Controller
•
Technical data are subject to change
8.
Circuit Diagram
8.1
Circuit Diagram
8.2
Changing the SI 1 Fuse for the Purge Valve
The
SILAS
Controller's
junction box has a fuse holder for a 5 x 20 mm fuse. This fuse serves to protect a digital purge
valve connected to the terminals 6,10 and 13. The fuse rating may not exceed the value of 3 x I
Nominal
of the valve’s nominal
current.
Observe the following when changing:
- Disconnect from voltage supply before changing the integrated SI 1 valve fuse.
Factory-fitted fuse values: mains voltage AC 230 V / 80 mA; AC 115 V / 160 mA; DC 24 V / 500 mA
13
N
L +
7
8
9
10
11
PE
12
µ-Controller
6
4
5
SI 1
K 1
LED 1
K 2
LED 2
Alarm
2
3
1
K 3
LED 3
Parameter
SET
ON/OFF
Yellow
Green
Yellow
Power
supply
Purge valve
Operate