Operating Instructions
SILAS
Controller for Zones 2 and 22
Version 2.00
Page 21 of 28
SILAS_E_110806.doc Operating Instructions for the SILAS Controller
•
Technical data are subject to change
K 2 +
Operate
Switches simultaneously with K2
P 1 +
MIN-Alarm
Switches on if the P 1 pressure value is
exceeded.
P 1 -
MIN-Alarm
Switches off if the value falls short of the
P 1 pressure.
P 2+
Prealarm
Switches on if the P 2 pressure value is
exceeded
P 2-
Prealarm
Switches off if the value falls short of the
P 2 pressure
P 3+
Purge pressure
Switches on if the P 3 pressure value is
exceeded
P 4+
Maxalarm
Switches on if the P 4 pressure value is
exceeded
PT+
Purge timet
Switches on when the purging time
counts down.
BYP
Bypass
Switches on if the bypass is activated.
7
Function of Relais K 3
ALR
Functions-Alarm Switches off in the event of internal
malfunctioning
8
Time delay ( sec)
DLY
General time delay for purging time bypassing and “MIN”
disconnection
9 Bypass NORMAL
The bypass function is activated with position 9 of S 2 and
setting the bypass bridge. The bypass function is deactivated
by removing the bypass bridge or altering the position of the
switch