background image

Manual 2100-365
Page  14

13. FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in
the service panel.

If the unit is equipped with a fresh air damper
assembly, the assembly is shipped already attached to
the unit.  The damper blade is locked in the closed
position.  To allow the damper to operate, the
maximum and minimum blade position stops must be
installed.  See Figure  9.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air
damper shipped with each unit.

One of several other ventilation options may be
installed.  Refer to model number and/or
supplemental installation instructions.

14. CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or
vented type system to assure proper drainage.

15. WIRING – MAIN POWER

FIGURE  9

FRESH AIR DAMPER

BLADE IS
LOCKED CLOSED
FOR SHIPPING

MIS-938

Refer to unit rating plate for wire sizing information
and maximum fuse or “HACR” type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
All models are suitable only for connection with
copper wire.  Each unit and/or wiring diagram will be
marked - “

Use Copper Conductors Only

”.  These

instructions 

must be

 adhered to.  Refer to the

National Electrical Code (NEC) for complete current
carrying capacity data on the various insulation
grades of wiring material.  All wiring must conform
to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure
that there will be no nuisance tripping due to the
momentary high starting current of the compressor
motor.

The disconnect access door on this unit may be
locked to prevent unauthorized access to the
disconnect.  To convert for the locking capability
bend the tab located in the bottom left hand corner of
the disconnect opening under the disconnect access
panel straight out.  This tab will now line up with the
slot in the door.  When shut a padlock may be placed
through the hole in the tab preventing entry.

See “Start Up” section for important information on
three phase scroll compressor start ups.

        WARNING

For your personal safety, turn off electric power
at service entrance panel before making any
electrical connections.  Failure to do so could
result in electric shock or fire.

        WARNING

Failure to provide an electrical power supply
shut-off means could result in electric shock or
fire.

Содержание WG421

Страница 1: ...RESPONSIBILITY OF INSTALLER TO KNOW AND UNDERSTAND ALL OF THESE REQUIREMENTS FAILURE TO DO SO COULD CREATE A HAZARD RESULTING IN PROPERTY DAMAGE BODILY INJURY OR DEATH INSTALLATION INSTRUCTIONS WG SER...

Страница 2: ...hermostats 16 18 Gas Supply Piping 19 19 Manifold Pressure Adjustment 20 20 Checking Gas Input Rate 20 21 Standard Orifice Sizing High Altitude Derate 21 22 Conversion of Gas Input BTUH From High to L...

Страница 3: ...Electronic Blower Control 29 Figure 17 Furnace Control Board Blower Control 30 Figure 18 460V Blower Motor Wiring Options 31 Figure 19 Fan Blade 37 Figure 20 Low NOx Insert 37 TABLES Table 1 Specifica...

Страница 4: ...Telephone 416 447 4044 COPYRIGHT AUGUST 2000 BARD MANUFACTURING COMPANY BRYAN OHIO 43506 USA Manufactured under the following U S patent numbers 5 485 878 5 002 116 4 924 934 4 875 520 4 4825 936 4 43...

Страница 5: ...t l o V 0 3 2 r o t a l i t n e V y r e v o c e R y g r e n E R 5 A V R E G W t l o V 0 6 4 r o t a l i t n e V y r e v o c e R y g r e n E R 5 C V R E G W VENTILATION OPTIONS 1 Low ambient control is...

Страница 6: ...erant system is completely assembled and charged All internal wiring is complete These instructions and any instructions packaged with any separate equipment required to make up the entire heating coo...

Страница 7: ...0 3 2 0 6 4 s p m A d a o L d e t a R 9 1 5 7 1 3 1 2 1 6 5 1 2 1 2 3 1 5 2 1 2 6 0 3 7 2 5 9 1 7 1 9 t n e r r u C n o i t c e l e S t i u c r i C h c n a r B 9 1 3 1 6 2 2 3 1 4 6 0 3 5 9 1 9 s p m...

Страница 8: ...Manual 2100 365 Page 5 MIS 1352 FIGURE 1 UNIT DIMENSIONS...

Страница 9: ...in the absence of specific recommendations from the local authority having jurisdiction equipment ratings shall be reduced as specified in Section 18 5 TRANSPORTATION DAMAGE All units are packed secu...

Страница 10: ...e Figures 6 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location 4 Mount bottom mounting bracket 5 Hook top rain flashing under back bend of top Top rain flashin...

Страница 11: ...Manual 2100 365 Page 8 FIGURE 2 VENT TERMINAL AND COMBUSTION AIR INTAKE MIS 1469 MIS 1449 FIGURE 3 INTERNAL FILTER ACCESS THROUGH UPPER SERVICE DOOR...

Страница 12: ...Manual 2100 365 Page 9 FIGURE 4 MOUNTING INSTRUCTIONS MIS 1472...

Страница 13: ...le materials This is required for the first three 3 feet of ducting It is important to insure that the one 1 inch minimum spacing is maintained at all points Failure to do this could result in overhea...

Страница 14: ...Manual 2100 365 Page 11 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS MIS 1475 MIS 1476...

Страница 15: ...Manual 2100 365 Page 12 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS MIS 1474...

Страница 16: ...r previous conditions of use 7 If improper venting is observed during any of the above tests the venting system must be corrected 9 CLEARANCES Minimum clearances as specified in Table 2 must be mainta...

Страница 17: ...imum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current All models are suitable only for connection with copper wire Each unit and or wiring diagram w...

Страница 18: ...with the manufacturer s instructions INSTALLATION OF FLEXIBLE CONDUIT THROUGH RETURN AIR OPENING NOTE To allow proper clearance between the control panel and any vent options 90 conduit fittings must...

Страница 19: ...m e t s y S 5 3 0 3 0 4 8 0 8 5 9 F 1 e g a t s 2 t a e h e g a t s 2 o o c l e l b a m m a r g o r P c i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C t a e h e g a t s 1 l o o c e g a t s 1 o t u a n o n...

Страница 20: ...Manual 2100 365 Page 17 FIGURE 11 LOW VOLTAGE WIRING MIS 1162...

Страница 21: ...Manual 2100 365 Page 18 FIGURE 12 GAS PIPE CONNECTION MIS 1478...

Страница 22: ...1 9 1 f o h t g n e L t e e F e p i P e z i S e p i P t u p n I r u o H r e p U T B y t i c a p a C e p i P 2 1 4 3 1 4 1 1 0 1 0 0 0 2 3 1 0 0 0 8 7 2 0 0 0 0 2 5 0 0 0 0 5 0 1 0 2 0 0 0 2 9 0 0 0 0...

Страница 23: ...pingement or overheating of heat exchanger NOTE For natural gas if gas flow rate can t be properly set within these pressure ranges then you must change main burner orifices to obtain proper gas flow...

Страница 24: ...s to consume two cubic feet of gas If dial is one half cubic foot per revolution measure time for four revolutions If dial is one cubic foot per revolution measure time for two revolutions If dial is...

Страница 25: ...2 5 4 2 5 4 2 0 4 2 5 3 2 0 3 2 5 2 2 0 2 2 5 1 2 9 9 8 0 8 8 0 5 2 0 4 2 5 3 2 0 3 2 0 3 2 5 2 2 0 2 2 5 1 2 0 1 2 9 4 9 0 0 9 0 4 2 0 3 2 0 3 2 5 2 2 0 2 2 0 2 2 5 1 2 0 1 2 5 0 2 9 9 9 0 5 9 5 3 2...

Страница 26: ...onditions 30 00 inches Mercury 60F saturated NOTE 2 40 Standard factory installed orifice size 2 30 is shipped with the unit for field installed optional 10 derate All orifice sizes not shown with a b...

Страница 27: ...de the temperature rise range specified on rating plate check duct system design with a qualified heating engineer It may be necessary to re size the duct work Recheck air temperature rise after revis...

Страница 28: ...rgize and go into a soft lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the ALARM OUTPUT Alarm terminal is outp...

Страница 29: ...Manual 2100 365 Page 26 26 LIGHTING AND SHUTDOWN INSTRUCTIONS FIGURE 14 INSTRUCTION LABEL...

Страница 30: ...at exchanger warms up There should be no change in the size or shape of the flame If there is any wavering or blowing of the flame on blower start up it is an indication of a possible leak in the heat...

Страница 31: ...ations Inspect venting system Make sure system has no holes is physically sound and free from obstructions c Make sure the supply and return air flange sleeves or duct work are securely fastened to un...

Страница 32: ...h T d e z i g r e n e s i l a n i m r e t W a a a a a d e z i g r e n e s i r e w o l b r i a n o i t s u b m o C d e h s i l b a t s e s i w o l f r i A s e k a m h c t i w s g n i v o r p r i A d e...

Страница 33: ...g may be required to be removed or added 32 INDOOR BLOWER OPERATION All models have three speed direct drive blower motors If supply and return ducts are connected to the unit the ducts must be of ade...

Страница 34: ...Manual 2100 365 Page 31 FIGURE 18 460 VOLT BLOWER MOTOR WIRING OPTIONS MIS 1487 A B C...

Страница 35: ...1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w o L h g i...

Страница 36: ...4 3 1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M...

Страница 37: ...1 0 3 4 1 0 3 4 1 0 3 1 1 P S E s e h c n I Hs O E D O M G N I L O O C N A F L A U N A M d n a E D O M G N I T A E H l i o C t e W U T B 0 0 0 0 0 1 t u p n I U T B 0 0 0 0 9 h g i H m u i d e M w o...

Страница 38: ...t i w s t u o l l o r n a F l a u n a M n o f I y a l e d f f o d e t c e l e s e h t r o f e t a r e p o l l i w r e w o l b r i a t r o f m o c e h t e t a r e p o o t e u n i t n o c l l i w r e w...

Страница 39: ...5 2 5 7 7 6 2 6 7 2 8 2 8 7 0 0 3 9 7 5 1 3 1 8 2 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 2 7 1 1 2 4 7 6 2 2 6 7 2 4 2 8 7 7 5 2 0 8 4 7 2 1 8 0 9 2 4 8 7 0 3 5 8 3 2 3 7 8 1 4...

Страница 40: ...information FIGURE 19 FAN BLADE TABLE 15 FAN BLADE DIMENSION l e d o M A n o i s n e m i D 1 2 4 G W 1 1 8 4 G W 1 1 0 6 G W 1 Any service work requiring removal or adjustment in the fan and or motor...

Страница 41: ...Manual 2100 365 Page 38...

Страница 42: ...Manual 2100 365 Page 39...

Страница 43: ...Manual 2100 365 Page 40...

Страница 44: ...Manual 2100 365 Page 41...

Страница 45: ...Manual 2100 365 Page 42...

Страница 46: ...Manual 2100 365 Page 43...

Страница 47: ...Manual 2100 365 Page 44...

Страница 48: ...Manual 2100 365 Page 45...

Страница 49: ...Manual 2100 365 Page 46...

Страница 50: ...Manual 2100 365 Page 47...

Страница 51: ...Manual 2100 365 Page 48...

Страница 52: ...Manual 2100 365 Page 49...

Отзывы: