manualshive.com logo in svg
background image

Manual 2100-385B
Page

12

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR" type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire.  Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be

 adhered

to.  Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material.  All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75° C
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to insure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab, located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel, straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.

Five (5) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A five conductor, 18
gauge copper, color-coded thermostat cable is
recommended.  The connection points are shown in
Figure 8.

WIRING — LOW VOLTAGE WIRING

230/208V – 1 phase and 3 phase equipment dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation,
reconnect from 240V to 208V tap.  The acceptable
operating voltage range for the 240V and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

TABLE 4

WALL THERMOSTAT AND SUBBASE

COMBINATIONS

TABLE  3

THERMOSTAT WIRE SIZE

r

e

m

r

o

f

s

n

a

r

T

A

V

A

L

F

e

g

u

a

G

e

r

i

W

m

u

m

i

x

a

M

n

i

e

c

n

a

t

s

i

D

t

e

e

F

5

5

3

.

2

e

g

u

a

G

0

2

e

g

u

a

G

8

1

e

g

u

a

G

6

1

e

g

u

a

G

4

1

e

g

u

a

G

2

1

5

4

0

6

0

0

1

0

6

1

0

5

2

t

a

t

s

o

m

r

e

h

T

e

s

a

b

b

u

S

s

e

r

u

t

a

e

F

e

t

a

n

i

m

o

d

e

r

P

2

0

0

-

3

0

4

8

1

1

1

3

F

7

8

T

3

0

0

-

4

0

4

8

0

2

2

1

A

9

3

5

Q

l

o

o

c

e

g

a

t

s

1

,

t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

f

f

o

-

t

a

e

h

:

m

e

t

s

y

S

1

4

0

-

3

0

4

8

C

4

3

0

8

T

-

-

-

l

o

o

c

e

g

a

t

s

1

,

t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

f

f

o

-

t

a

e

h

:

m

e

t

s

y

S

9

1

0

-

3

0

4

8

0

6

7

1

C

4

7

8

T

2

1

0

-

4

0

4

8

1

0

0

1

A

4

7

6

Q

t

a

e

h

e

g

a

t

s

2

,

l

o

o

c

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

o

t

u

a

-

t

a

e

h

:

m

e

t

s

y

S

1

2

0

-

3

0

4

8

4

3

9

1

D

4

7

8

T

2

1

0

-

4

0

4

8

1

0

0

1

A

4

7

6

Q

t

a

e

h

e

g

a

t

s

2

,

l

o

o

c

e

g

a

t

s

2

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

o

t

u

a

-

t

a

e

h

:

m

e

t

s

y

S

5

3

0

-

3

0

4

8

0

8

-

5

9

F

1

-

-

-

t

a

e

h

e

g

a

t

s

2

,

l

o

o

c

e

g

a

t

s

2

g

n

i

m

m

a

r

g

o

r

p

y

a

d

7

c

i

n

o

r

t

c

e

l

E

3

4

0

-

3

0

4

8

0

0

2

-

M

C

-

-

-

l

o

o

c

e

g

a

t

s

1

,

t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

f

f

o

-

t

a

e

h

:

m

e

t

s

y

S

Содержание WE252

Страница 1: ...STRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models WE252 WE301 WE371 WE421 WE482 WE602 WE701 Manual No 2100 385B Supersedes 2100 385A File Volume III Tab 16 Date 04 25 05 Bard Manufacturing Compa...

Страница 2: ...gerant Service Procedures Considerations 20 Charging 20 Leaks 20 Figures Figure 1 Unit Dimensions 4 Figure 2 Fresh Air Damper Assembly 6 Figure 3 Mounting Instructions 8 Figure 4 Electric Heat Clearan...

Страница 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Страница 4: ...DAMPER V COMMERCIALVENTILATOR MOTORIZED WITH EXHAUST E ECONOMIZER INTERNAL FULLY MODULATING WITH EXHAUST R ENERGY RECOVERY VENTILATOR MOTORIZED WITH EXHAUST TABLE 1 ELECTRIC HEAT TABLE s l e d o M D...

Страница 5: ...i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t i u c r i C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W Z 0 D 2 5 2 E W 5 0 D 8 0...

Страница 6: ...7 2 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 4 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 2 1 0 5 0 2 1 1 2 4 E W 2 8 4 E W 2 0 6 E W 5 7 0 2 4 2 3...

Страница 7: ...local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the...

Страница 8: ...is shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 Cap...

Страница 9: ...clearance to combustible material However it is highly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figures...

Страница 10: ...Manual 2100 385B Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 1641 SEE FIGURE 4 FOR FURTHER DETAILS...

Страница 11: ...hat the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE A 1 4...

Страница 12: ...L AROUND RETURN DUCT OPENING A I C K THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS ATTACH TO BOTTOM PLATE OF WALL 2 x 6 1 000 CLE...

Страница 13: ...OOR WALL SLEEVE CLOSET WALL LOWERED CEILING SUPPLY AIR GRILLE FINISHED CEILING SURFACE RAIN FLASHING SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE S...

Страница 14: ...through the hole in the tab preventing entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is r...

Страница 15: ...Manual 2100 385B Page 13 FIGURE 8 LOW VOLTAGE WIRING DIAGRAM MIS 1373...

Страница 16: ...h monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes pl...

Страница 17: ...DOB set at 2 minutes and DOM is 132 seconds Unit 2 DOB set at 4 minutes and DOM is 144 seconds PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent...

Страница 18: ...mance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry b...

Страница 19: ...h g i H d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S w o L y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l...

Страница 20: ...e d i S w o L e d i S h g i H 8 8 8 3 2 0 9 6 5 2 1 9 4 7 2 3 9 4 9 2 4 9 4 1 3 6 9 4 3 3 7 9 6 5 3 9 9 9 7 3 0 0 1 2 0 4 1 2 4 E W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 8 7 5 3 2 0 8 1 5 2 3...

Страница 21: ...n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C X X X X X 2 M F I E 3 M F I E 5 M F I E t s u a h x E h t i W r e z i...

Страница 22: ...erant cylinder must be in liquid phase it is suggested that a sight glass be connected between the charging hose and the suction service port This will permit you to adjust the cylinder hand valve so...

Страница 23: ...8 5 6 9 5 7 0 6 7 1 6 7 2 6 2 5 6 7 7 6 0 0 7 3 2 7 8 4 7 7 6 7 8 8 7 9 0 8 9 2 8 0 5 1 5 5 1 0 6 1 5 6 1 0 7 1 5 7 1 0 8 1 5 8 1 0 9 1 5 9 1 0 0 2 5 0 2 0 1 2 5 1 2 0 2 2 5 2 2 0 3 2 5 3 2 0 4 2 5 4...

Отзывы: