ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second  DOM
1.0 minute (60 seconds) DOB = 126 second  DOM
2.0 minute (120 seconds) DOB = 132 second  DOM
3.0 minute (180 seconds) DOB = 138 second  DOM
4.0 minute (240 seconds) DOB = 144 second  DOM
5.0 minute (300 seconds) DOB = 150 second  DOM

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

PRESSURE SERVICE PORTS

Liquid and suction pressure service ports are installed
on all units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

Содержание WE252

Страница 1: ...STRUCTIONS WALL MOUNTED PACKAGED AIR CONDITIONER Models WE252 WE301 WE371 WE421 WE482 WE602 WE701 Manual No 2100 385B Supersedes 2100 385A File Volume III Tab 16 Date 04 25 05 Bard Manufacturing Compa...

Страница 2: ...gerant Service Procedures Considerations 20 Charging 20 Leaks 20 Figures Figure 1 Unit Dimensions 4 Figure 2 Fresh Air Damper Assembly 6 Figure 3 Mounting Instructions 8 Figure 4 Electric Heat Clearan...

Страница 3: ...s Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORM...

Страница 4: ...DAMPER V COMMERCIALVENTILATOR MOTORIZED WITH EXHAUST E ECONOMIZER INTERNAL FULLY MODULATING WITH EXHAUST R ENERGY RECOVERY VENTILATOR MOTORIZED WITH EXHAUST TABLE 1 ELECTRIC HEAT TABLE s l e d o M D...

Страница 5: ...i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t i u c r i C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W Z 0 D 2 5 2 E W 5 0 D 8 0...

Страница 6: ...7 2 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 4 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 2 1 0 5 0 2 1 1 2 4 E W 2 8 4 E W 2 0 6 E W 5 7 0 2 4 2 3...

Страница 7: ...local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the...

Страница 8: ...is shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 Cap...

Страница 9: ...clearance to combustible material However it is highly recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figures...

Страница 10: ...Manual 2100 385B Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 1641 SEE FIGURE 4 FOR FURTHER DETAILS...

Страница 11: ...hat the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causing damage injury or death NOTE A 1 4...

Страница 12: ...L AROUND RETURN DUCT OPENING A I C K THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS ATTACH TO BOTTOM PLATE OF WALL 2 x 6 1 000 CLE...

Страница 13: ...OOR WALL SLEEVE CLOSET WALL LOWERED CEILING SUPPLY AIR GRILLE FINISHED CEILING SURFACE RAIN FLASHING SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN FINISHED CEILING SURFACE S...

Страница 14: ...through the hole in the tab preventing entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is r...

Страница 15: ...Manual 2100 385B Page 13 FIGURE 8 LOW VOLTAGE WIRING DIAGRAM MIS 1373...

Страница 16: ...h monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes pl...

Страница 17: ...DOB set at 2 minutes and DOM is 132 seconds Unit 2 DOB set at 4 minutes and DOM is 144 seconds PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent...

Страница 18: ...mance will occur with a refrigerant charge resulting in a suction line temperature 6 inches from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry b...

Страница 19: ...h g i H d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S w o L y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l i o C t e W y r D l...

Страница 20: ...e d i S w o L e d i S h g i H 8 8 8 3 2 0 9 6 5 2 1 9 4 7 2 3 9 4 9 2 4 9 4 1 3 6 9 4 3 3 7 9 6 5 3 9 9 9 7 3 0 0 1 2 0 4 1 2 4 E W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 8 7 5 3 2 0 8 1 5 2 3...

Страница 21: ...n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C r o t a l i t n e V m o o R l a i c r e m m o C X X X X X 2 M F I E 3 M F I E 5 M F I E t s u a h x E h t i W r e z i...

Страница 22: ...erant cylinder must be in liquid phase it is suggested that a sight glass be connected between the charging hose and the suction service port This will permit you to adjust the cylinder hand valve so...

Страница 23: ...8 5 6 9 5 7 0 6 7 1 6 7 2 6 2 5 6 7 7 6 0 0 7 3 2 7 8 4 7 7 6 7 8 8 7 9 0 8 9 2 8 0 5 1 5 5 1 0 6 1 5 6 1 0 7 1 5 7 1 0 8 1 5 8 1 0 9 1 5 9 1 0 0 2 5 0 2 0 1 2 5 1 2 0 2 2 5 2 2 0 3 2 5 3 2 0 4 2 5 4...

Отзывы: