Manual 2100-689
Page
29 of 32
TABLE 15
Maximum ESP of Operation
Electric Heat Only
Values shown are for units equipped with standard
1" throwaway filter or 1" washable filter.
Derate ESP by .15 for 2" pleated filters.
Model
W18A/L,
W24A/L
W30A/L, W36A/L
Outlet
FRONT
FRONT
Speed
Single
High
Low
-A0Z
-A05
-A08
-A10
-A15
.50
.50
.50
.30
.50
.50
.50
.40
.40
.50
.50
.50
.35
.35
-B0Z
-B06
-B09
-B15
.50
.40
.50
.50
.50
.35
.50
.40
.50
.30
-C0Z
-C06
-C09
-C15
.50
.50
.50
.50
.50
.45
.50
.50
.40
.35
TABLE 16
Electric Heat
Models
240V-1
208V-1
240V-3
208V-3
460V-3
KW
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
Amps
BTUH
5
20.8
17065
18.1
12800
6
14.4
20500
12.5
15360
7.2
20500
8
33.3
27300
28.8
20475
9
21.7
30600
18.7
23030
10.8
30700
10
41.6
34130
36.2
25600
15
62.5
51250
54.0
38400
36.2
51200
31.2
38400
18.0
51200
Содержание WA Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 24: ......
Страница 60: ...Manual 2110 1449A Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 64: ...Manual 2110 1449A Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 66: ...Manual 2110 1449A Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...