Manual 2100-689
Page
27 of 32
TABLE 13
Recommended Airflow
Model
Nominal
Rated
CFM*
Nominal
Rated
ESP*
Recommended
Airflow Range
Factory Speed
Connection
Minimum Airflow:
Balanced Climate Mode
W18A, W18L
600
.10
550 - 725
Rated
380
W24A, W24L
800
.10
700 - 950
500
W30A, W30L
950
.15
900 - 1125
605
W36A, W36L
1150
.15
1000 - 1200
685
* Rated CFM and ESP on factory speed connection.
Setting Unit Airflow
The unit is set from the factory at the rated speed.
Most units have three selectable speed taps that can
be utilized. The rated speed is the lowest speed. The
two higher speed taps can be used for higher duct
static applications so that the unit can maintain the
recommended airflow as shown in Table 13. The higher
speeds can also be used when higher sensible cooling
is desired. To change to the higher speed taps, move
the orange/black wire on the blower speed terminal
block (purple wire on some models) to either MED or
HI. Refer to Table 14 on page 28 for the corresponding
airflow of each tap. In the case of the units with a
purple wire, only one higher speed tap is available
(MED).
NOTE:
Be sure to adjust the system static or
blower speed to maintain airflows above the
minimum recommendations to prevent freeze
up conditions if Balanced Climate mode is
activated.
Do not operate the unit in Balanced Climate mode if
running high static applications as indicated in the
blower performance table. If Balanced Climate mode
is activated as described on page 18, the unit will
run in this mode at all times unless there is a call for
ventilation or electric heat. At that time, the unit will
automatically activate a higher speed tap.
Содержание WA Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 24: ......
Страница 60: ...Manual 2110 1449A Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 64: ...Manual 2110 1449A Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 66: ...Manual 2110 1449A Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...