Wiring – Main Power
Refer to the unit rating plate for wire sizing information
and maximum fuse or circuit breaker size. Each
outdoor unit is marked with a “Minimum Circuit
Ampacity”. This means that the field wiring used must
be sized to carry that amount of current. Depending
on the installed KW of electric heat, there may be two
field power circuits required. If this is the case, the
unit serial plate will so indicate. All models are suitable
only for connection with copper wire. Each unit and/or
wiring diagram will be marked “Use Copper Conductors
Only”. These instructions
must be
adhered to. Refer
to the National Electrical Code (NEC) for complete
current carrying capacity data on the various insulation
grades of wiring material. All wiring must conform to
NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C
copper) for all models including the most commonly used
heater sizes. Also shown are the number of field power
circuits required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or circuit breaker that is to be used with
the equipment. The correct size must be used for
proper circuit protection and also to ensure that there
will be no nuisance tripping due to the momentary high
starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect. To
convert for the locking capability, bend the tab located
in the bottom left-hand corner of the disconnect
opening under the disconnect access panel straight
out. This tab will now line up with the slot in the door.
When shut, a padlock may be placed through the hole
in the tab preventing entry.
See “Start Up” section for important information on
three phase scroll compressor start ups.
See Tables 11 and 12 on pages 25 and 26 for
electrical specifications.
Wiring – Low Voltage
All 230/208V 1 phase and 3 phase equipment have
dual primary voltage transformers. All equipment leaves
the factory wired on 240V tap. For 208V operation,
reconnect from 240V to 208V tap. The acceptable
operating voltage range for the 240 and 208V taps are:
Tap: 240
Range: 253 – 216
Tap: 208
Range: 220 – 187
NOTE:
The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
For low voltage wiring, an 18 gauge copper, color-coded
cable is recommended. See Table 7 on page 14 for
more information.
Low Voltage Connections
These units use a 24-volt AC low voltage circuit. The
RT
terminal is the 24V transformer output, and the
R
terminal is the 24VAC
hot
terminal for the operation
of the equipment. RT and R are connected with a
brass jumper bar which can be removed and RT and R
connected to an external NC (normally closed) contact
such as a fire/smoke detector that will cause immediate
shutdown of the equipment upon activation.
C
terminal is the
24VAC common and is grounded.
G
terminal is the
indoor blower input
.
Y1
terminal is the
1st Stage input for cooling.
Y2
terminal is the
2nd Stage compressor input for cooling
(if equipped with an economizer)
or
disables Balanced
Climate mode if jumper is removed on units without an
economizer (see page 18).
B/W1
terminal is the
1st stage electric heat
.
W2
terminal is the
2nd stage heat
(if equipped).
A
terminal is the
ventilation input
. This terminal
energizes any factory-installed ventilation option and
indoor blower.
D
terminal is the
dehumidification input
. If installed, this
terminal energizes any factory-installed dehumidification
option.
L
terminal is
24 volt alarm active output
.
For units equipped with an alarm relay:
1 terminal
is the
normally closed contact on the relay.
2 terminal
is the
normally open contact on the relay.
3 terminal
is the
common contact on the relay.
See Table 3 for additional low voltage connections.
TABLE 3
Additional Low Voltage Connections (if applicable)
See Table 4 on page 14 for low voltage connections for
DDC control.
Terminal
Unit
Description
9
V Control
Option Only
Discharge Air Sensor,
10K Ohm
10
V Control
Option Only
Discharge Air Sensor,
10K Ohm
11
F, V Control
Options
Filter Switch,
Normally Open Contact
12
F, V Control
Options
Filter Switch,
Normally Open Contact
13
V Control
Option Only
Blower Airflow Switch,
Normally Open Contact
14
V Control
Option Only
Blower Airflow Switch,
Normally Open Contact
15
V Control
Option Only
Compressor Current Sensor,
Normally Open Contact
16
V Control
Option Only
Compressor Current Sensor,
Normally Open Contact
Содержание WA Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 24: ......
Страница 60: ...Manual 2110 1449A Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 64: ...Manual 2110 1449A Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 66: ...Manual 2110 1449A Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...