Manual 2100-689
Page
26 of 32
TABLE 12
Electrical Specifications
−
W**LB Series
MODEL
Rated
Volts
&
Phase
No. Field
Power
Circuits
Single Circuit
Multiple Circuit
Minimum
Circuit
Ampacity
Maximum
External
Fuse or
Ckt. Brkr.
Field
Power
Wire
Size
Ground
Wire
Minimum
Circuit
Ampacity
Maximum
External Fuse or
Ckt. Breaker
Field Power
Wire Size
Ground
Wire Size
Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C Ckt. A Ckt. B Ckt. C
W18LB-A00, A0Z
A05
A08
A10
230/208-1
1
1
1
1
16
30
45
56
20
30
45
60
12
10
8
6
12
10
10
10
W24LB-A00, A0Z
A05
A08
A10
230/208-1
1
1
1
1
21
30
46
56
30
35
50
60
10
8
8
6
10
10
10
10
W24LB-B00, B0Z
B06
230/208-3
1
1
15
22
20
25
12
10
14
10
W24LB-C00, C0Z
C06
460-3
1
1
8
11
10
15
14
14
14
14
W30LB-A00, A0Z
A05
A08
A10
A15
230/208-1
1
1
1
1
1 or 2
23
31
46
57
83
35
35
50
60
90
8
8
8
6
4
10
10
10
10
8
57
26
60
30
6
10
10
10
W30LB-B00, B0Z
B09
B15
230/208-3
1
1
1
17
32
50
20
35
50
12
8
8
12
10
10
W30LB-C00, C0Z
C09
C15
460-3
1
1
1
9
16
24
10
25
30
14
12
10
14
12
10
W36LB-A00, A0Z
A05
A10
A15
230/208-1
1
1
1
1 or 2
27
32
58
84
35
35
60
90
8
8
6
4
10
10
10
8
58
26
60
30
6
10
10
10
W36LB-B00, B0Z
B09
B15
230/208-3
1
1
1
20
33
51
25
35
60
10
8
6
10
10
10
W36LB-C00, C0Z
C09
C15
460-3
1
1
1
10
15
24
10
15
25
14
14
10
14
14
10
Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing.
CAUTION:
When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention
to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying conductors are in a
raceway.
IMPORTANT:
While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Содержание WA Series
Страница 2: ......
Страница 12: ......
Страница 18: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...
Страница 19: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...
Страница 24: ......
Страница 60: ...Manual 2110 1449A Page 4 of 12 FUNCTIONAL COMPONENTS 10 11 2 3 1 4 5 6 9 8 7 12 13 14 15 SEXP 949...
Страница 64: ...Manual 2110 1449A Page 8 of 12 CONTROL PANEL 14 13 6 15 18 16 4 11 7 10 9 1 3 12 17 5 2 SEXP 908...
Страница 66: ...Manual 2110 1449A Page 10 of 12 CONTROL PANEL 7 17 11 12 16 3 10 8 13 15 14 9 4 5 6 18 1 2 SEXP 948...