background image

Manual 2100-509E 

Page 

14 of 17

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil 
with a dishwasher detergent.

SERVICE HINTS

  1.  Caution owner to maintain clean air filters at all 

times.  Also not to needlessly close off supply and 

return air registers.  This reduces airflow through the 

system which shortens equipment service life as well 
as increasing operation costs.

  2.  The unit is equipped with a high pressure cut out 

switch.

  3.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

  4.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

HIGH & LOW PRESSURE SWITCH

The W12A

à

 models are supplied with a remote reset 

high and low pressure switch.  If tripped, this pressure 
switch may be reset by turning the thermostat off then 
back on again.

SEQUENCE OF OPERATION

HEATING

 – Circuit R-Y makes at thermostat pulling 

in compressor contactor, starting the compressor 
and outdoor motor.  The G (indoor motor) circuit 
is automatically completed on any call for cooling 
operation or can be energized by manual fan switch 
on subbase for constant air circulation.  On a call for 
heating, circuit R-W1 make at the thermostat pulling in 
heat contact for the strip heat and blower operation.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the 
models covered by this manual.  The compressor control 
is an anti-short cycle/lockout timer with high and low 
pressure switch monitoring and alarm relay output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to 
the unit the 

delay on make

 period begins, which will be 

2 minutes plus 10% of the 

delay on break

 setting.  When 

the delay on make is complete and the high pressure 
switch (and low pressure switch if employed) is closed, 
the compressor contactor is energized.  Upon shutdown 
the delay on break time starts and prevents restart until 
the delay on break and delay on make periods have 
expired.

During routine operation of the unit with no power 
interruptions the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes 

and

 the delay on 

break time has expired.  If the high pressure switch opens 
again in this same operating cycle the unit will go into 
manual lockout condition and the alarm relay circuit 
will energize.  Recycling the wall thermostat resets the 
manual lockout.

Low Pressure Switch, Bypass  and Lockout 

Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize 
and go into a soft lockout.  Regardless the state of the 
low pressure switch, the contactor will reenergize after 
the delay on make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
that 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is powered 
whenever compressor is locked out due to HPC or LPC 
sequences as described.

NOTE:  Both high and low pressure switch controls 

are inherently automatic reset devices.  The 
high pressure switch and low pressure switch 

cut out and cut in settings are fixed by specific 

air conditioner or heat pump unit model.  The 
lockout features, both soft and manual, are a 
function of the Compressor Control Module.

Содержание W12A2-A

Страница 1: ...TED PACKAGE AIR CONDITIONERS Model W12A2 A W12A1 K INSTALLATION INSTRUCTIONS Manual 2100 509E Supersedes 2100 509D File Volume III Tab 16 Date 08 20 12 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...4 Adjustments 15 Pressure Service Ports 15 Troubleshooting Fan Blade Setting Dimension 16 Refrigerant Charge 16 Pressure Table 17 Optional Field Installed Accessories 17 Figures Figure 1 Unit Dimensio...

Страница 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Страница 4: ...MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VOLTS PHASE A 230 208 60 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW VENTILATION OPTIONS X Barometric Fresh...

Страница 5: ...osition is Blow Thru Condenser Airflow Flanges Built In Side Wall Mounting Shipping Location Top Rain Flashing field convertible position Optional Electrical Position of return air flanges are interch...

Страница 6: ...tandards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be install...

Страница 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Страница 8: ...cations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wi...

Страница 9: ...Manual 2100 509E Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 509E Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 509E Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...ta lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits required for the various models with heaters The...

Страница 13: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 14: ...on make is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance...

Страница 17: ...6 379 138 405 141 432 142 460 143 490 80 deg DB 67 deg WB Low Side High Side 128 298 133 318 138 340 142 364 143 387 148 415 151 443 152 472 153 503 85 deg DB 72 deg WB Low Side High Side 132 308 138...

Отзывы: