WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information 
and maximum fuse or “HACR” type circuit breaker size.  
Each outdoor unit is marked with a “Minimum Circuit 

Ampacity”.  This means that the field wiring used must 

be sized to carry that amount of current.  Depending 
on the installed  KW of electric heat, there may be two 

field power circuits required.  If this is the case, the unit 

serial plate will so indicate.  All models are suitable 
only for connection with copper wire.  Each unit and/or 
wiring diagram will be marked “Use Copper Conductors 
Only”.  These instructions 

must be

 adhered to.  Refer to 

the National Electrical Code (NEC) for complete current 
carrying capacity data on the various insulation grades of 
wiring material.  All wiring must conform to NEC and all 
local codes.

The electrical data lists fuse and wire sizes (75°C copper) 
for all models, including the most commonly used heater 

sizes.  Also shown are the number of field power circuits 

required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay 
Fuse” of “HACR” type circuit breaker that is to be used 
with the equipment.  The correct size must be used for 
proper circuit protection and also to assure that there 
will be no nuisance tripping due to the momentary high 
starting current of the compressor motor.

For wiring size and connections, refer to Wiring Manual 
2100-507.

NOTE:   The voltage should be measured at the field 

power connection point in the unit and while the 
unit is operating at full load (maximum amperage 
operating condition).

WIRING – LOW VOLTAGE WIRING

230/208, 1 phase equipment use dual primary voltage 
transformers.  All equipment leaves the factory wired on 
240V tap.  For 208V operation, reconnect from 240V to 
208V tap.  The acceptable operating voltage range for the 
240 and 208V taps are:

Tap

Range

240

253 - 216

208

220 - 187

Содержание W12A2-A

Страница 1: ...TED PACKAGE AIR CONDITIONERS Model W12A2 A W12A1 K INSTALLATION INSTRUCTIONS Manual 2100 509E Supersedes 2100 509D File Volume III Tab 16 Date 08 20 12 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...4 Adjustments 15 Pressure Service Ports 15 Troubleshooting Fan Blade Setting Dimension 16 Refrigerant Charge 16 Pressure Table 17 Optional Field Installed Accessories 17 Figures Figure 1 Unit Dimensio...

Страница 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Страница 4: ...MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VOLTS PHASE A 230 208 60 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW VENTILATION OPTIONS X Barometric Fresh...

Страница 5: ...osition is Blow Thru Condenser Airflow Flanges Built In Side Wall Mounting Shipping Location Top Rain Flashing field convertible position Optional Electrical Position of return air flanges are interch...

Страница 6: ...tandards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be install...

Страница 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Страница 8: ...cations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wi...

Страница 9: ...Manual 2100 509E Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 509E Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 509E Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...ta lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits required for the various models with heaters The...

Страница 13: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 14: ...on make is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance...

Страница 17: ...6 379 138 405 141 432 142 460 143 490 80 deg DB 67 deg WB Low Side High Side 128 298 133 318 138 340 142 364 143 387 148 415 151 443 152 472 153 503 85 deg DB 72 deg WB Low Side High Side 132 308 138...

Отзывы: