background image

Manual 2100-509E 

Page 

13 of 17

START UP

THESE UNITS REQUIRE R-410A 
REFRIGERANT AND POLYOL 
ESTER OIL.

GENERAL:

1.  Use separate service equipment to avoid cross    
 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.

3.  Use manifold gauges rated for R-410A (800 psi/250  
 

psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.

5.  R-410A is nearly azeotropic - similar to R-22 and  
 

R-12.  Although nearly azeotropic, charge with    

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   
 

R-22, and systems designed for R-22 cannot  

 

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  
 

but must be reclaimed due to its global warming   

 potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly absorb  
 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep  

 

 

vacuum will not separate moisture from the oil.

11.  Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug   
 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing 
recommends reclaiming, evacuating (see criteria above), 
and charging to the nameplate charge.  If done correctly, 
topping off the system charge can be done without 
problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound or 
single component refrigerant).  The remaining refrigerant 
charge, in the system, may be used after leaks have 
occurred and then “top-off” the charge by utilizing the 
pressure charts on the inner control panel cover as a 
guideline.

REMEMBER:  

When adding R-410A refrigerant, it must 

come out of the charging cylinder/tank as a liquid to 
avoid any fractionation, and to insure optimal system 
performance.  Refer to instructions for the cylinder that 
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses, Polyol Ester oils can  
 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the  

 

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the  

 

 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if   

 exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly at  

 

warmer temperatures.  Once a cylinder or line is full  

 

of liquid, any further rise in temperature will  

 

 

cause it to burst.

        WARNING

Failure to conform to these practices 
could lead to damage, injury or death.

Содержание W12A2-A

Страница 1: ...TED PACKAGE AIR CONDITIONERS Model W12A2 A W12A1 K INSTALLATION INSTRUCTIONS Manual 2100 509E Supersedes 2100 509D File Volume III Tab 16 Date 08 20 12 Bard Manufacturing Company Inc Bryan Ohio 43506...

Страница 2: ...4 Adjustments 15 Pressure Service Ports 15 Troubleshooting Fan Blade Setting Dimension 16 Refrigerant Charge 16 Pressure Table 17 Optional Field Installed Accessories 17 Figures Figure 1 Unit Dimensio...

Страница 3: ...esign for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hamps...

Страница 4: ...MODEL NUMBER REVISIONS CONTROL MODULES E Low Ambient Control J Telecommunication VOLTS PHASE A 230 208 60 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW VENTILATION OPTIONS X Barometric Fresh...

Страница 5: ...osition is Blow Thru Condenser Airflow Flanges Built In Side Wall Mounting Shipping Location Top Rain Flashing field convertible position Optional Electrical Position of return air flanges are interch...

Страница 6: ...tandards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be install...

Страница 7: ...service door A 2 inch pleated filter is also available as an optional accessory The internal filter brackets are adjustable to accommodate the 2 inch filter by bending the metal tabs holding the 1 in...

Страница 8: ...cations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wi...

Страница 9: ...Manual 2100 509E Page 9 of 17 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 509E Page 10 of 17 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 509E Page 11 of 17 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...ta lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits required for the various models with heaters The...

Страница 13: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 14: ...on make is complete and the high pressure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart...

Страница 15: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 16: ...the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance...

Страница 17: ...6 379 138 405 141 432 142 460 143 490 80 deg DB 67 deg WB Low Side High Side 128 298 133 318 138 340 142 364 143 387 148 415 151 443 152 472 153 503 85 deg DB 72 deg WB Low Side High Side 132 308 138...

Отзывы: