HANDLING UNIT AFTER REMOVAL
FROM SKID

The unit will have to be turned sideways and removed
from the skid to fit through a 36" doorway.  If the door
height allows, the unit can be slid sideways through the
door.

If the unit can not be slid through the door, then the unit
will have to be put on a cart and tipped down to roll
through the door.  It is recommended that an appliance
cart by used with a strap to hold the unit on the cart.
The wheels of the unit 

must be locked

.  If the wheels

were allowed to roll, the unit could roll off the cart.  

The

unit should always be carted from the left side

.  This is

the side where the compressor is located.  See Figure 4.

The blade of the appliance cart should be slid under the
wheels of the unit.  The strap of the appliance cart
should be placed around the unit and strapped tightly.
Help will be required to tip the unit back onto the cart.
The unit can be leaned far enough back to be rolled
through the door.  Be careful when setting the unit back
up to keep from damaging the unit.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The unit is designed for use with or without duct work.
For use without duct work, Plenum Box QPB42 is
recommended.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Start
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat gain or loss calculation made according to
methods of Air Conditioning Contractors of America
(ACCA).  The air duct should be installed in accordance
with the Standards of the National Fire Protection
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

MINIMUM INSTALLATION HEIGHT

The minimum installation height of the unit with a Free
Blow Plenum is 8 ft. 6 in.   This provides enough
clearance for the plenum to be removed.  See Figure 5.

The minimum installation height for ducted applications
is 8 ft. 4½ in.   This provides enough clearance to install
the duct work.  See Figure 6.

FIGURE  4

UNIT ON APPLIANCE CART

        WARNING

Exercise extreme caution when pushing the
unit on the rollers.  Handle and push from the
lower 1/3 of the unit.  Insure that debris is not
on the floor where the unit is to be moved on
the rollers.  Failure to do so could result in the
unit tipping over and causing bodily injury and/
or damage to the unit.

QT

EC

 UNIT

(Right Side)

APPLIANCE

CART

COMPRESSOR

STRAP

Содержание QTEC Q24A1D Series

Страница 1: ...g Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 523 Supersedes NEW File Vol II Tab 14 Date 08 20 09 Models Q24A1D Q30A1D Q36A1D Q42A1D Q48A1D Q60A1D QTEC SERIES PACK...

Страница 2: ...3 QTEC General Information QTEC Model Nomenclature 4 Shipping Damage 8 Unit Removal From Skid 8 Handling Unit After Removal From Skid 9 General 9 Minimum Installation Height 9 Duct Work 11 Filters 11...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commercial Ven...

Страница 5: ...1 V 0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0...

Страница 6: ...2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 2 4 Q 5 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 5 3 5 3 8 5 3 8 0 5 0 5 0 6 0 9 8 8 6 4 0 1 0 1 8 8 8 5 5 2 0 6 5 2 6 0 1 0 1 0 1 Z 0...

Страница 7: ...Manual 2100 523 Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...ed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the...

Страница 9: ...ate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to...

Страница 10: ...Manual 2100 523 Page 10 of 41 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...ustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be...

Страница 12: ...m the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be insta...

Страница 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Страница 14: ...Manual 2100 523 Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 523 Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...k both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessar...

Страница 20: ...breaker panel See Figure 15 WIRING LOW VOLTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation re...

Страница 21: ...R terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of...

Страница 22: ...o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o...

Страница 23: ...5 4 3 2 1 Plug 4 8 R C Rc 12 11 10 9 C R W2 E C R W2 W1 G A Y1 4 3 5 6 Y1 G F 1 2 3 Blue Yellow Brown White Orange Yellow Blue Brown 2 Red White Red White H200 Thermostat Black White Humidistat 8403...

Страница 24: ...8 4102 073 4 R Plug 2 C 1 Yellow 2 12 Purple White Brown Temp and Humidity Controller Pink Y1 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000A or...

Страница 25: ...Blue 9 D YO 10 Orange A 7 PART 8403 060 5 Black White G 3 Brown White 6 8 4102 074 11 R Y1 Plug 2 C 1 Yellow 4 2 12 Brown W1 E Temp and Humidity Controller W2 Purple White FIGURE 19 UNIT MOUNTED THERM...

Страница 26: ...nge 5 Part 8403 060 6 Black White 24VAC 10 D Y0 9 Blue Red White Controller Brown White A 7 Purple White Brown 2 Green 4 Out Yellow Black Brown Red Red White Orange CO2 Controller Part 8403 056 Temp a...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will...

Страница 29: ...ockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer th...

Страница 30: ...e mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be...

Страница 31: ...he unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist...

Страница 32: ...Manual 2100 523 Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 523 Page 33 of 41 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...the thermostat on units with E climate control option It is energized by applying power to the F terminal of the low voltage strip on units with G climate control options On climate option I it is ene...

Страница 35: ...Manual 2100 523 Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...

Страница 36: ...Manual 2100 523 Page 36 of 41 FIGURE 25 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM...

Страница 37: ...o c e s 0 1 n i h t i w d n a l a n i m r e t p u d e e p s C C C n e e w t e b r a e p p a d l u o h s r e w o p 0 1 r e t f a r e p m u j p u d e e p s e v o m e R s d n o c e s e v i t c e f e d r...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Страница 40: ...shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 29 FAN BLADE SETTING TABLE 6 FAN BLADE DIMENSIONS L E D O M A N O I...

Страница 41: ...0 0 5 1 4 0 0 7 5 2 0 0 0 0 4 0 0 3 5 2 0 0 5 8 3 0 0 6 4 2 0 0 0 7 3 0 0 0 4 2 0 0 4 5 3 0 0 3 3 2 0 0 9 3 3 0 0 5 2 2 0 0 3 2 3 0 0 8 1 2 D 1 A 2 4 Q 5 7 2 6 g n i l o o C l a t o T g n i l o o C e...

Отзывы: