background image

Manual 2100-523
Page

30 of 41

6. Some service requires the need to remove the unit

from the wall including replacement of the indoor
coil and/or the outdoor coil.  Also servicing the
outdoor fan motor or fan blade will require
removing the unit from the wall if the unit is
installed at a height that is not easily accessible
from the outside of the building.

In order to remove the unit from the wall the
following procedure must be used:

a. Turn off power to the unit at the remote

location.  Some units may have more than one
power supply.

b. Disconnect field wiring at unit terminal block

and remove from unit.

c. Disconnect condensate drain.

d. Remove the lower skirting around the unit.

e. Remove wall mounting brackets from wall on

each side of the unit.

f. If unit is attached to duct work, remove upper

cabinet extension by removing the top center
screw only from the cabinet side panel.

g. Remove screws that attach the duct work to

the unit flanges.

This unit is equipped with four rollers
mounted to the base.  For ease of pulling unit
out from the wall, you may want to remove
the bottom service door which requires
removal of the return air panel, and grip the
front flange of the base pan then pull straight
out.

7. Annual maintenance is required to make sure that

all of the systems are functioning properly.

a. Check to make sure that the drains are not

obstructed in any way.

b. Remove any debris in the condenser section of

the unit.

c. Inspect and clean mist eliminator as described

below.

d. Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve.  The
mist eliminator is constructed of an aluminum frame
and mesh.  The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall.  This requires that the ventilation package must
be removed.

It is recommended that the mist eliminator be inspected
annually and serviced as required.  The mist eliminator
can be inspected from the outside of the building by
looking through the outdoor grille.  The mist eliminator
can be serviced from the outside by using a vacuum
cleaner.  The outdoor grille must be removed.  Use the
vacuum to remove dirt and debris from the surface of the
mist eliminator.  If additional cleaning is required, the
mist eliminator will have to be removed from the sleeve.

The ventilation package will have to be removed to gain
access to the mist eliminator.  If the blank off plate
option is used, it is not necessary to service the mist
eliminator.  The steps necessary to remove each of the
vent options are listed on the following pages.

The mist eliminator can be cleaned by washing with
soap and water.  The excess water should be shaken off
the mist eliminator before it is reinstalled.

VENT OPTIONS

BAROMETRIC FRESH AIR DAMPER  (Standard)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
fresh air damper assembly can be seen on the back of the
unit.  See Figure 21.

1. The fresh air damper is attached to the back of the

unit with one screw on either side of the
assembly.  Both of the screws must be removed.

2. Once the mounting screws are removed, tilt the

assembly down and lift it out.

The mist eliminator can be seen through the opening.
The mist eliminator must be raised up and the bottom
can be pulled toward the front of the unit.

ECONOMIZER OR COMMERCIAL ROOM
VENTILATOR  (Option)

Before starting, make sure the power has been turned
off.  The return air grille panel must be removed.  The
economizer (EIFM) or commercial room ventilator
(CRV) can be seen after the panel has been removed.
The CRV or EIFM must be removed to gain access to
the mist eliminator.

1. The two mounting screws in the front of the

EIFM or CRV must be removed.

2. The power connectors for the CRV (located on

the right side of the unit) must be disconnected.
Squeeze the tabs on the sides of the connector and
pull straight out.  Unplug both of the connectors.

3. Slide the EIFM or CRV straight out of the unit.

Содержание QTEC Q24A1D Series

Страница 1: ...g Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 523 Supersedes NEW File Vol II Tab 14 Date 08 20 09 Models Q24A1D Q30A1D Q36A1D Q42A1D Q48A1D Q60A1D QTEC SERIES PACK...

Страница 2: ...3 QTEC General Information QTEC Model Nomenclature 4 Shipping Damage 8 Unit Removal From Skid 8 Handling Unit After Removal From Skid 9 General 9 Minimum Installation Height 9 Duct Work 11 Filters 11...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commercial Ven...

Страница 5: ...1 V 0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0...

Страница 6: ...2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 2 4 Q 5 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 5 3 5 3 8 5 3 8 0 5 0 5 0 6 0 9 8 8 6 4 0 1 0 1 8 8 8 5 5 2 0 6 5 2 6 0 1 0 1 0 1 Z 0...

Страница 7: ...Manual 2100 523 Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...ed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the...

Страница 9: ...ate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to...

Страница 10: ...Manual 2100 523 Page 10 of 41 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...ustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be...

Страница 12: ...m the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be insta...

Страница 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Страница 14: ...Manual 2100 523 Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 523 Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...k both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessar...

Страница 20: ...breaker panel See Figure 15 WIRING LOW VOLTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation re...

Страница 21: ...R terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of...

Страница 22: ...o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o...

Страница 23: ...5 4 3 2 1 Plug 4 8 R C Rc 12 11 10 9 C R W2 E C R W2 W1 G A Y1 4 3 5 6 Y1 G F 1 2 3 Blue Yellow Brown White Orange Yellow Blue Brown 2 Red White Red White H200 Thermostat Black White Humidistat 8403...

Страница 24: ...8 4102 073 4 R Plug 2 C 1 Yellow 2 12 Purple White Brown Temp and Humidity Controller Pink Y1 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000A or...

Страница 25: ...Blue 9 D YO 10 Orange A 7 PART 8403 060 5 Black White G 3 Brown White 6 8 4102 074 11 R Y1 Plug 2 C 1 Yellow 4 2 12 Brown W1 E Temp and Humidity Controller W2 Purple White FIGURE 19 UNIT MOUNTED THERM...

Страница 26: ...nge 5 Part 8403 060 6 Black White 24VAC 10 D Y0 9 Blue Red White Controller Brown White A 7 Purple White Brown 2 Green 4 Out Yellow Black Brown Red Red White Orange CO2 Controller Part 8403 056 Temp a...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will...

Страница 29: ...ockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer th...

Страница 30: ...e mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be...

Страница 31: ...he unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist...

Страница 32: ...Manual 2100 523 Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 523 Page 33 of 41 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...the thermostat on units with E climate control option It is energized by applying power to the F terminal of the low voltage strip on units with G climate control options On climate option I it is ene...

Страница 35: ...Manual 2100 523 Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...

Страница 36: ...Manual 2100 523 Page 36 of 41 FIGURE 25 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM...

Страница 37: ...o c e s 0 1 n i h t i w d n a l a n i m r e t p u d e e p s C C C n e e w t e b r a e p p a d l u o h s r e w o p 0 1 r e t f a r e p m u j p u d e e p s e v o m e R s d n o c e s e v i t c e f e d r...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Страница 40: ...shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 29 FAN BLADE SETTING TABLE 6 FAN BLADE DIMENSIONS L E D O M A N O I...

Страница 41: ...0 0 5 1 4 0 0 7 5 2 0 0 0 0 4 0 0 3 5 2 0 0 5 8 3 0 0 6 4 2 0 0 0 7 3 0 0 0 4 2 0 0 4 5 3 0 0 3 3 2 0 0 9 3 3 0 0 5 2 2 0 0 3 2 3 0 0 8 1 2 D 1 A 2 4 Q 5 7 2 6 g n i l o o C l a t o T g n i l o o C e...

Отзывы: