background image

Manual 2100-523
Page

20 of 41

FIGURE  15

COMPONENT LOCATION

TABLE  3

OPERATING VOLTAGE RANGE

P

A

T

E

G

N

A

R

V

0

4

2

6

1

2

3

5

2

V

8

0

2

7

8

1

0

2

2

WIRING  –  MAIN POWER

Refer to the unit rating plate and/or Table 2 for wire
sizing information and maximum fuse or “HACR Type”
circuit breaker size.  Each unit is marked with a
“Minimum Circuit Ampacity”.  This means that the field
wiring used must be sized to carry that amount of
current.  Depending on the installed KW of electric heat,
there may be two field power circuits required.  If this is
the case, the unit serial plate will so indicate.  All
models are suitable only for connection with copper
wire.  Each unit and/or wiring diagram will be marked
“Use Copper Conductors Only”.  These instructions

MUST BE

 adhered to.  Refer to the National Electrical

Code (NEC) for complete current carrying capacity data
on the various insulation grades of wiring material.  All
wiring must conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR Type” circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.

See “Start Up” section for information on three phase
scroll compressor start-ups.

The field wiring connections are located behind the top
and hinged panel in the circuit breaker panel.  See
Figure 15.

WIRING  –  LOW VOLTAGE WIRING

230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS.

All Equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 3.

DEHUMIDIFICATION
CONTROL
(OPTIONAL)

UNIT
MOUNTED
THERMOSTAT
LOCATION

ELECTRIC
HEATERS

CIRCUIT
BREAKER
PANEL &
CONTROLS

INDOOR
BLOWER

REMOTE
THERMOSTAT
TERMINAL
BLOCK

SIDE FIELD
WIRE
ENTRANCE

LOWER
CONTROL
PANEL

The standard Climate Control 

Option X

 is a remote

thermostat connection terminal block.  See Figure 17 for
wiring diagram.  Compatible thermostats are listed in
Table 4.

The Climate Control 

Option G

 is an electronic, non-

programmable manual or auto changeover thermostat
with humidistat. The subbase of the thermostat is
factory wired to the front panel of the unit.  See Figure
18 for wiring diagram.  Compatible for use with Bard
CS2000A* Controller and Energy Recovery Ventilator.

The Climate Control 

Option E

 is an electronic,

programmable thermostat with humidistat.  The subbase
of the thermostat is factory wired to the front panel of
the unit.  See Figure 19 for wiring diagram.  Compatible
for use with Energy Recovery Ventilator.

The Climate Control 

Option I

 is an electronic,

programmable thermostat with humidistat and a CO

2

controller.  The subbase of the thermostat and CO

2

controller are factory wired to the front panel of the unit.
See Figure 20 for wiring diagram.

NOTE: On option X or G the CS2000A* (or other field

provided means to control ventilation) must be
used if any of the motorized ventilation options
are installed.

NOTE: Thermostats are shipped in the bottom of the

unit and must be mounted to the factory
mounted subbase at time of installation.

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

Содержание QTEC Q24A1D Series

Страница 1: ...g Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 523 Supersedes NEW File Vol II Tab 14 Date 08 20 09 Models Q24A1D Q30A1D Q36A1D Q42A1D Q48A1D Q60A1D QTEC SERIES PACK...

Страница 2: ...3 QTEC General Information QTEC Model Nomenclature 4 Shipping Damage 8 Unit Removal From Skid 8 Handling Unit After Removal From Skid 9 General 9 Minimum Installation Height 9 Duct Work 11 Filters 11...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60 5 Ton KW 0Z 0KW 05 5KW 06 6KW 09 9KW 10 10KW 12 12KW 15 15KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate V Commercial Ven...

Страница 5: ...1 V 0 4 2 1 V 8 0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0...

Страница 6: ...2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 2 4 Q 5 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 5 3 5 3 8 5 3 8 0 5 0 5 0 6 0 9 8 8 6 4 0 1 0 1 8 8 8 5 5 2 0 6 5 2 6 0 1 0 1 0 1 Z 0...

Страница 7: ...Manual 2100 523 Page 7 of 41 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...ed and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the...

Страница 9: ...ate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to...

Страница 10: ...Manual 2100 523 Page 10 of 41 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...ustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be...

Страница 12: ...m the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be insta...

Страница 13: ...REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 O...

Страница 14: ...Manual 2100 523 Page 14 of 41 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 15: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 16: ...Manual 2100 523 Page 16 of 41 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 17: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 18: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Страница 19: ...k both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessar...

Страница 20: ...breaker panel See Figure 15 WIRING LOW VOLTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All Equipment leaves the factory wired on 240V tap For 208V operation re...

Страница 21: ...R terminal is the hot terminal and the C terminal is grounded G terminal or pin 6 of P2 are the fan inputs If the climate control option is abandoned and connections are made directly to P2 pin 6 of...

Страница 22: ...o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o...

Страница 23: ...5 4 3 2 1 Plug 4 8 R C Rc 12 11 10 9 C R W2 E C R W2 W1 G A Y1 4 3 5 6 Y1 G F 1 2 3 Blue Yellow Brown White Orange Yellow Blue Brown 2 Red White Red White H200 Thermostat Black White Humidistat 8403...

Страница 24: ...8 4102 073 4 R Plug 2 C 1 Yellow 2 12 Purple White Brown Temp and Humidity Controller Pink Y1 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM G THERMOSTAT OPTION NOTE On option X or G the CS2000A or...

Страница 25: ...Blue 9 D YO 10 Orange A 7 PART 8403 060 5 Black White G 3 Brown White 6 8 4102 074 11 R Y1 Plug 2 C 1 Yellow 4 2 12 Brown W1 E Temp and Humidity Controller W2 Purple White FIGURE 19 UNIT MOUNTED THERM...

Страница 26: ...nge 5 Part 8403 060 6 Black White 24VAC 10 D Y0 9 Blue Red White Controller Brown White A 7 Purple White Brown 2 Green 4 Out Yellow Black Brown Red Red White Orange CO2 Controller Part 8403 056 Temp a...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will...

Страница 29: ...ockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer th...

Страница 30: ...e mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be...

Страница 31: ...he unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist...

Страница 32: ...Manual 2100 523 Page 32 of 41 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 33: ...Manual 2100 523 Page 33 of 41 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 34: ...the thermostat on units with E climate control option It is energized by applying power to the F terminal of the low voltage strip on units with G climate control options On climate option I it is ene...

Страница 35: ...Manual 2100 523 Page 35 of 41 FIGURE 24 AIR CONDITIONING MODE CIRCUIT DIAGRAM...

Страница 36: ...Manual 2100 523 Page 36 of 41 FIGURE 25 DEHUMIDIFICATIONMODE CIRCUIT DIAGRAM...

Страница 37: ...o c e s 0 1 n i h t i w d n a l a n i m r e t p u d e e p s C C C n e e w t e b r a e p p a d l u o h s r e w o p 0 1 r e t f a r e p m u j p u d e e p s e v o m e R s d n o c e s e v i t c e f e d r...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Страница 40: ...shown in Table 7 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate FIGURE 29 FAN BLADE SETTING TABLE 6 FAN BLADE DIMENSIONS L E D O M A N O I...

Страница 41: ...0 0 5 1 4 0 0 7 5 2 0 0 0 0 4 0 0 3 5 2 0 0 5 8 3 0 0 6 4 2 0 0 0 7 3 0 0 0 4 2 0 0 4 5 3 0 0 3 3 2 0 0 9 3 3 0 0 5 2 2 0 0 3 2 3 0 0 8 1 2 D 1 A 2 4 Q 5 7 2 6 g n i l o o C l a t o T g n i l o o C e...

Отзывы: