Manual 2100-746D
Page
54 of 59
FIGURE 30
T**H Series Unit with No CHCRV-*
MC-5300: SYSTEM 1-3 OR
MC-5600: SYSTEM 1-6
HIGH
TEMP 2
NOTE: NOT ALL TERMINALS
REPRESENTED FOR ALARM
BOARD 1
LOCK OUT 1
LOCK OUT 3 LOCK OUT 2
POWER
LOSS 3
POWER
LOSS 2
LOW
TEMP
HIGH
TEMP 1
POWER
LOSS 1
VENT
FILTER
THEFT
LOCK OUT 4
POWER
LOSS 6
POWER
LOSS 5
POWER
LOSS 4
LOCK OUT 5
LOCK OUT 6
ALARM BOARD 1
MC5300-BC AND MC5600-BC
ALARM BOARD 2
MC5600-BC ONLY
Notes:
1.) Stage 2 Heat Input (Electric Heat), Filter Switch, Ventilation, and Mechanical Dehumidification are optional features. Refer to model
nomenclature to verify optional equipment installed in unit.
2.) Ventilation wire between the unit low voltage terminal "O1" and the "A" terminal on the MC board allows for energization of any factory
installed ventilation or economizer option (Exception:
CHCRV-* vent options not compatible with MC5000 controller). Use VENT Contacts of
Primary Board to activate ventilation using CO2 sensor or other peripheral device. For constant ventilation, jumper VENT contacts.
3.) Optional remote sensors #1 and #2 are temperature resistance 10k type 2. Remote sensor #2 can be used as an outdoor or indoor sensor.
4.) Emergency Off Contacts used in MC series controller to shut down all units. Emergency shutdown factory jumper may be removed to field
install a normally closed relay at each individual unit.
5.) All MC controllers will have a primary control board with connections for units 1 to 3. MC5600 controllers only will have an additional
secondary control board with connections for units 4 to 6.
6.) MC5300-BC and MC5600-BC controllers have additional alarm board(s) with dry contacts for wired alarms.
7.) Compressor Lockout Output will not trigger the alarm on the display of the MC5000 controller (T**H units).
PRIMARY BOARD
REM 2
REM 1
EMERG
OFF
GEN
VENT
THEFT
Emergency
Shutdown
Factory Jumper
R
C W1 W2 EC Y1 Y2 G O/B A
D
H
FILTER DUST LOR AUX IN EIN
NO C NC
AUX OUT
O1
G
Y1
Y
W2
C
R
RT
MC SERIES CONTROL BOARDS
MC5300 PRIMARY BOARD ONLY.
MC5600 PRIMARY AND SECONDARY BOARD.
T**H SERIES UNIT
24VAC
Common
2nd Stage Heat Input
1st Stage Input
Indoor Fan
LOW VOLTAGE
TERMINAL STRIP
24VAC
AVAILABLE NOC REMOTE MONITORING DRY CONTACTS. MC5300-BC AND MC5600-BC ONLY.
T**H SERIES UNITS
WITH NO CHCRV-*
MIS-4212
Reversing Valve
Vent
Contacts
(opt.)
Theft
Contacts
(opt.)
Optional Remote
Sensors #1 and #2
Emergency
Off Contacts
Generator
Contacts
W3
W1
B
Factory
Installed
Jumper
Ventilation
L
Factory
Installed
Jumper
M. Dehumidification