TABLE 1
MC5000 Series Set Points/Defaults/User Settings Record
Set Point (SP) or Item Name
Current Range
Default
User Settings
Cooling Set Point
4° above Heating SP to 90°F
77
Heating Set Point
32°F to 4° below Cooling SP
60
Comfort Mode Cooling Set Point
4° above Comfort Heating SP to 90°F
72
Comfort Mode Heating Set Point
32°F to 4° below Comfort Cooling SP
68
Dehumidification Level
10-100% RH +10% above Humidification Level
80%
Humidification Level
0-90% RH +10% under Dehumidification Level
45%
Cooling Interstage Differential
.5 – 5
1
Cooling Off Differential
.5 – 5
2
Heating Interstage Differential
.5 – 5
1
Heating Off Differential
.5 – 5
2
Dehumidification Interstage Differential
0 – 5
5
Dehumidification Off Differential
1 – 15
10
Humidification Interstage Differential
0 – 5
5
Humidification Off Differential
1 – 15
10
High Humidity Alarm Set Point
65 – 95
85
Low Humidity Alarm
0 – 80
25
Low Temperature Alarm Level
65 – 28
40
High Temperature Alarm Level 1
70 – 120
80
High Temperature Alarm Level 2
70 – 120
90
Heat Pump Lockout Range
None, 5 – 50
None
Equipment Setup Items
Number of HVAC Units
1 – 6
1
Number of Compressor Stages
1 or 2
1
Heat Pump Enabled
Yes or No
No
O/B Configuration
Energize in Heating or Energize in Cooling
Heating
Number of Electric Heat Stages
1 or 2
1
Max Units in Generator Mode
1 – 6
6
Number of Dehumidification Units
0 – 6
0
Dehumidification Type
Mechanical, Synchronized or None
None
Dehumidification Count
0 – 6
0
Humidification
Yes or No
No
Economizer Present
Yes or No
No/Hidden
Dust Sensor Type
Dry Contact, Analog or None
Dry Contact/
Hidden