Set Point (SP) or Item Name
Current Range
Default
User Settings
Auxiliary Out Configuration
Emergency Off, Gen Run, High Humidity
Alarm, Dust Alarm or Dehum Active
Emergency
Off
System Setup Items
Languages
English, French or Spanish
English
Password Protection
Yes or No
No
Staging Logic
Alternating or Non-Alternating
Alternating
Lead/Lag Changeover Time
0 – 30 Days 0 = Disable
7 Days
Continuous Blower Logic
Lead, All, None, Pre-Purge or Custom
None
Pre-Purge
1 – 5 Minutes
1 Minute
Degrees
Fahrenheit or Celsius
Fahrenheit
Temperature Sensor Logic
Average, Highest or Lowest
Average
REM 1 Temperature Sensor
Indoor Temperature or Not Connected
Not
Connected
REM 2 Temperature Sensor
Indoor Temperature, Outdoor Temperature or
Not Connected
Not
Connected
Minimum Run Time
0 – 5 Minutes
3 Minutes
Maximum Number of Units
While in Generator Mode
1 − 6 Units
1
Touch Screen Display Brightness
10 − 100%
80%
Time Settings
Hour
1 – 12
Minute
0 – 59
AM or PM
AM or PM
Date Settings
Month
1 – 12
Day
1 – 31
Year
2000 – 2999
Sensor Calibration Values
Local Temperature
-15 – 15°F
0
Local Humidity
-15 – 15% RH
0
Remote 1
-15 – 15°F
0
Remote 2
-15 – 15°F
0
TABLE 1 (cont.)
MC5000 Series Set Points/Defaults/User Settings Record
Manual 2100-746D
Page
23 of 59