background image

Manual

2100-563

Page

35 of 40

7961-731

Comfort Mode

Press “Comfort” button once to reset to 72F/22C
Cooling and 68F/20C Heating for 1-hour. Display
will flash during override period. Press 2nd-time to
cancel during override if desired, or controller will 
automatically revert to selected SP after 1-hour.

1. To swap lead and lag units press “ADVANCE”.

2. To enter the Program mode press the 
  “Program” button and release it when “Pro9”
  appears. Use “DOWN” or  “UP” arrows to
  scroll through menu.

3. A “Flashing” display means that the function
  or choice is “Set”, and the display will alternate
  between the step function and setting.

4. To change the setting of any step press
  the “Change” button and the display will
  stop flashing, allowing change to the
  setting by using the “Down” or “Up” arrows.
  When desired setting is reached press the
  “Save” button, and proceed as desired.

5. When done programming press the 
  “Program” button until display stops flashing
  and room temperature is shown. If no buttons
  are pushed within 30-seconds the controller
  will automatically revert back to “Run” mode.

Operating Instructions

1st

Stage

2nd

Stage

Unit

#1

Unit

#2

3rd

Stage

4th

Stage

Cooling

Heating

Digital

Display

Dehumid.
Operation

Lead
Unit

1st

Stage

2nd

Stage

3rd

Stage

4th

Stage

Power Loss Sys. 1

Fire/Smoke Alarm

Low Temp. Alarm

High Temp. Alarm 1

High Temp. Alarm 2

Lead/Lag Controller

Failure Alarm

Power Loss Sys. 2

Refrig. Alarm Sys. 1

Refrig. Alarm Sys. 2

AB3000-B 

Alarm Board Functions

AB3000-A

 Alarm Board Functions

On

Off

Program

Advance

Change

Save

Comfort

Alarms

Alarm boards are optional
and can be factory or field

installed. See inside of

controller for any alarm

functions.

CLIMATE CONTROL SOLUTIONS

Solid State Dual Unit Lead Lag Controller

Series

MC4000

Program Menu

NOTE: Push and hold Up or Down arrows for 1-second

until display blanks to move between steps.

Temperature at local (main) Sensor

Temperature at Remote 1 sensor location*

Temperature at Remote 2 sensor location*

Cooling setpoint temperature

 

(65 to 90F or 18.3 to 32.2C - Default is 77F/25C)

Deadband between cooling and heating setpoint

 

(2 to 40F or 1.1 to 22.2C - Default is 17F/9.4C)

Continuous blower operation

 

(None, Lead, Both - Default is None)

Degree display    (F or C - Default is F)

Alternating Lead-Lag-Lead-Lag Sequence or

 

Non-Alternating Lead-Lead-Lag-Lag Sequence

 

(Yes or No - Default is Yes for Alternating)

Lead-Lag changeover time (Days)

 

(1 to 30 days, or 0 for disabled - Default is 7)

10 

Heat pump logic enabled - only for 1-stage

 

heat pumps and forces Lead-Lag sequence

 

and overrides a Non-Alt setting

 

(Yes or No - Default is No)

11 

Unit 1 and 2 blowers automatically both run if

 delta 

T

>

5F between any 2 connected sensors

 

(Yes or No - Default is Yes)

12 

3-minute lead unit & 4-minute lag unit off-delay enabled                (Yes or No - Default is No)

13 

Minimum of 3-minute compressor runtime enabled                        (Yes or No - Default is No)

14 

Low temperature alarm setpoint                 (28 to 65F or 21.1 to 48.8C - Default is 45F/7.2C)

15 

High temperature alarm Level 1 setpoint

 

(70F to 120F or 21.1 to 48.8C - Default is 90F/32.2C)

16 

High temperature alarm Level 2 setpoint   (70F to 120F or 21.1 to 49C - Default is 95F/35C)

17 

Inter-stage differential from Stage 1 to 2                                    (2, 3, 4, 5 or 6F - Default is 4)

18 

Inter-stage differential from Stage 2 to 3                                                (2 or 3F - Default is 2)

19 

Inter-stage differential from Stage 3 to Stage 4                                     (2 or 3F - Default is 2)

20 

Turn “On” above SP for Stage 1 Cooling                                           (+1 or +2 - Default is +2)

21 

Turn “Off” below SP for Stage 1 Cooling                                (-1, -2, -3, or -4F  - Default is -2)

 

Note: For CSon and CSoF Stage 2, 3 and 4 Cooling are automatically same as Stage 1

22 

All Heating stages are equal -/+ On & Off differential            (-1/+1 or -2/+2 - Default is -2/+2)

23 

1 or 2-stage compressor, if set to 1 the 2nd-Stage Cooling Alarm activates on Cooling Call 2

 

If set to 2 the 2nd-Stage Cooling Alarm activates on Cooling Call 3.       (1 or 2 - Default is 1)

24 

Controller is Locked. Consult building authority for further instructions.

         

*

 

r1 and r2 will display temperature only if optional remote sensors are installed.

 

If sensors are not installed these are omitted in the display sequence.  If r1 and/or r2 sensor

 

installed the MC4000 will control to the “average” of the connected sensors.

 

Consult installation instructions for additional details.

Содержание MC4000 SERIES

Страница 1: ...LID STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563 Supersedes NEW File Vol III Tab 19 Date 06 17 11 Bard Manufacturing Company Inc Bryan Ohio 4...

Страница 2: ...Close On Alarm Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC40...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...red for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should th...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm H...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor will...

Страница 14: ...art your browser enter the CB4000 s default IP address http 192 168 1 67 and hit Enter 8 The MC4000 log in page should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click...

Страница 15: ...r or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot make any changes Admin and Write authority can make...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e g...

Страница 18: ...Manual 2100 563 Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563 Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563 Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563 Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563 Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563 Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563 Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563 Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563 Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563 Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563 Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563 Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563 Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...oose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct p...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree d...

Страница 36: ...Manual 2100 563 Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563 Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563 Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563 Page 40 of 40 This page intentionally left blank...

Отзывы: