 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 3. On a call for 4th Stage
cooling the Stage 4 LED comes on solid (no delay), and
the lag unit compressor will switch to compressor Stage
2 full capacity operation.

3.

1-Stage Compressor Units with Older EIFM
Economizers (Enthalpy OD Sensor)

1

st

 stage cooling set point is the setting (SP) input into

the controller. Factory default is 77F (25C). On a call for
cooling the blower of the lead unit will come on
immediately (if not already on – See Blower Operation),
and the Stage 1 LED will blink for 10-seconds before
going solid, at which time the lead unit Y1 cooling
output turns on. If the outdoor temperature and humidity
conditions are below the set point of the economizer
control the lead unit economizer will operate instead of
the compressor. If outdoor conditions are not acceptable
for free cooling the compressor will automatically
operate instead of the economizer.

2

nd

 cooling set point is 4F (default setting, user selectable

2-6F) warmer than Stage 1. On a call for 2

nd

 Stage

cooling the blower of the lag unit is turned on (if not
already on – See Blower Operation), and the Stage 2
LED will blink for 10-seconds before going solid, at
which time the lag unit Y1 cooling output turns on. If the
outdoor temperature and humidity conditions are below
the set point of the economizer control the lag unit
economizer will operate instead of the compressor. If
outdoor conditions are not acceptable for free cooling
the compressor will automatically operate instead of the
economizer.

3

rd

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 2. On a call for 3

rd

 Stage

cooling the lead unit economizer will close and the
compressor will operate.

4

th

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 3. On a call for 4th Stage
cooling the lag unit economizer will close and the
compressor will operate.

4.

1-Stage Compressor Units with Newer
ECONWMT Economizers (See Note A)

1

st

 stage cooling set point is the setting (SP) input into

the controller. Factory default is 77F (25C). On a call for
cooling the blower of the lead unit will come on
immediately (if not already on – See Blower Operation),
and the Stage 1 LED will blink for 10-seconds before
going solid, at which time the lead unit Y1 cooling
output turns on. If the outdoor temperature and humidity
conditions are below the set point of the economizer
control the lead unit economizer will operate instead of
the compressor. If outdoor conditions are not acceptable
for free cooling the compressor will automatically
operate instead of the economizer.

2

nd

 cooling set point is 4F (default setting, user selectable 2-

6F) warmer than Stage 1. On a call for 2

nd

 Stage cooling the

blower of the lag unit is turned on (if not already on – See
Blower Operation), and the Stage 2 LED will blink for 10-
seconds before going solid, at which time the lag unit Y1
cooling output turns on. If the outdoor temperature and
humidity conditions are below the set point of the
economizer control the lag unit economizer will operate
instead of the compressor. If outdoor conditions are not
acceptable for free cooling the compressor will
automatically operate instead of the economizer.

3

rd

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 2. On a call for 3

rd

 Stage

cooling the lead unit economizer will continue to
operate as long as outdoor conditions are acceptable, and
the compressor will operate.

4

th

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 3. On a call for 4th Stage
cooling the lag unit economizer will continue to operate
as long as outdoor conditions are acceptable, and the
compressor will operate.

5.

2-Stage Compressor Units with Older EIFM
Economizers

1

st

 stage cooling set point is the setting (SP) input into the

controller. Factory default is 77F (25C). On a call for
cooling the blower of the lead unit will come on
immediately (if not already on – See Blower Operation),
and the Stage 1 LED will blink for 10-seconds before going
solid, at which time the lead unit Y1 cooling output turns
on. If the outdoor temperature and humidity conditions are
below the set point of the economizer control the lead unit
economizer will operate instead of the compressor. If
outdoor conditions are not acceptable for free cooling the
compressor will automatically operate on compressor Stage
1 partial capacity instead of the economizer.

2

nd

 cooling set point is 4F (default setting, user selectable

2-6F) warmer than Stage 1. On a call for 2

nd

 Stage cooling

the blower of the lag unit is turned on (if not already on –
See Blower Operation), and the Stage 2 LED will blink
for 10-seconds before going solid, at which time the lag
unit Y1 cooling output turns on. If the outdoor
temperature and humidity conditions are below the set
point of the economizer control the lag unit economizer
will operate instead of the compressor. If outdoor
conditions are not acceptable for free cooling the
compressor will automatically operate on compressor
Stage 1 partial capacity instead of the economizer.

3

rd

 cooling set point is 2F (default setting, user selectable

2-3F) warmer than Stage 2. On a call for 3

rd

 Stage cooling

the lead unit economizer will close and the compressor
will operate on full capacity compressor Stage 2.

4

th

 cooling set point is 2F (default setting, user selectable 2-

3F) warmer than Stage 3. On a call for 4th Stage cooling
the lag unit economizer will close and the compressor will
operate on full capacity compressor Stage 2.

Содержание MC4000 SERIES

Страница 1: ...LID STATE DUAL UNIT LEAD LAG CONTROLLER INSTALLATION INSTRUCTIONS REPLACEMENT PARTS LIST Manual No 2100 563 Supersedes NEW File Vol III Tab 19 Date 06 17 11 Bard Manufacturing Company Inc Bryan Ohio 4...

Страница 2: ...Close On Alarm Strategy 33 MC4000 Label 35 Figure 17 Parts List Description Diagram 36 Tables Table 1 Hook Up Diagram Selection 17 Table Parts List 37 Getting Other Information and Publications 3 MC40...

Страница 3: ...90B and Air Conditioning Systems FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax...

Страница 4: ...red for special applications or user preference The MC4000 can be equipped with one of two alarm boards and these can be factory installed or installed at any time in the field if so desired Should th...

Страница 5: ...The standard local temperature sensor has 12 leads and comes installed from the factory A secondary sensor is located internally on the main controller board and serves as a reference and back up sen...

Страница 6: ...Smoke and Generator interface for Controller to function Inputs Lockout 1 2 3 input from HVAC 1 Lockout 2 2 3 input from HVAC 2 Outputs Smoke Fire Form C SPDT Lockout 1 Form C SPDT Refrigerant alarm H...

Страница 7: ...ol located in the electrical control panel of the air conditioners being controlled by the lead lag controller To eliminate the 60 second blower off delay disconnect and isolate the wire that is facto...

Страница 8: ...u t a r e p m e T n A F c n o i t a r e p o r e w o l b s u o u n i t n o C h t o B d a e L e n o N e n o N g e d C r o F n i s e t a r e p o m e t s y s r e l l o r t n o C C r o F F t l A e c n e u...

Страница 9: ...conomizer 1st stage cooling set point is the setting SP input into the controller Factory default is 77F 25C On a call for cooling the blower of the lead unit will come on immediately if not already o...

Страница 10: ...default setting user selectable 2 6F warmer than Stage 1 On a call for 2nd Stage cooling the blower of the lag unit is turned on if not already on See Blower Operation and the Stage 2 LED will blink f...

Страница 11: ...operation COOLING OPERATING SEQUENCES FOR NON ALTERNATING LEAD LEAD LAG LAG CONFIGURATION Note Heat pumps cannot be operated in Non Alternating Lead Lead Lag Lag sequence Selecting Heat Pump Yes will...

Страница 12: ...mizer control If outdoor conditions are not acceptable for free cooling the compressor will automatically operate instead of the economizer 4th cooling set point is 2F default setting user selectable...

Страница 13: ...to operate and the compressor will operate on compressor Stage 2 full capacity If the compressor is already operating on Stage 1 partial capacity because outside free cooling range the compressor will...

Страница 14: ...art your browser enter the CB4000 s default IP address http 192 168 1 67 and hit Enter 8 The MC4000 log in page should appear For Vista or Windows 7 1 Open Control Panel click Network Internet 2 Click...

Страница 15: ...r or Alarm d High Temp 2 Clear or Alarm e Controller Failure Clear or Alarm SETPOINTS PAGE Note Read level authority can view this screen but cannot make any changes Admin and Write authority can make...

Страница 16: ...buttons while the controller is in the normal operating run mode 2 Press and hold the Advance Change Save button and the Up and Down arrow buttons simultaneously for 20 seconds until the display show...

Страница 17: ...C d r a o B r e w e N T M W N O C E o N r e z i m o n o c E n o i t a c i n u m m o C d r a o B r e w e N T M W N O C E r e z i m o n o c E 0 0 0 4 B C h t i w n o i t a c i n u m m o C d r a o B e g...

Страница 18: ...Manual 2100 563 Page 18 of 40 FIGURE 2 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS...

Страница 19: ...Manual 2100 563 Page 19 of 40 FIGURE 3 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS NO ECONOMIZER WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 20: ...Manual 2100 563 Page 20 of 40 FIGURE 4 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS NO ECONOMIZERS WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 21: ...Manual 2100 563 Page 21 of 40 FIGURE 5 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 22: ...Manual 2100 563 Page 22 of 40 FIGURE 6 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS...

Страница 23: ...Manual 2100 563 Page 23 of 40 FIGURE 7 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 24: ...Manual 2100 563 Page 24 of 40 FIGURE 8 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH OLDER STYLE EIFM ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 25: ...Manual 2100 563 Page 25 of 40 FIGURE 9 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 26: ...Manual 2100 563 Page 26 of 40 FIGURE 10 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS...

Страница 27: ...Manual 2100 563 Page 27 of 40 FIGURE 11 CONTROLLERCONNECTIONS 1 STAGE WA WL W A W L SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 28: ...Manual 2100 563 Page 28 of 40 FIGURE 12 CONTROLLERCONNECTIONS 2 STAGE WA S WL S SERIES AIR CONDITIONERS WITH ECONWMT ECONOMIZERS AND WITH ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 29: ...Manual 2100 563 Page 29 of 40 FIGURE 13 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER...

Страница 30: ...Manual 2100 563 Page 30 of 40 FIGURE 14 CONTROLLERCONNECTIONS HEAT PUMPS NO ECONOMIZER WITH OPTIONAL ALARM BOARD CB4000 COMMUNICATION BOARD...

Страница 31: ...hod to issue an alarm signal that the lead air conditioner is down or not delivering full capacity and that the lag air conditioner is now operating REFRIGERANT PRESSURE ALARMS Air conditioners with J...

Страница 32: ...loose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct...

Страница 33: ...oose to protect it from possible damage during installation of the wiring to main controller board and or the alarm board It is polarity sensitive and is keyed so it can only be installed in correct p...

Страница 34: ...wn If no buttons are pushed within thirty 30 seconds the controller will automatically revert back to RUN mode To reset all controller settings to the factory default values press the PROGRAM button f...

Страница 35: ...or 18 3 to 32 2C Default is 77F 25C 5 Deadband between cooling and heating setpoint 2 to 40F or 1 1 to 22 2C Default is 17F 9 4C 6 Continuous blower operation None Lead Both Default is None 7 Degree d...

Страница 36: ...Manual 2100 563 Page 36 of 40 FIGURE 17 PARTS LIST DESCRIPTION DIAGRAM MIS 2954 12 9 3 4 5 7 6 11 2 1 10 8...

Страница 37: ...o B m r a l A X X X 3 1 2 0 2 1 6 8 B d r a o B m r a l A X X X 4 2 2 0 2 1 6 8 y a l p s i D m r a l A X X X X X X 5 4 0 3 4 3 1 1 t e k c a r B t r o p p u S X X X X X 6 4 5 8 3 2 5 1 r o o D x o B...

Страница 38: ...Manual 2100 563 Page 38 of 40 This page intentionally left blank...

Страница 39: ...Manual 2100 563 Page 39 of 40 This page intentionally left blank...

Страница 40: ...Manual 2100 563 Page 40 of 40 This page intentionally left blank...

Отзывы: