Manual 2100-585B

Page 

5 of 19

DUCT WORK

All duct work, supply and return, must be properly 

sized for the design airflow requirement of the 

equipment.  Air Conditioning Contractors of America 

(ACCA) is an excellent guide to proper sizing.  All duct 

work or portions thereof not in the conditioned space 

should be properly insulated in order to both conserve 

energy and prevent condensation or moisture damage.
Refer to Table 5 for maximum static pressure available 

for duct design.
Design the duct work according to methods given by 

the Air Conditioning Contractors of America (ACCA).  

When duct runs through unheated spaces, it should be 

insulated with a minimum of one inch of insulation.  

Use insulation with a vapor barrier on the outside of the 

insulation.  Flexible joints should be used to connect 

the duct work to the equipment in order to keep the 

noise transmission to a minimum.
For model series H42, H48 and H60 a 1/4 inch 

clearance to combustible material for the first three feet 

of duct attached to the outlet air frame is required.  See 

Wall Mounting Instructions and Figures 2 and 3 for 

further details.
Ducts through the walls must be insulated and all joints 

taped or sealed to prevent air or moisture entering the 

wall cavity.
Some installations may not require any return air duct.  

A metallic return air grille is required with installations 

not requiring a return air duct.  The spacing between 

louvers on the grille shall not be larger than 5/8 inch.
Any grille that meets with 5/8 inch louver criteria may 

be used.  It is recommended that Bard Return Air Grille 

Kit RG5 or RFG5 be installed when no return duct 

is used.  Contact distributor or factory for ordering 

information.  If using a return air filter grille, filters 

must be of sufficient size to allow a maximum velocity 

of 400 fpm.

NOTE:  If no return air duct is used, applicable  

 

installation codes may limit this cabinet to    

 

installation only in a single story structure.

FILTERS

A 2-inch pleated MERV 8 is standard with each 

unit.  The filter slides into position making it easy to 

service.  This filter can be serviced from the outside by 

removing the filter access panel.

CONDENSATE DRAIN 

A plastic drain hose extends from the drain pan at 

the top of the unit down to the unit base.  There are 

openings in the unit base for the drain hose to pass 

through.  In the event the drain hose is connected to a 

drain system of some type, it must be an open or vented 

type system to assure proper drainage.

Содержание H42A2-A

Страница 1: ...PACKAGED AIR CONDITIONERS Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585B Supersedes 2100 585A Date 10 09 14 H42A2 A H48A2 A H60A2 A...

Страница 2: ...ns 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation Inst...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3...

Страница 5: ...lls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required...

Страница 6: ...es H42 H48 and H60 However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figure 2 for details...

Страница 7: ...Bracket Back View P M L O E R S S S S S T N Q B 44 I A C K 2 13 H J N Q P M L O E 44 W 5 88 F G R S S S S S T B D 7 Economizer Air Intake Hood 1 Heat Electric Filter Access Panel MIS 3625 Heater Drai...

Страница 8: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Страница 9: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 12: ...24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to exte...

Страница 13: ...arge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrig...

Страница 14: ...interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The...

Страница 15: ...echarge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screw...

Страница 16: ...139 554 80 DB 67 WB Low Side High Side 132 328 133 351 135 376 137 401 139 427 141 454 143 481 145 509 147 539 149 568 85 DB 72 WB Low Side High Side 137 339 138 363 140 389 142 415 144 442 146 470 1...

Страница 17: ...or 2 42 42 60 86 60 60 60 90 8 8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors Based on 75C copper wire All wir...

Страница 18: ...450 1405 0 2 1685 1640 1460 1415 1925 1865 1395 1355 0 3 1590 1550 1390 1345 1870 1815 1340 1300 0 4 1495 1460 1310 1270 1755 1705 1225 1185 0 5 1400 1365 1225 1185 1660 1610 1125 1085 Model Rated CFM...

Страница 19: ...Plate X Y EWM5 T 100 Economizer Temperature X Z EWM5 E 100 Economizer Enthalpy X F N A 100 Economizer DC Temperature X G N A 100 Economizer DC Enthalpy X Factory Installed Option Number Field Install...

Отзывы: