background image

Manual 2100-585B 

Page  6 of 19

Minimum Clearances Required to

Combustible Materials

MODELS

 SUPPLY AIR DUCT

FIRST THREE FEET

 CABINET

H42A, L / H48A, L

H60A, L

1/4"

0"

Clearances Required for Service Access 

and Adequate Condenser Airflow

MODELS

 LEFT SIDE

 RIGHT SIDE

H42A, H48A, H60A

20"

20"

H42L, H48L, H60L

20"

20"

NOTE: For side by side installation of two (2) H**A models there 

must be 20" between units.  This can be reduced to 15" by using 

a H**L model (left side compressor and controls) for the left unit 

and HA (right side compressor and controls) for right unit.

INSTALLATION INSTRUCTIONS

        WARNING

Failure to provide the 1/4 inch clearance 

between the supply duct and a combustible 

surface for the first 3 feet of duct can result in 

fire causing damage, injury or death.

WALL MOUNTING INFORMATION

  1. Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 2.

  2. On wood frame walls, the wall construction must be 

strong and rigid enough to carry the weight of the 

unit without transmitting any unit vibration.

  3. Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 

weight of the installed unit.

MOUNTING THE UNIT

  1. These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 

both sides.  A bottom mounting bracket, attached 

to skid for shipping, is provided for ease of 

installation, but is not required.

  2. The unit itself is suitable for 0 inch clearance, 

but the supply air duct flange and the first 3 feet 

of supply air duct require a minimum of 1/4 inch 

clearance to combustible material for model series 

H42, H48 and H60.  However, it is generally 

recommended that a 1-inch clearance is used for 

ease of installation and maintaining the required 

clearance to combustible material.  See Figure 2 for 

details on opening sizes.

  3. Locate and mark lag bolt locations and bottom 

mounting bracket location.  See Figure 2.

  4. Mount bottom mounting bracket.

  5. Hook top rain flashing, attached to front - right of 

supply flange for shipping, under back bend of top.

 6.  Position unit in opening and secure with 5/16 lag 

bolts; use 7/8 inch diameter flat washers on the lag 

bolts.

  7. Secure rain flashing to wall and caulk across entire 

length of top.  See Figure 2.

  8. For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 

and screwed or welded to the structural wall itself 

(depending upon wall construction).  Be sure to 

observe required clearance if combustible wall.

  9. On side-by-side installations, maintain a minimum 

of 20 inches clearance on right side to allow access 

to control panel and heat strips, and to allow proper 

airflow to the outdoor coil.  Additional clearance 

may be required to meet local or national codes.

10. Care should be taken to ensure that the recirculation 

and obstruction of condenser discharge air does not 

occur.  Recirculation of condenser discharge air 

can be from either a single unit or multiple units.  

Any object such as shrubbery, a building or other 

large object can cause obstructions to the condenser 

discharge air. Recirculation or reduced airflow caused 

by obstructions will result in reduced capacity, 

possible unit pressure safety lockouts and reduced 

unit service life.

  For units with blow through condensers, it is 

recommended there be a minimum distance of 10' 

between the front of the unit and any barrier or 20' 

between the fronts of two opposing (facing) units.

Содержание H42A2-A

Страница 1: ...PACKAGED AIR CONDITIONERS Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585B Supersedes 2100 585A Date 10 09 14 H42A2 A H48A2 A H60A2 A...

Страница 2: ...ns 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation Inst...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3...

Страница 5: ...lls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required...

Страница 6: ...es H42 H48 and H60 However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figure 2 for details...

Страница 7: ...Bracket Back View P M L O E R S S S S S T N Q B 44 I A C K 2 13 H J N Q P M L O E 44 W 5 88 F G R S S S S S T B D 7 Economizer Air Intake Hood 1 Heat Electric Filter Access Panel MIS 3625 Heater Drai...

Страница 8: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Страница 9: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 12: ...24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to exte...

Страница 13: ...arge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrig...

Страница 14: ...interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The...

Страница 15: ...echarge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screw...

Страница 16: ...139 554 80 DB 67 WB Low Side High Side 132 328 133 351 135 376 137 401 139 427 141 454 143 481 145 509 147 539 149 568 85 DB 72 WB Low Side High Side 137 339 138 363 140 389 142 415 144 442 146 470 1...

Страница 17: ...or 2 42 42 60 86 60 60 60 90 8 8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors Based on 75C copper wire All wir...

Страница 18: ...450 1405 0 2 1685 1640 1460 1415 1925 1865 1395 1355 0 3 1590 1550 1390 1345 1870 1815 1340 1300 0 4 1495 1460 1310 1270 1755 1705 1225 1185 0 5 1400 1365 1225 1185 1660 1610 1125 1085 Model Rated CFM...

Страница 19: ...Plate X Y EWM5 T 100 Economizer Temperature X Z EWM5 E 100 Economizer Enthalpy X F N A 100 Economizer DC Temperature X G N A 100 Economizer DC Enthalpy X Factory Installed Option Number Field Install...

Отзывы: