manualshive.com logo in svg
background image

Manual 2100-585B

Page 

13 of 19

START UP

THESE UNITS REQUIRE R-410A 

REFRIGERANT AND POLYOL 

ESTER OIL.

GENERAL:

1.  Use separate service equipment to avoid cross    

 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.
3.  Use manifold gauges rated for R-410A (800 psi/250  

 

psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.
5.  R-410A is nearly azeotropic - similar to R-22 and  

 

R-12.  Although nearly azeotropic, charge with   

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   

 

R-22, and systems designed for R-22 cannot    

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  

 

but must be reclaimed due to its global warming  

 potential.
8.  R-410A compressors use Polyol Ester oil.
9.  Polyol Ester oil is hygroscopic; it will rapidly    

 

absorb moisture and strongly hold this moisture in  

 

the oil.

10. A liquid line dryer must be used - even a deep    

 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug  

 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard 

Manufacturing recommends reclaiming, evacuating 

(see criteria above), and charging to the nameplate 

charge.  If done correctly, topping off the system charge 

can be done without problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 

recharges.  R-410A refrigerant is close to being an 

azeotropic blend (it behaves like a pure compound 

or single component refrigerant).  The remaining 

refrigerant charge, in the system, may be used after 

leaks have occurred and then “top-off” the charge by 

utilizing the pressure charts on the inner control panel 

cover as a guideline.

REMEMBER:  

When adding R-410A refrigerant, it 

must come out of the charging cylinder/tank as a liquid 

to avoid any fractionation, and to insure optimal system 

performance.  Refer to instructions for the cylinder that 

is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1.  Never mix R-410A with other refrigerants.
2.  Use gloves and safety glasses, Polyol Ester oils can  

 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the    

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the    

 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if  

 exposed.
6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.
9.  Never heat cylinders above 125°F.
10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly  

 

at warmer temperatures.  Once a cylinder or line is  

 

full of liquid, any further rise in temperature will  

 

cause it to burst.

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil 

with a dish washing detergent.

HIGH PRESSURE SWITCH

All H**A/H**L wall mounted air conditioner series 

models are supplied with a remote reset for the high and 

low pressure switch.  If tripped, this pressure switch may 

be reset by turning the thermostat off then back on again.

        WARNING

Failure to conform to these practices 

could lead to damage, injury or death.

Содержание H42A2-A

Страница 1: ...PACKAGED AIR CONDITIONERS Models INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 585B Supersedes 2100 585A Date 10 09 14 H42A2 A H48A2 A H60A2 A...

Страница 2: ...ns 19 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5 Filters 5 Condensate Drain 5 Installation Inst...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3...

Страница 5: ...lls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Some installations may not require any return air duct A metallic return air grille is required...

Страница 6: ...es H42 H48 and H60 However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material See Figure 2 for details...

Страница 7: ...Bracket Back View P M L O E R S S S S S T N Q B 44 I A C K 2 13 H J N Q P M L O E 44 W 5 88 F G R S S S S S T B D 7 Economizer Air Intake Hood 1 Heat Electric Filter Access Panel MIS 3625 Heater Drai...

Страница 8: ...1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SI...

Страница 9: ...ible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating t...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...IC SUPPLYAIRDUCT SUPPLYAIRDUCT SUPPLYAIRDUCT RETURNAIR OPENINGW GRILLE OUTSIDE W GRILLE FALSEWALLINSTALLATION CEILING RAIN FLASHING RAIN FLASHING SUPPLYDUCTMAYBELOCATEDINANATTIC ORBELOWCEILINGRAFTERSA...

Страница 12: ...24V transformer output and the R terminal is the 24VAC hot terminal for the operation of the equipment RT and R are connected with brass jumper bar which can be removed and RT and R connected to exte...

Страница 13: ...arge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrig...

Страница 14: ...interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contactor will de energize immediately The...

Страница 15: ...echarge the unit to the serial plate charge REMOVAL OF FAN SHROUD 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove screw...

Страница 16: ...139 554 80 DB 67 WB Low Side High Side 132 328 133 351 135 376 137 401 139 427 141 454 143 481 145 509 147 539 149 568 85 DB 72 WB Low Side High Side 137 339 138 363 140 389 142 415 144 442 146 470 1...

Страница 17: ...or 2 42 42 60 86 60 60 60 90 8 8 6 3 10 10 10 8 60 26 60 30 6 10 10 10 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors Based on 75C copper wire All wir...

Страница 18: ...450 1405 0 2 1685 1640 1460 1415 1925 1865 1395 1355 0 3 1590 1550 1390 1345 1870 1815 1340 1300 0 4 1495 1460 1310 1270 1755 1705 1225 1185 0 5 1400 1365 1225 1185 1660 1610 1125 1085 Model Rated CFM...

Страница 19: ...Plate X Y EWM5 T 100 Economizer Temperature X Z EWM5 E 100 Economizer Enthalpy X F N A 100 Economizer DC Temperature X G N A 100 Economizer DC Enthalpy X Factory Installed Option Number Field Install...

Отзывы: