Force Cloud Push Button
Press and hold this button for five seconds to send an immediate push message from the device (if properly
configured).
Clear Password
By default, the DXM700 does not require a password to load a configuration file. If a password is defined, the
DXM700 requires that you enter the password before uploading a configuration file.
To change the password, you must already know the current password. If you do not know the current password,
clear the password from the DXM700.
CAUTION: Clearing the password erases the current configuration and any program files, log files, or
history files currently on the DXM700.
Follow these steps to clear the password requirement from your DXM700.
1. Turn off the power.
2. Set DIP switch 4 to the ON position.
3. Press and hold the processor button.
4. Apply power to the device.
5. After leaving the device powered on for a few seconds, turn off the power again.
6. Set DIP switch 4 to the OFF position.
7. Reload the configuration file before resuming normal operation.
The password is cleared from the system.
4.1 DIP Switch Settings for the Base Board
After making changes to the DIP switch settings, cycle power to the device.
Settings
DIP Switches
1
2
3
4
Disable Ethernet Port
OFF *
ON
Disable LCD Display
OFF *
ON
Not used
OFF *
Bypass XML
OFF *
ON
Bypass XML
Turn on to have the XML file ignored at boot time. This is useful for ignoring a corrupt or questionable XML
configuration file. After the device is running, a new XML file can be loaded using the DXM configuration tool.
Turn on to stop the processor from executing defined configuration. This is useful if the loaded configuration is
using all the processing time and not allowing DXM Configuration Tool operations.
The factory default position is OFF.
Disable Ethernet Port
Set to on to power down the Ethernet interface. Disabling the unused Ethernet port reduces power consumption.
The factory default position is OFF.
Disable LCD Display
Set to on to disable the LCD. This DIP switch should be on when the LCD display board is not connected.
The factory default position is OFF.