Banner DXMR110-8K Скачать руководство пользователя страница 23

© Banner Engineering Corp. www.bannerengineering.com

20

 C

ONFIGURATION

 I

NSTRUCTIONS

When a configuration is running on the DXMR110-8K, viewing the Local Registers can help you to understand the application's operation. This 

utility can also access data from remote devices and the LED registers.

5.2.3.  Saving and Loading Configuration Files

The DXM Configuration Software saves its configuration information in a XML file. Use the 

File

 menu to Save or Load configuration files.

Save the configuration file before attempting to upload the configuration to the DXMR110-8K. The DXM Configuration Software uploads the 

configuration file saved on the PC to the DXMR110-8K; it will not send the configuration loaded in the tool.

5.2.4.  Uploading or Downloading Configuration Files

The DXMR110-8K requires a XML configuration file to become operational. To upload or download configuration files, connect a computer to the 

DXMR110-8K using the Ethernet port. Then use the 

Upload Configuration to Device

 or 

Download Configuration from Device

 under the 

Device

 menu.

5.3.  EtherNet/IP™ Configuration

The DXMR110-8K can be configured to send/receive local register data to and from an EtherNet/IP™

1

 host. EDS (Electronic Data Sheet) files 

allow users of the EtherNet/IP protocol to easily add a Banner DXM device to the PLC. Download the EDS files from the Banner website. 

DXM EDS Configuration File (for PLCs) (p/n 

b_4205242

)

DXM EIP Config File for DXM Controller with Internal Gateway (Models: DXM1xx-BxR1, DXM1xx-BxR3, and DXM1xx-BxCxR1) (p/n 

194730

)

5.3.1.  Configuring the Host PLC

On the host PLC, install the DXMR110-8K using an EDS file or by using the following parameters: 

Assembly1: Originator to DXM = Instance 112, 456 bytes (228 words)

Assembly2: DXM to Originator = Instance 100, 456 bytes (228 words)

The Originator is the host PLC system, and the DXM is the DXMR110-8K. The host system sees the DXMR110-8K as a generic device with the 

product name of 

Banner DXM

 (ProdType: 43 - Generic Device, ProdName: Banner DXM, Integer Type - INT).

 

IMPORTANT

Do not set the Requested Packet Interval (RPI) any faster than 150 ms.

5.3.2.  Configuring the Controller

Use the configuration software to define the 

Protocol conversion

 for each local register to be 

EIP Originator > DXM

 or 

EIP DXM > Originator

 

from the 

Edit Register

 or 

Modify Multiple Register

 screens.

Define a DXM local register as 

EIP Originator > DXM

 when the host PLC (Originator) will send data to the DXMR110-8K local register (DXM).

Define a DXM local register as 

EIP DXM > Originator

 when that register data will be sent from the DXMR110-8K (DXM) to the host PLC (Orig

-

inator).
Data from an EIP controller in assembly instance 112 is data destined for the DXMR110-8K local registers. The PLC is normally configured for 

INT or UINT data transfer. This allows for a seamless transfer of data.

Data from the DXMR110-8K local registers is sent to the EIP controller using assembly instance 100. Each local register in the DXMR110-8K 

defined as 

EIP DXM > Originator

 is collected in numerical order and placed into the data buffer destined for assembly instance 100. DXM local 

registers are capable of 32-bits, but only the lower 2-bytes (16-bits) for each local register are transferred.

1. EttherNet/IP is a trademark of Rockwell Automation.

 EIP Assembly Instance 112 (16-bit)

 DXM Local Registers

 Adrs

 Data

 Adrs

 Data

 0

 1122

 1

 1122

 1

 3344

 2

 3344

 2

 5566

 3

 5566

 3

 7788

 4

 7788

 4

 9900

 5

 9900

Содержание DXMR110-8K

Страница 1: ...DXMR110 8K IO Link Master Instruction Manual April 10 2023 Banner Engineering Corp All rights reserved...

Страница 2: ...tion Backup Restore Mode 16 Configuring Connected Banner IO Link Devices DXMR110 8K 16 Chapter 5 Configuration Instructions 18 Set the Controller to use Authentication 18 Set the Web Services to Use A...

Страница 3: ...ons for the DXMR110 8K 32 File System and Archive Process 33 Update Your DXM Processor Firmware Using the Configuration Software 33 DXM Support Policy 33 Firmware Updates 33 Website Information 33 Fea...

Страница 4: ...DD IODD files contain information about identification device parameters process and diagnostic data communication properties and other details The IODD files for Banner IO link devices can be downloa...

Страница 5: ...Link device 2 IOL_AUTOSTART Digital Input The IO Link port functions as a standard digital input 3 DI_C Q Digital Output The IO Link port functions as a standard digital output 4 DO_C Q 1 3 Combining...

Страница 6: ...ize cabling and associated weight especially in weight critical applications such as robotics Flexible and Customizable Expanded internal logic controller with action rules and ScriptBasic programming...

Страница 7: ...ess the DXMR110 8K using the Modbus TCP IP protocol over Ethernet Standard Modbus TCP port 502 is used by the DXMR110 8K for all Modbus TCP IP requests All internal local registers are available to th...

Страница 8: ...Corp www bannerengineering com DXMR110 8K OVERVIEW Figure 1 DXMR110 8K Dimensions 145 0 mm 5 71 91 1 mm 3 59 11 X M12 x 1 0 2 X 4 5 M12 x 1 0 30 mm 1 18 25 mm 0 98 25 mm 0 98 25 mm 0 98 25 mm 0 98 40...

Страница 9: ...igure 1 DXMR110 8K IO Link Master ports Table 1 Ports 1 8 female connector Port 1 8 5 pin M12 Connector female Pin Wire Color Description 1 Brown bn 18 V DC to 30 V DC 2 White wh I Q digital in out 3...

Страница 10: ...ware from http www bannerengineering com For more information on using the DXM Configuration Software refer to the instruction manual p n 209933 Table 3 4 pin M2 female connector 4 pin M12 Power Conne...

Страница 11: ...tion Manual p n 209933 3 2 2 Configuring the DXMR110 8K Controller This section will walk you through the method of setting up the DXM Configuration Software and communicating with a connected DXM dev...

Страница 12: ...92 168 0 1 To connect to the device you need to be on the same subnet You can do this by accessing the control panel on your PC and accessing your Network Connections properties It is important to ens...

Страница 13: ...d cannot read the data If the permissions are set to Read Write the web server can read the data from the device and write to the device from the web 5 Click Modify Registers to save and apply the cha...

Страница 14: ...ation Tool unplug and re plug in the cable and recon nect the DXM to the software If the Application Status indicator is green the file upload is complete If the Application Status indicator is gray a...

Страница 15: ...he DXMR110 8K on page 6 For more information on the device registers and port settings of the DXMR110 8K IO Link Master refer to the DXMR110 8K IO Link Master IO Link Master Device Register Map p n 23...

Страница 16: ...a that must be maintained when power is turned off This register data is stored in a data flash component that has a limited write capability of 100 000 cycles so these registers should not be used as...

Страница 17: ...of write map timeouts 22107 Number of write map errors 22108 Write map success streak 22109 Number of passthrough successes API message passing statistics 22110 Number of passthrough timeouts 22111 N...

Страница 18: ...s parameters for the IO Link ports are set in the DXM Configuration Software and are saved in the XML configuration file Each port can have unique settings Figure 2 RTU Configuration screen for ports...

Страница 19: ...Mode If a port on the IO Link master is set to Backup Restore then the new device added to the IO Link port takes in the same device configuration as the device that was just replaced as the IO Link...

Страница 20: ...17 Banner Engineering Corp www bannerengineering com CONTROLLER CONNECTIONS FOR THE DXMR110 8K Figure 3 IO Link configuration start page Figure 4 IO Link configuration to select Ethernet...

Страница 21: ...tication screen STEP RESULT The first time you select Require Authentication a pop up box appears with additional instructions Since the data is not stored in the XML configuration file it is hidden f...

Страница 22: ...When programming an application in the DXMR110 8K first plan the overall data structure of the Local Registers The Local Registers are the main storage elements in the DXMR110 8K Everything goes into...

Страница 23: ...10 8K using an EDS file or by using the following parameters Assembly1 Originator to DXM Instance 112 456 bytes 228 words Assembly2 DXM to Originator Instance 100 456 bytes 228 words The Originator is...

Страница 24: ...k Master AOI is to provide quasi realtime read write access to all IO Link parameter data in the sensor Each Param eter Data AOI is specific to a given sensor IO Link Master AOIs v2 1 These files requ...

Страница 25: ...tries a message five times The five retry attempts immediately follow each other After all attempts are exhausted the register data packet is lost At the next sched uled time the DXMR110 8K attempts t...

Страница 26: ...across a variety of tools as a standard set of device information 6 2 DXM PROFINET IO Data Model The PROFINET IO data model is based on the typical expandable field device that has a backplane with sl...

Страница 27: ...uration 6 4 Slots and Modules for DXM PROFINET There are ten slots to accommodate the DXM Controller data It is important to note that the module placed in slot 2 corresponds to Port 1 the module plac...

Страница 28: ...gister End Direction 0x4D 0x01 ISDU 190 Byte Status 196 351 442 Bidirectional 196 200 291 0x4E 0x01 ISDU 80 Byte Status 86 351 396 86 200 245 Slot Module Description Slot 1 Banner IO Link Master Info...

Страница 29: ...eering com 2 Launch the Siemens TIA Portal v14 software 3 Click Open existing project 4 Select a project and open it 5 After the project is uploaded click Devices networks Figure 2 Devices and network...

Страница 30: ...ering Corp 6 5 2 Change the Device IP Address Follow these instructions to change the IP address of the DXM device using the Siemens TIA Portal v14 software Use these instructions as a basis if you ar...

Страница 31: ...t 11 Enter the IP address 12 Right click on the device icon and select Online diagnostics Figure 7 Online diagnostics menu and screen STEP RESULT The Online diagnostics windows displays 13 Select Assi...

Страница 32: ...If the DXM is restarted after it was discovered and configured by the PLC the DXM retains the IP address that was assigned to it using the LCD or software until after the PLC discovers the DXM and ass...

Страница 33: ...SMBR90S Stainless steel bracket 4x M4 07 pemnuts B Includes 2x M4 stainless steel hex head screws and flat washers Hole center spacing A 40 B 20 Hole size A 5 4 Pin Threaded M12 Cordsets Double Ended...

Страница 34: ...ge 2 Orange 3 White Blue 6 Blue 1 White Orange 2 White Blue 3 Orange 4 Blue STP M12D 415 4 57 m 15 ft STP M12D 430 9 14 m 30 ft 4 pin M12 D code Double ended Male Model Length Style Dimensions Pinout...

Страница 35: ...Port 6 Status Red green blue on port 7 IO Link Port 7 Status Red green blue on port 8 IO Link Port 8 Status Connections Nine integral 4 pin M12 female quick disconnects One integral 4 pin M12 male qui...

Страница 36: ...ETING THIS TASK After the file load is completed reboot the device by selecting DXM Reboot DXM To verify the firmware has been updated go to Tools Reprogram Get Device Information and verify the new v...

Страница 37: ...vice IMPORTANT Por favor descargue desde www bannerengineering com toda la documentaci n t cnica de los DXMR110 8K IO Link Master disponibles en m ltiples idiomas para detalles del uso adecuado aplica...

Страница 38: ...UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGI...

Отзывы: