7.4 Power Modbus Registers
Modbus Register
Description
6071
Battery backup charging algorithm.
0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc . (default)
6081
Battery voltage (mV)
6082
Battery charging current (mA)
6083
Incoming supply voltage (mV) (solar or power supply)
6084
On-board thermistor temperature (
⁰
C)
7.5 LCD Board (Modbus Slave ID 201)
Control the four user-defined LEDs using the display board's Modbus registers. Using write maps or ScriptBasic, write the
Modbus registers shown below with 0 (off) or 1 (on). The LCD display is Modbus Slave 201.
Modbus Register I/O Connection
Modbus Register
I/O Connection
1102 : bit 0
LED 1
1104 : bit 0
LED 3
1103 : bit 0
LED 2
1105 : bit 0
LED 4
DXM100 Controller Instruction Manual
www.bannerengineering.com - Tel: 763.544.3164
49