Technical data
62
Mobile Panel 40/50 User's manual V1.80
Receptacle - Pinout
Control
cabinet cable - Wire colors
Control
device
wires
1
Gray-Pink
Stop / Emergency stop normally closed contact 1 (11)
2
Brown-Green
Stop / Emergency stop normally closed contact 2 (21)
15
White-Green
Stop / Emergency stop normally closed contact 1 (12)
16
Red-Blue
Stop / Emergency stop normally closed contact 2 (22)
18
Yellow
Button (S13)
26
Green
Button (S14)
Receptacle - Pinout
Control
cabinet cable - Wire colors Power supply wires
3
Red
+24 VDC power supply
14
Black
Ground
17
Gray
Shielding
Receptacle - Pinout
Control
cabinet cable - Wire colors
Ethernet
RJ45 connector
27
Green
Pin 3 (RX)
28
Pink
Pin 1 (TX)
29
Yellow
Pin 6 (RX\)
30
Blue
Pin 2 (TX\)
Ethernet
shield
Shielding
Shielding
Receptacle - Pinout
Control
cabinet cable - Wire colors
CAN
wires
10
White
CAN
1 High
11
Orange
CAN
1 Low
12
Yellow
CAN
2 High
13
Green
CAN
2 Low
CAN
shield
Black
Shielding
Not used on the MP40/50
Table 26: 5CAMPC.0020-10 - Cable pinout
Information:
When installing the
control
cabinet cable, make sure that it is not too loose or too tight in the
control
cabinet.
2.3.2.2.1.5 Receptacle - Drilling template
A cutout or drill hole must be made (e.g. in a
control
cabinet door) according to the following diagram to fasten
the receptacle.
Cutout
ø3
0.
1
28.6
Marking point
Outline of
Slotted nut
Figure 38: Receptacle - Drilling template