396
Standards and certifications • Requirements for immunity to disturbances (immunity)
Automation PC 620 with 945GME N270 CPU board User's Manual V 1.10
4.7 Voltage dips, fluctuations and short-term interruptions
4.8 Damped vibration
Test carried out according to
EN 61000-4-11
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
AC power inputs
Voltage dip
70% (30% reduction), 0.5 periods,
criteria B
-
AC power inputs
Voltage dip
40% (60% reduction), 5 periods,
criteria C
-
AC power inputs
Voltage dip
40% (60% reduction), 50 periods,
criteria C
-
AC power inputs
Voltage interruptions
< 5% (> 95% reduction), 250
periods, criteria C
-
AC power inputs
-
20 interruptions, 0.5 periods,
criteria A
DC power inputs
-
20 interruptions for 10 ms < UN -
15%, criteria A
Table 249: Test requirements - Voltage dips, fluctuations, and short-term interruptions
Test carried out according to
EN 61000-4-12
Limits according to
EN 61131-2
Power I/O, L to L
±1 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Power I/O, L to PE
±2.5 kV, 1 MHz, repeat rate
400/seconds, length 2 seconds,
connection lengths 2 m, criteria B
Table 250: Test requirements - Damped vibration
Содержание Automation PC 620
Страница 2: ...2 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Страница 4: ...4 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Страница 6: ...6 Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Страница 38: ...38 General information Typical topologies Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Страница 202: ...202 Technical data Individual components Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...
Страница 568: ...568 Appendix A Glossary Automation PC 620 with 945GME N270 CPU board User s Manual V 1 10 ...