![B&R 5AP92D.1505-I00 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/bandr/5ap92d-1505-i00/5ap92d-1505-i00_user-manual_460482059.webp)
Technical data
Automation Panel 9xD - Hygienic design User's manual V 1.80
59
4.1.6.2 AP93D - Features
are equipped with the following interfaces:
•
Rear USB interface
1)
Figure 6: Front and rear view without operating elements (AP93D)
4.1.6.2.1 USB interface
Panels are equipped with a rear USB 2.0 interface. This is equipped with a protective cover.
Caution!
IP66 protection can only be achieved if the USB protective cover is properly installed.
Warning!
USB peripheral devices can be connected to the USB interfaces. Due to the variety of USB devices
available on the market, B&R cannot guarantee their functionality. The functionality of USB devices
available from B&R is ensured.
Caution!
Due to the general PC specification, this interface must be handled with the utmost care with regard
to EMC, cable routing, etc.
The USB interface is available to the user for service purposes.
Information:
The USB interface on the panel takes up the USB2 interface on the link module. If the USB cable is
unplugged, the USB interface is disabled.
Depending on the transfer method (SDL or DVI operation), there are limitations regarding the transfer rate for
interfaces USB1 and USB2. For possible transfer methods, see section
.
Transfer method
USB type
Max. cable length
SDL operation mode 1
USB 1.1
40 m
SDL operation mode 2
USB 2.0
5 m
Single-touch DVI operation
USB 2.0
5 m
Multi-touch DVI operation
USB 2.0
5 m
SDL3 operation
USB 2.0
100 m
SDL4 operation
USB 2.0
100 m